www.abelko.se
Power supply
UltraBase30 is powered by 24 V DC, through the terminal marked +24V and
GND.
Requirements and characteristics of the unit’s inputs and outputs can be found
in the table below.
Port Supply
Supply expansion
module (port Ex)
+24V/GND 24 VDC* (>300 mA) 24 VDC, 1A
* Stabilized DC voltage.
The Power LED lights up when the device is energized and the Status LED
lights up when the device has started up and is working.
Safety instructions
All external equipment connected to the device must have double or
enhanced isolation (class II) from power mains or other dangerous
voltage source (>50 VAC or > 75 VDC).
Note that all cables used must be approved for at least 50 °C ambient
temperature.
At high ambient temperatures there is a risk for burning injuries. Wait
for the equipment to cool down, and use protective gloves.
Network connection
The unit is connected to a permanent network by the Ethernet port. The
factory default IP address is 10.0.48.94.
Local PC is used only to connect the unit directly to a PC. It has IP address
192.168.142.1, and can be used to congure the regular network connection
in the UltraBase30.
When you use the Local PC port, the computer should be congured for DHCP
(which it usually is).
1. Open a web browser and enter the IP address https://192.168.142.1 in
the address bar. This will take you to the login page.
User name and password the rst time you log in:
User name: cong
Password: ef56
2. Go to the menu Communication and Network, and set the IP
address and netmask, in order to congure the settings for the port
marked Ethernet.