ABB OVRHTP Series User manual

—
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
OVRHTP series SPDs

B1 copy starts here
B2 copy starts here
B3 copy starts here WARNING
Do not HIPOT the SPD unit or the electrical system to which
the SPD unit is connected without disconnecting the SPD
unit’s conductors, including phases, neutral and ground.
Ne procédez PAS à des ESSAIS DE RIGIDITÉ DIÉLECTRIQUE
sur le SPD ou le système électrique auquel il est connecté
sans déconnecter les conducteurs des SPD, y compris les
phases, le neutre et la terre.
WARNING
The SPD warranty is voided if the unit is damaged as a
result of improper installation. Improper installation or
misapplication may result in serious personal injury or
damage to the electrical system. Read the complete
installation instructions before proceeding with installation.
La garantie du SPD est annulée si l’appareil est endommagé à
la suite d’une mauvaise installation. Une mauvaise installation,
ou utilisation, peut entraîner des blessures graves ou des
dégâts au système électrique. Lisez les instructions
d’installation en intégralité avant de procéder à l’installation.
WARNING
The equipment covered by these instructions should be
installed and serviced only by competent qualified personnel
utilizing proper safety practices and procedures. These
instructions are written for such personnel and are not
intended as a substitute for adequate training and experience
in safe procedures for this type of equipment
L’équipement couvert par ces instructions doit être installé
et entretenu uniquement par un personnel compétent et
qualifié, utilisant des pratiques et des procédures de sécurité
appropriées. Ces instructions sont rédigées à l’intention de
ce personnel et ne sauraient se substituer à une formation
adéquate et à une expérience des procédures de sécurité
pour ce type d’équipement
WARNING
Remove all power to the electrical panel before installing or
servicing the SPD. All work must be performed by licensed
and qualified personnel. Follow applicable electrical codes
and regulations for the country/location in which the unit is
being used.
Coupez l’alimentation du panneau électrique avant d’installer
ou de procéder à l’entretien du SPD. Tous les travaux doivent
être effectués par un personnel qualifié et agréé. Respectez
les codes et réglementations électriques en vigueur dans le
pays / lieu où l’appareil est utilisé.
CAUTION
Ungrounded power systems are inherently unstable and
can produce excessively high line-to-ground voltages during
certain fault conditions. During these fault conditions any
electrical equipment, including an SPD, may be subjected
to voltages, which exceed their designed ratings. This
information is being provided to the user so that an informed
decision can be made before installing any electrical
equipment on an ungrounded power system.
Les réseaux électriques non mis à la terre sont
intrinsèquement instables et peuvent produire des tensions
ligne-terre excessivement élevées dans certaines conditions
de défaut. Dans ces conditions de défaut, tout équipement
électrique, y compris un SPD, peut être soumis à des tensions
qui dépassent les valeurs nominales prévues. Cette
information est fournie à l’utilisateur afin qu’il puisse prendre
une décision réfléchie avant d’installer un équipement
électrique sur un réseau électrique non mis à la terre.
—
Guide to installation and assistance
2OVRHTP SERIES SPDS

WARNING
Check to ensure that a proper bond is installed between
neutral and ground at the transformer upstream from all
3-phase wye, 3-phase high-leg or 2-phase SPD devices. If
the transformer is not accessible, check the main service
disconnect/panel for the NG bond. Lack of a proper bond may
damage the SPD and void the warranty. Failure to provide this
bond, as required per article 250.30 of the National Electrical
Code, can result in elevated phase-to-ground source voltage
potentials. These voltages can cause damage to electrical
equipment as well as safety hazards including fire, electrical
shock, serious injury or death.
Vérifiez qu’une liaison correcte est installée entre le neutre et
la terre au niveau du transformateur en amont de tous les SPD
triphasés en étoile, triphasés en triangle ou biphasés. Si le
transformateur n’est pas accessible, vérifiez la liaison NG sur
le sectionneur / panneau de service principal. L’absence d’une
liaison appropriée peut endommager le SPD et annuler la
garantie. L’absence de cette liaison, telle que requise par
l’article 250.30 du Code national de l’électricité, peut entraîner
des potentiels de tension élevés entre la phase et la terre. Ces
tensions peuvent causer des dégâts aux équipements
électriques ainsi que des risques en matière de sécurité,
notamment des incendies, des chocs électriques, des
blessures graves ou la mort.
WARNING
Installation by persons with electrotechnical
expertise only.
WARNUNG!
lnstallation nur durch elektrotechnische Fachkraft.
AVERTISSEMENT!
lnstallation uniquement par des personned qualifiées
électrotechnique.
IADVERTENCIA!
La instalación deberá ser realizada únicamente
por electricistas especializados.
3GUIDE TO INSTALLATION AND ASSISTANCE

B1 copy starts here
B2 copy starts here
B3 copy starts here
Filter
Enclosure
Confirm that the voltage(s) and service configuration shown on the OVRHTP series product label are consistent with
the voltage and service configuration of the facility. The SPD model number can be found on the UL label affixed to
the SPD enclosure. The SPD selection can be verified by comparing the model number to the correct electrical system.
Sample model number scheme
Example of an SPD model number: OVRHTP1001201PPB1.
Please note if the model number ends with T2 the unit is compliant with UL 1283.
kA rating
Voltage
Monitoring
Model
X X X 1 2 0 1 Y YPTHRVO Z 1
Configuration
—
Table 1a: Operating voltage ranges
Model number
Unit
voltages (V)
L-N voltage
range (V)
L-L operating
voltage range (V) Configuration
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
XXX is 60, 80, 100, 120, 160, 200, 240, 300 or 400 kA per phase
Y = 4 or P
4 = Metal
P= Polycarbonate
Z= B, U or UE
B= Standard monitoring
U = Advanced monitoring
UE = Advanced monitoring and surge counter
—
Pre-installation checklist
4OVRHTP SERIES SPDS

Filter
Confirm that the environmental conditions are consistent with the following ranges:
• Ambient temperatures: Between -35 to 70 °C (-31 to 158 °F).
• Relative humidity: Between 5% and 95% non-condensing.
• Altitude: Less than 4000 m (13,000 feet).
—
Table 1b: Operating voltage ranges
Model number Unit voltages (V) L-G voltage range (V) Configuration
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
OVRHTPXXXYZ
XXX is 60, 80, 100, 120, 160, 200, 240, 300 or 400 kA per phase
Y = 4 or P
4 = Metal
P= Polycarbonate
Z= B, U or UE
B= Standard monitoring
U = Advanced monitoring
UE = Advanced monitoring and surge counter
5PRE-INSTALLATION CHECKLIST

B1 copy starts here
B2 copy starts here
B3 copy starts here
—
Figure 4: 3-phase delta, 3-wire
—
Service configurations
—
Figure 1: 1-phase, 2-wire
30–200 amp, 1-pole 1
circuit breaker
G
N
Earth
ground
XO bond
Conductors 2
furnished
with SPD
L1
L1
N
N
G
NG
L
OVRHTP
—
Figure 2: 2-phase, 3-wire
30–200 amp, 2-pole 1
circuit breaker
L1
L2
G
N
Earth
ground
XO bond
Conductors 2
furnished
with SPD
L1
N
L2
NG
L1
L2
N
G
OVRHTP
—
Figure 3: 3-phase wye, 4-wire
30–200 amp, 3-pole 1
circuit breaker
OVRHTP
Earth
ground
XO bond
B
N
CA
NG
N
G
Conductors 2
furnished
with SPD
A
B
C
G
N
ABC
30–200 amp, 3-pole 1
circuit breaker
B
CA
NG
Conductors 2
furnished
with SPD
A
B
C
G
ABC
G
Earth
ground
OVRHTP
1 Please refer to the "OCPD" chart to determine if the SPD requires an upstream breaker/fuse.
2OVRHTP 60 through 100 kA are furnished with #10 AWG leads. OVRHTP 120 through 200 kA are furnished with #6 AWG leads.
200 thorough 400 kA are furnished with #10–#4 AWG Lugs. Additionally, units with a ML, PL, or SL in part number.
—
Figure 5: 3-phase high-leg delta, 4-wire
Note: High-leg orange must be B phase
A
30–200 amp, 3-pole 1
circuit breaker
AB
BC
C
N
N
G
NG
Conductors 2
furnished
with SPD
A
C
B
G
N
Earth
ground
XO bond
OVRHTP
6OVRHTP SERIES SPDS

NOTICE
The SPD unit’s performance will be degraded if the
conductors are (a) too long, (b) are of too small a wire
gauge, (c) have too many bends or (d) have sharp bends.
Les performances du SPD seront dégradées si les
conducteurs sont (a) trop longs, (b) d’un calibre de fil
trop faible, (c) présentent trop de courbures ou (d) ont
des courbures trop prononcées.
The factors listed above should be addressed during the
design of an installation to reserve a suitable place for
the OVRHTP series unit next to its point of connection
to the electrical system. The selected mounting location
should allow for the shortest possible conductor runs
and a direct route with a minimum of bends. If bends are
required, they should be sweeping bends. Do not make
sharp 90° bends for appearance purposes because
they will decrease the effectiveness of the OVRHTP
series unit.
Binding or twisting conductors together using cable
ties or electrical tape improves the protection
performance of the device.
—
Conductors
—
Wiring color installation guide
Voltage (V) A, L1 B, L2 C, L1 Neutral Ground
Black White Green/yellow
Black White Green/yellow
Brown Blue Green/yellow
Brown Blue Green/yellow
Black White Green/yellow
Black White Green/yellow
Black White Green/yellow
Black White Green/yellow
Black Red White Green/yellow
Brown Orange White Green/yellow
Black Red Blue White Green/yellow
Black Brown Gray Blue Green/yellow
Black Brown Gray Blue Green/yellow
Brown Orange Yellow White Green/yellow
Brown Orange Yellow White Green/yellow
Black (A) Black (B) Black (C) White Green/yellow
Black Orange (HL) Blue White Green/yellow
Black Red Blue Green/yellow
Black Red Blue Green/yellow
Black Brown Gray Green/yellow
Brown Orange Yellow Green/yellow
Black (A) Black (B) Black (C) Green/yellow
Brown Blue Green/yellow
Brown Blue Green/yellow
Brown Blue Green/yellow
Brown Blue Green/yellow
Upstream overcurrent protection device (OCPD)
The OVRHTP series units can either be Type 1 or Type 2. Please refer
to the SPD types chart to determine the SPD type for the unit.
—
SPD types
Country SPD
is installed in
Polycarbonate enclosure Metal and stainless steel enclosure
UL 1283 Not UL 1283 UL 1283 Not UL 1283
United States and
all other countries
Canada
The OVRHTP series unit is a one-port SPD and is to be connected in
parallel with the electrical system. It may be connected via a circuit
breaker, molded case switch, fused switch, or connected directly to
the bus of the panelboard or switchboard (local and national electric
codes take precedence). If direct bus connection is used, ABB
recommends installing the OVRHTP series unit behind a disconnect
switch or other disconnecting means for ease of serviceability.
If the unit is Type 2, the following OCPD is recommended:
Si l’unité est de type 2, il est recommandé d’utiliser le dispositif
suivant de protection contre les surintensités:
kA
United States and all other countries
États-Unis et tous les autres pays Canada
7SERVICE CONFIGURATIONS, CONDUCTORS

B1 copy starts here
B2 copy starts here
B3 copy starts here
—
Mounting
Optional flush-mount plate can be purchased for flush-mount
assumed that the facing layer of wall board has not been
installed yet.
First, the enclosure should be mounted to the rear wall or
studs with the appropriate hardware. It should be positioned
so that when the next steps are followed, the enclosure will
project through the wall by the desired amount. Next, the
wall board should be installed. The wall board should
be installed over the SPD, so that the SPD projects through
the wall board.
CAUTION
If the SPD has become energized, it must be de-energized
now. Appropriate high voltage safety procedures should be
followed here.
The lid of the enclosure must be unscrewed. It is generally not
necessary to disconnect the monitor cables from the lid. It is
permissible to allow the lid dangle on its ground lead, so long
as the lid is gently lowered into place. The lid should be
maneuvered through the rectangular hole in the wall board.
The flush-mount plate (FMP) is placed over the SPD enclosure.
Mark the mounting hole locations through the 4 holes in the
FMP. Remove the FMP. Drill holes at the marked locations.
(These should be wide enough for the wall anchors to fit
snugly.) Push the wall anchors into the holes. Tighten the
screws that were in the wall anchors, until the wall anchors
expand against the wall board. Remove and discard the 4
screws. (The anchors will remain in place.) Place the FMP over
the SPD enclosure again. Fasten the FMP to the anchors with
the (nicer looking) truss mount screws. Fasten the lid back
onto the enclosure body. When fastening the lid, be careful
that cables do not get pinched! Now, power may be restored
to the SPD.
11.00
8.10
1.45
0.062 (4x)
8.10
11.00
1.45
.75
.75
R0.125 (4x)
.250 (4X)
9.00
6.10
1.45
0.062 (4x)
6.10
9.00
1.45
.75
.75
R0.125 (4x)
.250 (4X)
Ø0
Ø0
—
—
All measurements in inches are approximate.
8OVRHTP SERIES SPDS

—
Electrical connections
CAUTION
Prior to installation, ensure the system configuration
and voltage is equivalent to the SPD unit being installed.
Avant l’installation, assurez-vous que la configuration et la
tension du système sont équivalentes à celles du SPD en cours
d’installation.
conductor.
de conducteur neutre.
Connecting form C dry contacts
Units supplied with form C dry relay contact provide the
means for customer-supplied remote status indication
that operates in tandem with the SPD’s inherent LED status
indication. These contacts are for connection to a user-
provided remote alarm and monitoring circuit. The relay
contacts are rated maximum 1 A/30 V DC, 6 A/125 V AC.
The form C contacts come pre-wired with 914 mm (36 in.)
of #20 AWG conductors.
When input power is present on all phases, terminals “NO”
black (normally open) and “COM” white (common) are an open
circuit, and terminals “NC” red (normally closed) and “COM”
are a closed circuit. The contacts change state when the unit
has encountered failure to one or more phases.
The installer must provide the appropriate raceway and wiring
for the monitoring circuit, observing the restrictions and
conduit openings illustrated in an earlier section of this
manual.
Use butt splices within the panelboard to connect the form C
leads to the user’s monitoring circuits. Alternatively, install a
junction box between the OVRHTP series and the panelboard
to connect form C leads to user’s monitoring circuits. If the
form C contacts are not used, user has the option of either
cutting off the leads or coiling up the leads. Consult applicable
local codes to ensure proper installation.
For these models, the form C contacts must be wired
by the installer.
See terminal block cover rear view diagram for the form C
contact configuration and terminal location on the monitor
board. The annotations on the diagram match the markings
on the terminal block.
The installer must route the monitoring conductors to the
terminal blocks on the main monitoring board. Tighten screws
on terminals to 0.4 Nm (3.5 in-lb). This terminal block will
recommended.
—
Terminal block cover rear view
Contacts shown in energized normal state (no fault condition).
—
Remote monitoring
9MOUNTING, ELECTRICAL CONNECTIONS, REMOTE MONITORING

B1 copy starts here
B2 copy starts here
B3 copy starts here
—
Verification and power up
WARNING
The cover of the OVRHTP series unit along with its associated
cabling must be installed prior to applying power. The
monitoring harness contains line voltage when power is
applied to the unit.
Le couvercle du parafoudre et le câblage associé doivent
être installés avant la mise sous tension. Le faisceau de
surveillance contient la tension de ligne lors de la mise
sous tension de l’unité.
Apply power to the SPD by closing the OCPD or switch feeding
the suppressor.
Mettez sous tension le parafoudre en fermant le dispositif
de protection contre les surintensités ou l’interrupteur qui
alimente le parasurtenseur.
Upon energization of the SPD, if any of the LED(s) or alarms
indicates an abnormal condition, power should promptly be
disconnected from the SPD. The electrical system should be
inspected and the pre-installation requirements should be
validated. Do not attempt to leave power applied to the SPD,
or re-energize the SPD in the event of an alarm condition.
Please contact your local ABB representative for further
assistance.
Lors de la mise sous tension du parafoudre, si l’une des LED
ou des alarmes indique une anomalie, l’alimentation doit être
rapidement déconnectée du parafoudre. Le système électrique
doit être inspecté et les exigences préalables à l’installation
doivent être validées. N’essayez pas de laisser le parafoudre
sous tension ou de le remettre sous tension en cas d’alarme.
Veuillez contacter votre représentant ABB local pour obtenir
de l’aide.
Standard monitoring package
Verify that the indicating LED(s) are illuminated. The indicating
lights extinguish only upon failure of one or more phases
(indicating an alarm condition).
Advanced monitoring package
Verify that aII “phase protection status”indicating lights are
illuminated. The “service required”indicating light illuminates
only upon failure of one or more phases. Audible alarm should
not operate under normal conditions. The audible alarm can
be “muted”by pressing the “alarm ON/OFF”button, which
subsequently will illuminate the “alarm silenced”light.
Pressing the “alarm ON/OFF”button again will enable
the alarm.
Units with surge counter
The number of surges detected by the SPD is displayed on
an eight-digit LCD display on the front of the door. The LCD
counter is battery backed to maintain the number of surges
even during a power loss. Press the button on the lid to reset
the surge count.
NOTICE
Pressing the “Alarm ON/OFF” button when the alarm has not
triggered will prevent the audible alarm from sounding during
a failure.
En appuyant sur le bouton « Alarm ON/OFF » lorsque l’alarme
ne s’est pas déclenchée, vous empêchez l’alarme sonore de
retentir en cas de panne.
OVR HTP
Surge Protec tive Device
STATUS
Number of LEDs l it per system volta ge
1 Phase – 1 LED
2 Phase – 2 LEDs
3 Phase – 3 LEDs
Operational wh en lit green
126-0392-019
Service re quired
Alarm
On/OFF
Alarm silence d
OVR HTP
Surge Protec tive Device
STATUS
Number of LEDs l it per system volta ge
1 Phase – 1 LED
2 Phase – 2 LEDs
3 Phase – 3 LEDs
Operational wh en lit green
126-0392-020
OVRHTP
Surge Protective D evice
STATUS
Number of LEDs l it per system volta ge
1 Phase – 1 LED
2 Phase – 2 LEDs
3 Phase – 3 LEDs
Operational wh en lit green
126-0393-019
OVRHTP
Surge Protective D evice
System Alarm
Alarm silence d
Alarm
ON/OFF
STATUS
Number of LEDs l it per system volta ge
1 Phase – 1 LED
2 Phase – 2 LEDs
3 Phase – 3 LEDs
Operational wh en lit green
126-0393-020
—
with standard
monitoring
—
with advanced
monitoring
—
with standard monitoring
—
with advanced monitoring
OVRHTP
Surge Protective D evice
126-0393-023
STATUS
Number of LEDs l it per system
voltage
1 Phase – 1 LED
2 Phase – 2 LEDs
3 Phase – 3 LEDs
Operational wh en lit green
Surge counter
Alarm silenced
Service re quired
Reset
counter
Alarm
ON/OFF
—
advanced monitoring and
surge counter
10 OVRHTP SERIES SPDS

VERIFICATION AND POWER UP, SERVICEABILITY, TROUBLESHOOTING, STANDARDS AND LISTING, WARRANTY PERIOD
ABB does not provide a specific schedule for preventative
maintenance as conditions will vary based on location and
the environmental factors presented at each installation site.
However, periodic inspections should be scheduled to verify
that the SPD does not indicate a failure mode. Inspections
should also be made to check the integrity of the electrical
supply connections to the SPD to ensure continued reliable
performance.
The unit’s heavy-duty construction is designed to provide
years of uninterrupted service.
The unit contains no serviceable parts.
L’unité ne contient aucune pièce réparable.
NOTICE
In the event of an SPD alarm condition, do not attempt to
dis-assemble the SPD to replace fusing or other components.
The SPD contains thermally protected MOVs that will only
open when the SPD has failed in a non-serviceable condition.
The entire SPD must be replaced. Verify that the input power
feeding the SPD unit is energized using a voltage tester.
En cas de condition d’alarme du SPD, n’essayez pas de
démonter le SPD pour remplacer les fusibles ou d’autres
composants. Le SPD contient des MOV protégés
thermiquement qui ne s’ouvrent que lorsque le SPD tombe
en panne et ne fonctionne plus. L’ensemble du SPD doit être
remplacé. Vérifiez que la puissance d’entrée qui alimente le
SPD est sous tension à l’aide d’un testeur de tension.
—
Serviceability
The following standards and listings apply to the OVRHTP
series product line:
• UL Listed 1449 5th Edition for Type 1 and Type 2 SPD
applications, cUL and UL 1283
• Type 1 SPDs meet requirements for UL 96A
• Compliant to IEEE C62.41.1-2002, C62.41.2-2002
and C62.45-2002
• NFPA 70 [NEC], Article 242, Part II
• RoHS compliant
—
Standards and listings
OVRHTP series —10 years
—
Warranty period
LED(s) indication
Please contact ABB Technical Support if one of the following
three conditions occur:
1. One or more phase protection status indicating lights
are off.
2. System alarm indicating light is on.
3. Form C alarm contacts have changed state.
—
Troubleshooting
11

750-0122-009 C- 2.2023
—
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With regard
to purchase orders, the agreed particulars
shall prevail. ABB Inc. does not accept any
responsibility whatsoever for potential
errors or possible lack of information in
this document.
We reserve all rights in this document
and in the subject matter and illustrations
contained therein. Any reproduction or
utilization of its contents – in whole or in
parts – is forbidden without prior written
consent of ABB Inc. © 2023 ABB.
All rights reserved.
—
USA
ABB Inc.
5900 Eastport Blvd.
Richmond, VA 23231-4453
(888) 385-1221
electrification.us.abb.com/
products/surge-protective-devices
This manual suits for next models
1
Table of contents
Other ABB Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

SCHUNK
SCHUNK VERO-S NSE3-A3 138 Assembly and operating manual

Mayr
Mayr ROBA-servostop 8980.00 00 Operational instructions

Siemens
Siemens SIMATIC RTU3041C manual

Geo Knight
Geo Knight Digital Knight K20S manual

Schmalz
Schmalz FXCB Quick reference guide

Siemens
Siemens SIREMOBIL Iso-C 3D Installation and startup guide