ABB Power Express RRH User manual

Page 1
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Power Express RRH
•
•
•
•
• Lug - double-hole #10 on 5/8”centers (not provided).
• Secure lug with screws - 10-32 (provided)
Chassis Ground
150044533
J2015003L001
•1111111111111•
Jllllllllllllll'
-'---'
-
dllll
llllllllb
JIIIIII
IIIIIIII'
Read and
follow
all
safety
statements,
warnings, and precautions
in
this
guide.
Provide
unrestricted
front
to
rear
air
flow-minimum
3
inches
behind
the
shelf.
Capacitive
jumper
required
at
each load
Tools
required:
Jl
1111
11111,1,
,111
111111111111
JIIIIII
IIIIIIII'
• Cablacrimpers Sockets-
5/16,"
7
/16"
and
1/2!'
• Torquewrench
(0-240
in-lb/
28
Nm) •
Wire
cuttersandstrippers
• ScrewDrivers-
Flat
& 2Phtlllps
Step
1-
Mount
Shelf
Ensure
the
frame/rack
is
properly
bounded.
Attach
the
system
to
the
frame/rack
usinga minimum
of
4
(two
on
eachside)
12-24
screws(provided).Torque
to
35
in-lb-5/1&"socket.
Step
2 -
Connect
Chassis
Ground
wtra
• 6AWG minimum
Torque
to
10-32
screws
to
30
in-lb
(3.4Nm)
-5/16" socket.
Some
applications
may
rely
on
frame
mounting
screws
for
shelfground
omitting
the
shelf
ground
cable.

Page 2
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Secure lug with screws - 10-32 (provided)
Torque to 30 in-lb (3.4Nm) - 5/16” socket.
Note: In+ and Out + wires must be connected to DC Reference Ground (CO Ground).
• Verify that the DC Input voltage is -48VDC and matches the marked polarity using a meter on each In+ and In-.
Connections are on the rear behind a cover - 2
screws.
•
Connections are on the rear behind a cover - 2 screws.
•
Secure lug with screws - 10-32 (provided)
Torque to 30 in-lb (3.4Nm) - 5/16” socket.
Step
3 -
Connect
DC
Outputs
•
Wire-6AW
G
•
Recommen
decl
extemal
feed
protectors -50A
•
Lug•stngl
Connect
In
eachmodu
a-hole
110
(notprovided).
-
and
In+
wires
to
each
circuit
of
le.
Connect
In•wirebeforeIn+wire.
+
Connectfo111
-
Connections
____.--A
Module
A ModuleB
ModufeC
':' I
r:,
":'
l
r:1
'='
I
r.,
':' I
r:,
'='
I
r.,
OIi
r:,
':'
I
r:,
":'
I
r:,
.
~
II~I
~
II~I
~
II~I ~ II~I
~
11~1
...
~
I
~
II~I
~
II~I
.
Circuit1
CmiltZ
Cln::ult
3
Circuit
1 Circuitz Orailt:S Circuit1 OrailtZ
Step
4 -
Verify
DC
Input
Voltage
and
Polarity
Step
5 -
Connect
DC
Outputs
• Wlre-6AWGor8AWG
• Lug• single
Connect
out
eachmodu
•hole
#10
(not
provided).
-
and
out+
w1res
to
each
circuit
of
le.
Connect
out•
wtre
before
out+
wtre.
+
Connections
-
Connections
~'
Module
A ModuleB ModuleC
":'
lr.7
":'
lr:7
":'
lr.7
":'
lr:7
":'
lr.7
~
rn
":'
Im
":'
Im
".:"
II~I
".:"
11
~
I
".:"
11
~
I
".:"
II~I
".:"
11
~
I
".:"
I~I
".:"
11
~
I
".:"
11
~
I
Circuit1 Clrtultz
Cln::ult:S
0n:ult1
Cln::ult2
Clrtult3 Cln:,,,lt1 Clttult2
~
1/,
~
~
~
~
~
\:!
-!)
~
21
t
f--S
,_
...,---,_
A
If
~
,A
If
x-
¥
~
-!)
~
~
£.
Mod
ul
eA
Out
In
Out
In
+
♦
+ +
Out
Ill
Out
In
- - - -
Circuit
1 Clrcult2
ModuleD
'='
I
r:,
c:-
Ir.,
'='
I
r.,
~
II~
~
II
~
I
".:"
II~I
Clrcult3
Circuit
1 Circuitz
~
~
~
~
~
~
~
~
~
~
~
~
A
If
~
A
If
~
¥
;s
~
¥
~
~
Module
A.
Out
In
Out
In
+ + + +
Out
In
Out
In
--=-
-
--=--
-
Circuit
1 Circuit 2
ModuleO
":'
I
r
♦
,
":'
Im
":'
Im
".:"
11
~
".:"
I ~I
".:"
11
~
I
Cln::ult
3
Ortultl
Cln:ult2
Jl
1111
11111,1,
~
~
~ '
~
~
t
A
If
~
¥
~
~
Out
In
♦
+
Out
..
- -
Clrcuft3
°!'
I
r.,
~ II~
Cmilt:S
~
/f
~
'
~
~
~
~
,,;.
~
¥
~
~
Out
..
+ +
Out
..
--=--
-
Clrcult3
":'
Im
".:"
II
~
Clrtult3

Page 3
© 2021 ABB. All rights reserved.
QUICK START GUIDE
ID Switch is on the left side near the rear.
• Strip wire 3/16”
• Insert wire fully into wire entry
• Tighten screw
•
•
SW2
Alarm
•
•
•
Screw (1/16” flat screw
driver)
• Verify Module Type - use only 150045202 (PS1200DCxx) modules.
• Slide converter into its slot approximately 3/4 of the way.
•
• Slide the unit into the slot until it engages with the back of the shelf.
Swing the faceplate closed to fully seat the converter. Verify the faceplate
is latched.
•
• Turn on the DC input breakers.
• Wait until LEDs stop blinking - up to 5 minutes.
•
Step
6 -
Connect
Alarm
Cable
Remove
alarm
connectors
from
the
chassis.
Connect
alarm
cable.
Insert
alarm
connector
Into
the
chassis.
___
Open
On
Alarm•
00A
--
Common
•
COM
CloseOnAlarm-
COA
Wire
entry
28
•
16
gauge
MajorAlarm
Minor
Warning:
ShockHazard
and
Equipment
Damage-Equipment
and
subassembly
ports
are
suitable
for
connection
to
intra-building
or
unexposed
wiring
or
cabling;
canbe
connected
to
shielded
intra-building
cabling
grounded
at
both
ends.
Step
7 -
Verify
Shelf
ID
Setting
Down
is
0.
•
Shelf
ID
O•
operate
without
a
system
controller.
•
Otherwise,
Power
Shift
shelf
IDs
must
be
unique.
Step
8 -
Install
Modules
ShelflD
SWl
0
0-down
1
1-up
2
0-down
3
1-up
Open
the
faceplate
by
sHdlng
the
faceplate
latch
to
the
left
untll
the
faceplatereleasas
and
swings
outward.
Step
9 -
Initial
Start
Up
Verify
that
all
connections
are
complete
and
secure.
If
any
module
LEDs
are
not
green,
see
Information
Module
Status
LEDs
0-down
0-down
1-up
1-up
Jl
1111
11111,1,

Page 4
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Each Module has an LED for each circuit (1, 2, & 3), and one LED for the module itself.
• Intermittent or latent failures will be indicated by the X indicator.
• Some fault indications remain active after correction.
Reset the module by toggling the DC input circuit breaker for the unit.
• OK LED indicates the highest LED priority. Priority 1 is highest.
• Each Circuit LED indicates the Condition of its Circuit, independently of the other Circuits.
• Will not occur if shelf ID is 0.
X
Condition
Action
Priority1LED
Circuit External Fault See Circuit External Fault below.
Toggle DC Input breaker after action applied.
Circuit Shutdown Clear external fault. Toggle DC Input breaker.
Jl
1111
11111,1,
Information: ModuleStatus LEDs
Module
OK
LED
G
G
4 YBLINK
2 R
BLINK
1 R
y
3
y
3
1 R
Circuit
LEDr
1-
3
G
OFF
YBLINK
RBLINK
R
Module
Status
LEDs
CiraJit-
ON
-normal
Circuit
-
No
Input
Voltage
Apply
DC
Input
remains
replace
module.
Circuit-
Internal
Fault
Replace
module.
Y
Circuit
Standby
(remote)3
Turn
circuit
ON
via
controller.
lffault
GBLINK
Correct
high
ambient
temperature
and
airflowblockage
.
Toggle
Circuit
Thermal
Shutdown
DC
Input
breaker.
lffau
It
remains
or
reoccursreplace
module.
PerCircuitCondition Defective Fan
(not
immedi-
Replace
modules
ately
serviceeffecting
P Ci . C
d'
.
Module
Fail -
Any
Service Replace
module.
er
rcu,t
on
,non
effecting
Internal
Fault
5 RBLINK Per
Circuit
Condition
RS-485
Comm
Fault3
Connect
to
powered
controller.

Page 5
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Circuit External Fault - Circuit functioning properly, but not able to deliver power normally due to external cause
Possible Cause Action
•
• Specifications and ordering information are in the Power Express RRH Ordering Guide available at
abbpowerconversion.com
•
• Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an
Integrated Ground Plane (Mesh Bonding Network or Common Bonding Network).
• Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
•
These documents are available at abbpowerconversion.com
Document Title
Power Express RRH Ordering Guide

Page 6
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Safety Statements
• Do not install this equipment over combustible surfaces.
• Rules and Regulations - Follow all national and local rules and regulations when making field connections.
• Compression Connectors
• U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/Certified
field-wire conductors where required.
• All installations - apply the appropriate connector to the correct size conductor as specified by the connector
manufacturer, using only the connector manufacturer’s recommended or approved tooling for that connector.
• Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.
• Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors.
• Fuses and Circuit Breakers - Size as required by the National Electric Code (NEC) and/or local codes. Refer to the
equipment ratings to assure current does not exceed:
Continuous Load (List 1) - 60% of protector rating
Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.
• Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations .
• Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
• Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit breaker
rating.
• Size DC field-wired conductors with 90°C ampacity (NEC) equal to or greater than circuit breaker/fuse rating.
• AC and DC input disconnect/protection - Provide accessible devices to remove input power in an emergency.
• Alarm Signals - Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted.
• Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet
ac service ground bus. In huts, vaults, and central offices connect to the system bonding network.
• Circuit Breakers and Fuses - Use only those specified in the equipment ordering guide.
• GMT Style Fuses - Use only fuses provided with safety caps.

Page 7
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Precautions
• Install, service, and operate equipment only by professional, skilled and qualified personnel who have the necessary
knowledge and practical experience with electrical equipment and who understand the hazards that can arise when
working on this type of equipment.
• Disconnect batteries from outputs and/or follow safety procedures while working on equipment. Batteries may be
connected in parallel with the output of the rectifiers. Turning off the rectifiers will not necessarily remove power from
the bus.
• Do not disconnect permanent bonding connections unless all power inputs are disconnected.
• Verify that equipment is properly safety earth grounded before connecting power. High leakage currents may be
possible.
• Exercise care and follow all safety warnings and practices when servicing this equipment. Hazardous energy and
voltages are present in the unit and on the interface cables that can shock or cause serious injury. When equipped with
ringer modules, hazardous voltages will be present on the ringer output connectors.
• Use the following precautions in addition to proper job training and safety procedures:
• Use only properly insulated tools.
• Remove all metallic objects (key chains, glasses, rings, watches, or other jewelry).
• Follow Lock Out Tag Out (LOTO) procedures: customer specified, site specific, or general as appropriate.
Disconnect all power input before servicing the equipment. Check for multiple power inputs.
• Wear safety glasses.
• Follow Personal Protective Equipment requirements: customer specified, site specific, or general as appropriate.
• Test circuits before touching.
• Be aware of potential hazards before servicing equipment.
• Identify exposed hazardous electrical potentials on connectors, wiring, etc.
• Avoid contacting circuits when removing or replacing covers;.
• Use a personal ESD strap when accessing or removing electronic components.
• Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems,
including batteries and cables, typically found in telecommunications utility rooms, can affect medical electronic
devices, such as pacemakers. Effects decrease with distance.

Page 8
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Notes

Page 9
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Notes

Page 10
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Notes

Page 11
© 2021 ABB. All rights reserved.
ABB
601 Shiloh Rd.
Plano, TX USA
abbpowerconversion.com
We reserve the right to make technical changes or modify the
contents of this document without prior notice. With regard to
purchase orders, the agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for potential errors or
possible lack of information in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure
to third parties or utilization of its contents–in whole or in
parts – is forbidden without prior written consent of ABB.
Copyright© 2021ABB
All rights reserved
Table of contents
Other ABB Industrial Equipment manuals