ABB TMC User manual

16
7
.
M
.
7
-
10
PAGE
2
GROUND
FAULT
MONITOR
TABLE
OF
CONTENTS
Page
2
Page
2
Page
3
Page
k
Page
6
Page
11
Int
roduction
Precautions
Placing
Monitor
into
Service
Application
Data
Operation
Testing
INTRODUCTION
These
instructions
contain
the
information
required
to
properly
install
,
operate
,
and
test
the
Ground
-
Shield
ground
fault
test
and
monitor
panel
,
Types
TMC
and
TMS
semi
-
flush
and
surface
mounted
.
The
TMC
and
TMS
monitors
are
optional
accessories
for
use
with
the
Type
GRC
surface
case
ground
fault
relays
to
provide
operation
indicators
and
testing
features
.
Standard
features
include
:
Flush
mounting
case
.
Memory
type
operation
target
.
Lamp
,
to
indicate
availability
of
control
power
.
Relay
testing
with
or
without
tripping
of
disconnect
means
.
Sensor
testing
with
or
without
tripping
of
disconnect
means
(
Type
TMS
only
)
.
a
.
b
.
c
.
d
.
e
.
Optional
features
:
Auxiliary
contact
output
for
tripping
or
alarm
,
or
to
prevent
reclosing
of
circuit
b
reakers
.
a
.
See
Instruction
Book
IB
7.1
.
1.7
-
5
for
information
covering
the
Type
GRC
ground
relay
and
Type
GS
ground
sensors
.
The
Type
TMS
monitor
can
be
used
only
with
those
ground
sensors
that
include
a
test
winding
(
Terminal
nTn
)
.
Earlier
versions
of
the
TMC
Monitor
,
catalog
number
202
T
3010
and
202
T
321
^
(
120
VAC
/
125
VDC
dual
-
rating
)
have
slightly
different
connections
than
the
units
shown
in
this
instruction
book
.
See
"
MAINTENANCE
"
on
Page
11
or
refer
to
IB
7
*
1
*
1.7
-
&
.
See
Instruction
Book
IB
7
*
1.1
.
7
-
9
for
recommendations
for
Field
Testing
of
Ground
Fault
Systems
.
PRECAUTIONS
The
following
precautions
should
be
taken
when
applying
this
equipment
:
Incorrect
wiring
may
result
in
damage
,
gram
for
the
particular
unit
before
the
unit
is
energized
.
Be
sure
wiring
agrees
with
the
connection
dia
-
1
.
If
a
control
wiring
Do
not
apply
high
voltage
tests
to
solid
-
state
relays
or
monitors
,
insulation
test
is
required
,
bond
all
terminals
together
before
applying
test
voltage
.
2
.
I
f
a
monitor
Follow
test
instructions
to
verify
that
unit
is
in
proper
working
order
,
is
found
to
be
defective
,
we
suggest
that
it
be
returned
to
the
factory
for
repair
.
Immediate
replacement
can
be
made
available
from
the
factory
;
identify
by
catalog
num
-
We
suggest
that
a
complete
spare
unit
be
ordered
as
a
replacement
,
and
the
inop
-
erative
unit
be
repaired
and
retained
as
a
spare
.
entails
working
with
energized
equipment
,
caution
should
be
taken
to
avoid
personal
shock
.
3
*
ber
.
CAUTION
:
Since
t
roub
1
eshooting
Only
competent
technicians
familiar
with
good
safety
practices
should
service
these
devices
.
4
.
Do
not
hold
the
TEST
SWITCH
in
the
test
position
for
more
than
2
seconds
.
Courtesy of NationalSwitchgear.com

IB
7.1
.
1.7
-
10
PAGE
3
GROUND
FAULT
MONITOR
PLACING
THE
MONITOR
INTO
SERVICE
RECEIVING
,
HANDLING
,
STORAGE
1
.
Upon
receipt
of
the
unit
(
when
not
included
as
part
of
a
switchboard
)
examine
for
ship
-
ping
damage
.
nearest
BBC
Brown
Boveri
Inc
.
Sales
Office
,
damage
.
Keep
reasonably
clean
and
dry
.
the
operation
indicator
(
target
)
display
showing
orange
.
If
damage
or
loss
is
evident
,
file
a
claim
at
once
and
promptly
notify
the
Use
normal
care
in
handling
to
avoid
mechanical
The
ground
fault
monitor
is
normally
shipped
with
2
.
INSTALLATION
Mounting
The
panel
drilling
and
cutout
information
is
given
in
Figure
1
.
A
rectangular
panel
cutout
and
(
A
)
mounting
holes
are
required
.
The
outline
of
the
Type
TMC
is
shown
in
Figure
2
A
,
and
the
Type
TMS
is
shown
in
Figure
2
B
.
The
monitor
is
completely
enclosed
.
The
upper
part
of
the
front
plate
provides
space
for
user
’
s
identification
markings
of
associated
circuits
or
disconnect
means
.
If
stencil
-
ling
is
desired
,
remove
the
switch
guards
and
(
4
)
screws
(
3
inches
apart
)
to
detach
the
front
plate
.
Connections
Use
only
copper
wire
when
making
connections
.
Special
care
must
be
taken
to
connect
control
power
of
proper
voltage
and
polarity
.
See
monitor
nameplate
for
voltage
rating
.
Typical
external
connection
diagrams
of
TMC
and
TMS
monitors
and
GRC
relays
are
shown
in
Figures
3
"
6
.
AM
monitor
leads
connected
to
the
ground
fault
relay
should
be
routed
to
-
gether
.
See
Application
Data
section
for
control
and
test
power
requirements
.
Remove
the
jumper
between
relay
terminals
4
and
5
of
the
GRC
relay
when
the
is
wired
in
.
monitor
NOTE
:
IF
THE
MONITOR
IS
DISCONNECTED
OR
REMOVED
FROM
THE
CIRCUIT
FOR
ANY
REASON
,
YOU
MUST
REINSTALL
A
JUMPER
BETWEEN
TERMINALS
4
AND
5
ON
THE
GRC
RELAY
(
JUMPER
COMPLETES
TRIPPING
CIRCUIT
)
.
3
.
CONTROLS
AND
INDICATORS
The
Type
TMC
or
TMS
monitor
does
not
contain
adjustments
which
require
field
settings
.
The
following
controls
and
indicators
are
provided
:
Indicates
presence
of
control
power
.
CONTROL
POWER
LIGHT
NO
-
TRIP
SWITCH
-
Holding
the
spring
-
return
toggle
in
the
up
position
temporarily
disconnects
the
trip
coil
(
and
auxiliary
output
relay
if
provided
)
.
TEST
SWITCH
-
For
Type
TMC
,
tests
relay
with
or
without
tripping
of
circuit
breaker
.
Type
TMS
,
tests
sensor
and
relay
with
or
without
tripping
circuit
breaker
.
For
GROUND
FAULT
TARGET
-
Orange
target
indicates
relay
operation
under
ground
fault
or
test
conditions
.
Indication
is
retained
even
if
control
power
is
lost
after
operation
.
RESET
PUSHBUTTON
-
Resets
target
to
black
(
and
resets
auxiliary
output
relay
if
provided
)
.
4
.
INITIAL
CHECK
After
wiring
is
completed
and
checked
,
apply
control
power
and
note
if
lamp
is
lit
.
Then
attempt
to
reset
the
operation
indicator
.
If
the
indicator
cannot
be
reset
,
recheck
connections
,
voltage
and
polarity
.
Do
not
attempt
any
other
tests
until
wiring
errors
are
corrected
.
Courtesy of NationalSwitchgear.com

IB
7.1
.
1
-
7
-
10
PAGE
A
GROUND
FAULT
MONITOR
APPLICATION
DATA
The
Types
TMC
or
TMS
Test
and
Monitor
Panel
is
an
optional
,
flush
mounted
unit
for
use
with
the
standard
GRC
Ground
Fault
Relay
System
.
Standard
Features
include
:
1
)
A
CONTROL
POWER
LAMP
to
indicate
the
presence
of
control
power
to
the
relay
system
.
2
)
A
ground
fault
OPERATION
IN
-
DICATOR
which
maintains
indication
even
on
loss
of
control
power
.
3
)
A
TEST
SWITCH
for
perform
-
ing
an
operational
test
on
the
GRC
ground
relay
,
A
)
A
NO
-
TRIP
switch
to
prevent
the
disconnect
from
tripping
when
the
operational
test
is
performed
,
if
continuity
of
service
must
be
maintained
.
5
)
A
RESET
pushbutton
to
reset
the
target
from
orange
to
black
.
An
auxiliary
output
relay
can
be
provided
as
an
option
for
remote
alarm
or
other
purposes
.
Its
contacts
are
reset
after
a
relay
operation
by
the
RESET
pushbutton
.
TYPE
TMC
MONITOR
This
monitor
allows
testing
of
the
GRC
relay
and
the
disconnect
device
operation
.
If
the
sensor
includes
the
MT
"
Any
of
terminal
,
the
Type
GS
Ground
Sensors
may
be
used
in
this
system
,
it
must
be
jumpered
to
the
SI
terminal
.
TYPE
TMS
MONITOR
The
Type
TMS
monitor
is
provided
with
test
circuits
and
current
limiting
resistors
to
inject
a
test
current
into
the
sensor
test
winding
(
3
“
5
amperes
maximum
)
.
Thus
the
test
power
transform
-
er
should
be
sized
accordingly
to
supply
the
test
current
at
120
VAC
for
1
-
2
seconds
.
A
minimum
rating
of
250
VA
is
recommended
.
Note
that
the
monitor
test
and
control
circuits
are
isolated
,
hence
could
be
connected
to
different
sources
.
However
,
the
monitor
terminal
2
should
be
connect
-
ed
to
the
ungrounded
end
of
the
120
VAC
test
source
,
and
terminal
S
2
of
the
sensor
must
be
wired
to
the
grounded
terminal
of
the
same
source
.
Also
,
the
optional
trip
or
alarm
contacts
are
iso
-
lated
and
could
be
connected
to
another
circuit
.
The
Type
TMS
monitor
is
designed
for
use
with
Type
GS
sensors
that
have
provisions
for
test
-
ing
(
terminal
T
)
.
The
test
circuit
requires
that
the
T
-
Sl
jumper
supplied
on
the
sensor
be
removed
.
See
the
GRC
relay
instruction
book
IB
7.1
.
1.7
”
5
for
a
list
of
available
sensors
.
CONTROL
SOURCE
CONNECTIONS
The
primary
of
a
control
transformer
,
if
provided
and
supplied
from
the
power
circuit
,
must
be
connected
line
to
line
.
When
control
power
is
taken
from
the
power
circuit
ahead
of
the
main
disconnecting
means
or
from
a
separate
source
,
the
control
circuit
conductors
should
have
overcurrent
protection
,
trol
circuit
overcurrent
protective
devices
should
have
an
interrupting
rating
adequate
for
the
short
-
circuit
current
available
,
should
be
kept
as
short
as
possible
.
Con
-
Conductors
ahead
of
the
control
circuit
overcurrent
protection
RATINGS
Major
ratings
appear
on
the
front
panel
or
labels
.
See
nameplate
for
nominal
control
voltage
.
Main
Control
Voltage
:
Available
control
voltage
models
:
120
VAC
125
VDC
A
8
VDC
2
A
/
32
VDC
Monitor
must
have
the
same
control
voltage
rating
as
the
associated
GRC
relay
.
Maximum
voltage
is
nominal
plus
10
%
.
Minimum
operating
control
voltage
:
55
%
of
nominal
for
AC
monitors
,
80
%
of
nominal
for
DC
monitors
.
Negligible
on
stand
-
by
;
15
-
50
ma
on
operation
of
auxiliary
relay
.
Control
Source
Drain
:
Output
Contacts
at
125
VDC
:
5
amps
RMS
continuous
1
amp
break
(
resistive
)
0.3
amp
break
(
inductive
)
30
amps
RMS
for
0.33
seconds
12.5
amps
RMS
for
0.25
seconds
7
-
5
amps
RMS
for
1
second
Courtesy of NationalSwitchgear.com

IB
7.1
.
1.7
-
10
PAGE
5
GROUND
FAULT
MONITOR
SENSOR
TEST
SOURCE
(
Type
TMS
Only
)
:
120
VAC
(
+
10
,
-
20
%
)
Sensor
Test
Drain
:
The
test
current
provided
by
the
TMS
Monitor
must
be
related
to
the
pick
-
up
current
range
of
the
GRC
Ground
Relay
used
in
the
application
.
Resistors
in
the
monitor
are
sized
to
provide
sufficient
current
to
operate
the
particular
GRC
Relay
for
all
pickup
settings
.
See
Table
1
for
a
listing
of
TMS
Monitors
.
Table
1
also
indicates
the
range
of
current
drain
to
be
expected
for
each
model
.
The
control
transformer
must
provide
this
current
.
The
actual
value
of
current
drawn
will
depend
on
the
particular
sensor
being
used
in
the
system
and
the
line
voltage
.
TABLE
1
:
SUMMARY
OF
COMMON
UNITS
Monitor
Catalog
Number
Sensor
Test
Drain
Auxi
1
iary
Contact
For
Use
Wi
th
GRC
Range
Monitor
Type
202
T
30
x
0
202
T
30
x
4
Ai
1
TMC
No
Yes
202
T
58
x
0
202
T
58
X
4
24
A
0
.
1
-
0.2
A
TMS
2
No
Yes
0.2
-
0.4
A
60
A
202
T
57
x
0
202
T
57
x
4
No
5
Yes
202
T
56
X
0
202
T
56
X
4
20
-
240
A
0.7
-
1
A
No
Yes
202
T
55
x
0
202
T
55
x
4
3
-
5
A
100
-
1200
A
No
Yes
The
"
x
"
in
the
above
catalog
numbers
MUST
be
replaced
with
the
proper
digit
in
-
These
are
:
IMPORTANT
:
dicating
the
main
control
voltage
value
to
completely
specify
the
unit
.
4
"
for
125
VDC
"
0
“
for
24
/
32
VDC
“
6
"
for
120
VAC
3
“
for
48
VDC
1 1
1 1
Test
current
drain
shown
exists
For
the
Type
TMS
,
the
sensor
test
voltage
source
is
always
120
VAC
.
only
during
operation
of
the
Sensor
Test
(
should
be
1
-
2
seconds
in
duration
)
.
4.00
*
*
3.625
^
0.1875
0.625
1.812
1.812
i
^
(
)
4
.
I
Fig
.
Is
Panel
Cutout
for
FLUSH
MOUNTED
MONITOR
(
dimensions
in
inches
)
2.50
<
r
-
-
x
4.875
5.00
.
w
2.50
e
-
U
v O
y
'
/
t
(
4
)
0.1563
or
0.188
mounting
holes
0.0625
Courtesy of NationalSwitchgear.com

IB
7.1
.
1.7
-
10
PAGE
6
GROUND
FAULT
MONITOR
OPERATION
The
CONTROL
POWER
light
should
normally
be
lit
,
indicating
the
availability
of
control
power
.
If
it
is
off
,
control
power
fuses
or
wiring
should
be
checked
.
If
the
control
power
transformer
is
on
the
load
side
of
the
circuit
protective
device
,
the
light
will
not
be
on
until
the
discon
-
nect
is
closed
.
Should
the
light
be
burned
out
it
is
easily
replaced
.
Upon
a
ground
fault
or
a
test
operation
,
the
FAULT
indicator
will
change
state
to
orange
,
and
the
optional
auxiliary
contact
(
if
provided
)
will
pick
up
and
seal
in
.
The
GRC
Ground
Fault
Relay
'
s
thyristor
(
SCR
)
output
is
restored
to
functional
status
upon
the
opening
of
the
circuit
protective
device
auxiliary
contact
(
52
a
)
and
does
not
require
manual
reset
.
The
FAULT
target
is
a
memory
type
and
will
retain
its
indication
even
if
the
control
power
transformer
is
on
the
load
side
of
the
disconnect
,
thus
resulting
in
loss
of
control
power
upon
operation
.
The
RESET
pushbutton
resets
the
target
and
the
auxiliary
contact
(
if
provided
)
.
Reclosing
on
a
fault
may
increase
arcing
damage
;
therefore
,
it
is
recommended
that
a
ground
fault
condition
be
located
and
corrected
before
the
disconnect
is
reclosed
.
The
types
TMC
and
TMS
Monitors
allow
GRC
Relay
testing
with
or
without
tripping
the
circuit
disconnect
device
.
For
the
Type
TMS
,
actuation
of
the
TEST
switch
disconnects
one
of
several
sensor
windings
from
a
parallel
arrangement
and
connects
it
to
a
120
VAC
source
through
resistors
which
set
the
test
current
level
.
The
test
sequence
,
which
is
also
printed
on
the
front
panel
of
the
monitor
,
is
:
1 1
FOR
"
NO
-
TRIP
TEST
FOR
"
TRIP
TEST
1 1
Operate
NO
-
TRIP
switch
UP
and
HOLD
.
1
.
1
.
Operate
TEST
switch
UP
for
1
-
2
seconds
maximum
,
RELEASE
.
Operate
TEST
switch
UP
for
1
-
2
seconds
maximum
.
2
.
2
.
Press
target
RESET
button
.
RELEASE
.
RELEASE
NO
-
TRIP
switch
.
3
.
b
.
Press
RESET
button
.
If
the
relay
or
monitor
oper
-
Do
not
hold
the
TEST
switch
on
for
more
than
2
seconds
.
CAUTION
:
ation
is
improper
,
recheck
wiring
,
voltages
,
and
interconnected
devices
before
resuming
tests
.
NOTE
:
Control
power
must
be
present
to
reset
the
target
.
DOUBLE
ENDED
APPLICATIONS
To
verify
the
operation
of
the
GRC
Relay
'
s
"
No
-
Trip
"
Interlock
used
on
the
main
breakers
in
double
-
ended
applications
,
the
following
procedure
may
be
used
:
close
the
interlocking
device
or
the
tie
circuit
breaker
,
or
temporarily
short
circuit
GRC
Relay
terminals
9
and
10
.
Perform
the
TRIP
TEST
.
The
relay
should
NOT
trip
.
If
terminals
9
and
10
were
shorted
to
run
the
test
,
BE
SURE
to
remove
the
short
at
the
end
of
the
tests
.
Courtesy of NationalSwitchgear.com

I B
7.1
.
1.7
-
1 0
PAGE
7
GROUND
FAULT
MONITOR
3
4
»
(
4
)
DIA
.
MTG
.
HOLES
6
-
32
HARDWARE
16
5
4
*
16
<
>
TB
2
7
8
9
10
II
12
3
5
=
O
8
7
3
i
16
]
AI
8
4
=
8
12
3
4
5
6
^
uL
-
\
cr
\
h
.
“
Ui
irnrju
T
TBI
fo
i
a
4
32
I
21
'
I
3
k
4
k
2
2
32
REAR
VIEW
SIDE
VIEW
FRONT
VIEW
FIGURE
2
A
:
TMC
MONITOR
OUTLINE
Al
1
Dimensions
In
Inches
HEAT
SINK
*
3
6
-
32
HAROWARE
<
4
)
(
^
DIA
.
MTG
.
HOLES
5
4
16
Tfl
V
}
ib
'
(
I
F
*
s
*
F
r
0
TB
2
7
8
9
1 0
I
M
2
I
3
]
o
8
7
3
i
16
o
1
7
4
i
]
8
4
k
a
1 2
3
4
5
6
JL
c
TBI
"
,
«
1
.
1
13
i
:
-
*
4
l
<
-
32
I
31
3
i
«
•
—
2
~
2
32
4
«
REAR
VIEW
SIDE
VIEW
FRONT
VIEW
FIGURE
2
B
:
TMS
MONITOR
OUTLINE
Courtesy of NationalSwitchgear.com

IB
7.1
.
1.7
-
10
PAGE
8
GROUND
FAULT
MONITOR
GRC
RELAY
-
TMC
MONITOR
INTERCONNECTION
DIAGRAMS
Notes
for
Figures
3
and
4
:
If
terminal
T
is
provided
on
the
type
GS
sensor
,
jumper
J
(
T
-
$
1
)
is
required
.
Wiring
of
earlier
versions
of
the
TMC
,
catalog
numbers
302
T
3010
and
302
T
3214
,
is
slightly
different
than
shown
below
.
1
.
2
.
See
note
under
MAINTENANCE
on
Page
11
.
ItO
VAC
1
DOUBLE
-
CM
)
*
*
"
-
1
I
,
—
li
-
ne
CD
sue
I
I
I
A
IK
.
I
&
1
9
n
l
7
TJjg
,
In
BftC
C
K
r
~
n
N
z
1
.
.
K
I
?
'
9
'
V
I
THY
I
52
110
4
T
~
•
t
No
-
nr
;
'
J
"
i
(
PIE
i
S
2
TEST
tv
,
*
*
I
i
x
-
’
Is
SENSOR
9
mart
-
a
s
6
PS
112
I
J
?
—
—
-
O
—
NO
-
TRIP
SW
4
t
-
-
Ai
<
£
=
0
—
0
I
I
2
OPTIONAL
I
-
L
MB
-
L
S
2
A
A
S
C
k
LOAD
i
*
FIGURE
3
:
GRC
/
TMC
with
120
VAC
Control
Power
I
I
TC
)
52
B
0
RD
HO
DC
CONTROL
PWR
.
T
OOUBLE
—
ENO
II
SUB
TIE
CB
A
-
o
9
V
-
91
—
L
.
CS
T
B
5
-
6
1
l
7
TMC
6
RC
I
,
.
C
=
K
O
N
T
.
.
K
I
)
)
)
Q
'
Q
'
O
'
0
=
K
THY
I
52
110
4
r
~
T
J
-
<
NO
-
TRIP
;
:
„
’
'
sw
I
SI
(
pm
i
K
52
TEST
t
\
>
s
*
I
i
SENSOR
I
e
4
,
o
<
?
RESET
e
6
i
12
I
PS
NO
-
TRIP
$
W
4
*
-
<
2
=
0
—
0
I
2
OPTIONAL
-
L
52
A
-
L
52
B
A
B
C
N
LOAD
FIGURE
4
:
GRC
/
TMC
wi
th
DC
Control
Power
i
•
0
I
I
TC
)
52
B
TC
)
S
2
A
<
-
)
Courtesy of NationalSwitchgear.com

120
VAC
52
Q
DOUBLE
-
END
11
-
TIE
CB
SUB
i
I
I
A
l
9
9
|
3
JU
CS
.
V
B
1
T
5
~
6
1
6
RC
C
7
S
=
S
=
K
r
*
?
1
N
i
1
I
K
I
o
I
i
i
I
30
O
)
)
)
Q
'
O
'
O
'
CRT
0
=
=
K
THY
I
I
30
52
m
REMOVE
T
-
SI
LINK
>
I
4
110
-
<
r
-
1
250
VA
T
OR
-
I
N
0
-
TR
1
P
]
l
-
H
SI
2
CD
I
LARGER
(
y
c
-
o
-
SENSOR
302
L
to
30
K
o
2
c
:
^
5
C
^
A
.
0
T
\
>
sw
2
o
z
TEST
I
z
o
I
H
T
|
le
>
o
c
:
30
ft
V
OR
R
|
SET
jq
z
8
6
302
T
2
I
2
l
J
?
—
-
O
NO
-
TRIP
SW
o
m
z
30
4
o
0
?
r
?
:
O
o
z
z
30
I
l
m
o
OPTIONAL
1
o
z
-
L
52
B
-
L
52
A
A
B
C
N
LOAD
o
0
0
>
a
30
1
>
2
t
/
>
TC
)
526
TCJ
52
A
#
GRD
GO
FIGURE
5
:
GRC
/
TMS
WITH
120
VAC
CONTROL
AND
120
VAC
TEST
POWER
-
o
—
>
•
cry
*
^
1
m
1
vo
©
Courtesy of NationalSwitchgear.com

120
VAC
TEST
PWR
.
{
+
)
DC
CONTROL
PWR
.
52
a
DOUBLE
-
END
II
—
TIE
CB
SUB
A
91
CS
9
B
"
I
T
5
ii
ir
i
6
RC
C
TMS
II
7
K
O
t
N
T
x
I
K
I
I
0
)
0
)
0
)
0
/
0
'
0
'
0
CPT
K
THY
I
I
52
lie
REMOVE
T
-
Sl
LINK
I
4
110
r
-
T
250
VA
-
1
NO
-
TRIP
i
>
I
T
-
SW
ill
OR
GC
SI
I
I
o
LARGER
(
¥
'
^
-
o
-
SENSOR
302
L
z
t
\
3
S
*
£
TEST
o
I
5
z
:
I
8
3
ft
<
9
OR
Ll
_
8
6
302
T
|
9
I
NO
-
TRIP
SW
jr
—
PB
o
-
O
z
3
4
o
M
-
0
cc
o
I
OPTIONAL
-
1
-
52
A
-
L
52
B
A
B
C
N
LOAD
a
a
I
(
rc
)
52
A
(
TC
)
52
B
(
-
)
o
#
GRD
i
r
»
»
•
o
FIGURE
6
:
GRC
/
TMS
WITH
DC
CONTROL
POWER
AND
120
VAC
TEST
POWER
r
*
.
ui
o
00
<
—
a
.
Courtesy of NationalSwitchgear.com

IB
7.1
.
1.7
-
10
PAGE
11
GROUND
FAULT
MONITOR
TESTING
I
.
MAINTENANCE
AND
RENEWAL
PARTS
No
routine
maintenance
is
required
on
the
monitor
.
Follow
test
instructions
to
verify
that
the
unit
is
in
proper
working
order
.
We
recommend
that
an
inoperative
unit
be
returned
to
the
factory
for
repair
.
The
control
power
indicating
lamp
is
a
plug
-
in
device
.
Replacement
lamps
may
be
order
-
ed
from
the
factory
.
The
pins
on
the
lamp
must
be
properly
aligned
when
reinstalling
in
the
socket
.
If
you
are
replacing
an
earlier
,
dual
-
rated
{
120
VAC
/
125
VDC
)
version
of
the
TMC
Monitor
{
Catalog
#
202
T
3010
or
202
T
3214
)
with
the
present
design
TMC
covered
by
this
instruc
-
tion
book
,
all
connections
are
the
same
EXCEPT
the
wire
on
terminal
9
of
the
older
unit
moves
to
terminal
2
of
the
new
unit
.
Note
:
2
.
HIGH
POTENTIAL
TESTS
If
a
control
wiring
insulation
Do
not
apply
high
voltage
tests
to
solid
-
state
circuits
,
test
is
required
,
bond
all
terminals
together
before
applying
test
voltage
.
3
.
TESTING
Periodic
testing
is
recommended
to
confirm
proper
system
operation
.
Ope
rationa
1
Tests
Refer
to
"
OPERATION
"
section
,
Page
6
.
in
open
position
,
providing
control
and
test
power
is
available
,
additional
recommendations
on
Field
Testing
of
Ground
Fault
Systems
.
Bench
Tests
(
with
Type
GRC
Relay
)
If
bench
tests
are
desired
,
we
recommend
that
the
monitor
be
tested
with
a
type
GRC
surface
case
relay
interconnected
as
shown
in
Figure
3
to
6
,
as
appropriate
.
Follow
the
instructions
in
the
"
OPERATION
"
section
,
Page
6
.
To
apply
current
signals
to
the
GRC
relay
use
the
test
circuits
shown
in
Instruction
Book
IB
7.1
.
1.7
-
5
,
including
a
type
GS
sensor
.
Bench
Tests
(
without
Type
GRC
Relay
)
If
a
relay
is
not
available
and
a
target
or
auxiliary
relay
operation
test
is
necessary
,
connect
the
monitor
to
an
appropriate
control
power
source
as
shown
in
Figure
7
-
Operate
and
hold
the
TEST
switch
,
then
depress
the
external
test
pushbutton
momentarily
to
short
circuit
terminal
7
to
terminal
8
.
Target
shall
operate
and
auxiliary
relay
(
if
provided
)
will
pick
up
.
Release
TEST
switch
and
operate
RESET
button
,
if
repeating
tests
.
Continuity
of
test
circuits
in
monitors
can
be
checked
by
means
of
an
ohmmeter
across
terminals
2
and
9
(
Type
TMS
)
or
8
and
2
(
Type
TMC
)
.
Operate
the
TEST
switch
to
take
a
read
-
i
ng
.
Tests
can
be
performed
with
the
circuit
breaker
Also
see
IB
7
-
1
.
l
-
7
'
9
for
Leave
the
target
in
the
orange
position
after
finishing
bench
tests
and
prior
to
instal
-
lation
in
switchboard
.
INITIAL
CHECK
1
Refer
to
section
,
Page
3
•
fO
R
TMS
t
I
/
FUSE
I
'
+
)
OR
AC
!
1
T
c
l
I
I
EXTERNAL
PUSH
-
BUTTON
+
H
CONTROL
POWER
SOURCE
(
PER
NAMEPLATE
)
OHMMETER
(
m
rz
?
DIODE
BRIDGE
I
:
s
0
8
I
I
MONITOR
012
2
I
4
I
I
ft
I
(
-
)
OR
AC
2
I
i
—
i
FOR
—
'
\
TMC
BENCH
TEST
WIRING
FOR
CHECKING
MONITOR
WITHOUT
GRC
RELAY
FIGURE
7
:
Courtesy of NationalSwitchgear.com
This manual suits for next models
1
Other ABB Monitor manuals

ABB
ABB 8242 User manual

ABB
ABB 9438 User manual

ABB
ABB Endura AZ20 series Operating manual

ABB
ABB AV410 User manual

ABB
ABB Industrial enabled Analyzer 9437 User manual

ABB
ABB M2238 Series User manual

ABB
ABB Endura AZ25 Series User manual

ABB
ABB CEM11-FBP.35 User manual

ABB
ABB 8232 User manual

ABB
ABB IRC5 Compact User guide