
voltage sequence measurement functions (CMSQI and
VMSQI) and IEC 61850 generic communication I/O
functions (MVGAPC) are provided with measurement
supervision functionality. All measured values can be
supervised with four settable limits: low-low limit, low
limit, high limit and high-high limit. The measure value
expander block (RANGE_XP) has been introduced to
enable translating the integer output signal from the
measuring functions to 5 binary signals: below low-low
limit, below low limit, normal, above high limit or above
high-high limit. The output signals can be used as
conditions in the configurable logic or for alarming
purpose.
Gas medium supervision SSIMG GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v5
Gas medium supervision SSIMG is used for monitoring
the circuit breaker condition. Binary information based
on the gas pressure in the circuit breaker is used as
input signals to the function. In addition, the function
generates alarms based on received information.
Liquid medium supervision SSIML
GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v5
Liquid medium supervision SSIML is used for monitoring
the circuit breaker condition. Binary information based
on the oil level in the circuit breaker is used as input
signals to the function. In addition, the function
generates alarms based on received information.
Breaker monitoring SSCBR GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v10
The breaker monitoring function SSCBR is used to
monitor different parameters of the breaker condition.
The breaker requires maintenance when the number of
operations reaches a predefined value. For a proper
functioning of the circuit breaker, it is essential to
monitor the circuit breaker operation, spring charge
indication or breaker wear, travel time, number of
operation cycles and estimate the accumulated energy
during arcing periods.
Event counter with limit supervison L4UFCNT
GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v5
The 30 limit counter L4UFCNT provides a settable
counter with four independent limits where the number
of positive and/or negative flanks on the input signal
are counted against the setting values for limits. The
output for each limit is activated when the counted
value reaches that limit.
Overflow indication is included for each up-counter.
Running hour-meter TEILGAPC GUID-464FB24F-B367-446C-963A-A14841943B87 v2
The Running hour-meter (TEILGAPC) function is a
function that accumulates the elapsed time when a
given binary signal has been high.
The main features of TEILGAPC are:
• Applicable to very long time accumulation (≤ 99999.9
hours)
• Supervision of limit transgression conditions and
rollover/overflow
• Possibility to define a warning and alarm with the
resolution of 0.1 hours
• Retain any saved accumulation value at a restart
• Possibilities for blocking and reset
• Possibility for manual addition of accumulated time
• Reporting of the accumulated time
10. Metering
Pulse-counter logic PCFCNT M13394-3 v7
Pulse-counter logic (PCFCNT) function counts externally
generated binary pulses, for instance pulses coming
from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the
binary input module and then read by the PCFCNT
function. A scaled service value is available over the
station bus. The special Binary input module with
enhanced pulse counting capabilities must be ordered
to achieve this functionality.
Function for energy calculation and demand
handling (ETPMMTR) GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v2
Measurements function block (CVMMXN) can be used to
measure active as well as reactive power values.
Function for energy calculation and demand handling
(ETPMMTR) uses measured active and reactive power as
input and calculates the accumulated active and reactive
energy pulses, in forward and reverse direction. Energy
values can be read or generated as pulses. Maximum
demand power values are also calculated by the
function. This function includes zero point clamping to
remove noise from the input signal. As output of this
function: periodic energy calculations, integration of
energy values, calculation of energy pulses, alarm
signals for limit violation of energy values and maximum
power demand, can be found.
The values of active and reactive energies are calculated
from the input power values by integrating them over a
selected time
tEnergy
. The integration of active and
reactive energy values will happen in both forward and
reverse directions. These energy values are available as
output signals and also as pulse outputs. Integration of
energy values can be controlled by inputs (STARTACC
and STOPACC) and
EnaAcc
setting and it can be reset to
initial values with RSTACC input.
The maximum demand for active and reactive powers
are calculated for the set time interval
tEnergy
and
these values are updated every minute through output
channels. The active and reactive maximum power
1MRK 504 161-BEN C
Transformer protection RET650 2.1 IEC
ABB 19