www.abelko.se
automatically get network settings. After a while, you can see which IP
address it received. You can use this IP address to access the device
from a PC, connected to the same network.
HTTPS
The rst time you log in to an Ultra, you will be warned that the connection is
not secure, or similar. This is because the HTTPS protocol ensures a secure and
encrypted connection. The security is guaranteed by a certicate, which needs
to be issued for a specic IP number. Since the IP address is and needs to be
congurable, there is no signed certicate for the unit.
You need to accept and add this exception. The procedure diers depending on
which browser you are currently using. The communication is still encrypted, so
no-one can see, for example, which passwords are being used.
Grapical programming
Graphical programming is available as an installable program. Download it at
www.abelko.se
There is also a link to the program in your units user interface under
Conguration and Graphical programming.
Analog outputs
There are four analog outputs for 0-10 V, marked AO.The gure below is an
example on how you can connect an AC-powered valve controller.
Digital outputs
There are three digital outputs, marked DIGITAL OUT. They are normally
open relays with breaking capacity of 250 VAC/2A or 30 VDC/2A with resistive
load.
Temperature sensor inputs
There are six inputs for resistive temperature sensors, marked with T. They
have a measurement range of 800 to 1600 Ohms and works for example with
PT1000 sensors (approximately -50ºC to 150ºC) and Ni1000 sensors.