HM/A 1.1, HM/A 2.1 | 9AKK107991A0084 EN Rev. A 5
—
TECHNIC AL DATA
Technical data
Operating voltage 10 – 30 V DC (supplied by the zone)
Contact load of switch S2 < 25 V AC / 2 A or
< 60 V DC / 2 A
Dimensions (W x H x D) 126 x 126 x 35 mm
Connection Screw terminals
Max. 1.5 mm²
Cable entry point
Top and bottom
rear wall
2 pcs. M20 x 1.5 mm
2 pcs. 24 x 10 mm
Weight 420 g
Degree of protection IP43
Rel. humidity 5 – 95% (non condensing)
Ambient temperature -20 to +60 °C (continuous operation, without icing)
-25 to +70 °C (max. 12 hours)
—
IMPORTANT NOTES
The Manual Call Points are built using high-quality
electronic components and materials that provide
excellent resistance to environmental conditions.
We nevertheless recommend replacing the Manual
Call Points after 10 years of continuous operation in
order to lower the risk of limited functionality due to
external influences. Ensure that these Manual Call
Points are used only with compatible Fire Alarm
Control Panels. Fire detection systems must be
checked and maintained at regular intervals in order
to ensure that they function properly.
Observe the national procedural rules and other in-
ternationally recognized fire protection technology
standards. A corresponding risk analysis should
first be performed to determine the required proj-
ect planning criteria and then updated on an ongo-
ing basis.