AccuEnergy Acuvim-L Series User manual

• Appearance and Dimension
• Installation Method
• Terminals
• Wiring Diagram
• Settings Mode
• Communication
• I/O Options
• Time of Use
• DIN Rail Installation
• Specification
Acuvim-L Series
Quick Setup Guide

1
Appearance and Dimension
Units: mm(inches)
Gasket
91.00 (3.583)
35.90
(1.413)
50.70 (1.996)
96.00 (3.800)
96.00 (3.800)
91.00 (3.583)
35.90
10.00
(0.394) 14.00
(0.551)
35.90
91.00 (3.583)
38.00 (1.496)
7.60 (0.300)
(1.413) (1.413)
50.70 (1.996)
Front View of the Display Meter and
Remote Display Unit
Gasket
Side View of the
Display Meter
Side View of the Remote
Display Unit
Side View of the DIN
rail Meter
Acuvim-L
Multifunction Power Meter
H P E V/A

2
Part Name Description
LCD Display Large bright white backlight LCD display.
Front Casing Visible portion (for display and control) aer mounting
onto a panel.
Key Four keys are used to select display and set.
Enclosure The Acuvim-L series meter enclosures is made of high
strength anti-combustible engineering plastic.
DIN rail Used for Installation 35mm rail of the DIN rail Meter.
Voltage Input Terminals Used for voltage input.
Current Input Terminals Used for current input.
Power Supply Terminals Used for aux. power supply input.
Communication Terminals Communication output.
Interface Used for link the remote display unit and the DIN rail
meter.
Installation Clip Used for fixing the meter to the panel.
Gasket Insert the gasket in between the meter and the cutout
to cover up gaps from the round hole.
Rear View Rear View of the Remote
Display Unit
Installation Clip

3
Installation Method
Environment
Make sure meter is installed in a dry and dust free environment. Avoid placing meter
near to heat, radiation and strong electrical interference sources. Meter's working
temperature range is from -25°C to 70°C.
Meter can be installed into an ANSI C39.1 (4'' round) or an IEC 92mm DIN(square)
form.
Installation Steps
1. Meter Installation
(1) Cut a square or a round hole on the panel. Units: mm(inches)
Cu ttin g
Cutting
Panel
Panel
101.6
(4.000)
+0.5
-0.0
92.00
(3.622)
+0.5
-0.0
92.00
(3.622)
+0.5
-0.0
Cutting

4
(2) Remove installation clips from the meter and insert the meter into the square or
round hole from the front side.
Gasket
Gasket
Panel
Panel

5
2. Extend module Installation
(1) The extend module could be installed from the bottom of the meter.
(2) The extend module is fixed on the meter by the screw.
Note: The display meter and the remote display unit have the same installation
method. The DIN rail meter have a quite other installation method, it must be
installed on the 35mm rail. You can references the others DIN rail meters for the
details installation method.
Panel
(3) Install the clips to the meter from backside and push the clips tightly so that the
meter is fixed on the panel.

6
Terminals
Terminal strips
Voltage Input Power Supply
Current Input
Communication and Digital Output
Note: Model Acuvim-AL has no digital output and communication terminal strips,
Model Acuvim-BL/CL/DL/EL/KL share the same strips. When the Acuvim-BL is
selected, the strips is used as DO. When Acuvim-CL/DL/EL/KL would be selected, the
strips are used for communication.
Comm Port
AB S
14 15 16
Digital Output
DO 1 DO 2 DOC
14
15 16
Power Supply
1211
N/–L/ +
13
7 8 9
V1V2V3
10
VN
I
11
I
12
I
21
I
22
I
31
I
42
1 2 3 4 5 6
!
32 41
17 18
I I

7
Extend module
The meter has 2 current input options available for dierent applications.
1. Standard: 5Aac
2. Optional: 1Aac
Ground Terminal Connection
Before setting up the meter's wiring, please connect the meter's ground terminal and
the switch gear's ground terminal together.
Auxiliary Power
The meter has 2 auxiliary power supply options available for dierent applications
(aux. power supply terminals are 11, 12, 13).
1. Universal (standard): 100~415Vac, 50/60Hz; 100~300Vdc
2. Low Voltage DC Power: 20~60Vdc
Please make sure the right type before powering up the meter.
Comm Port Digital Output Digital Input
S B A DO11 DO12 DO21 DO22 DI1 DI2 DI3 DI4 DIC

8
Wiring Diagram
The following shows two typical wiring input configurations:
Please refer to Acuvim-L user's manual section 2.3 for other wiring configuration
details.
Settings Mode
Meter Settings
Press V/A and H together to enter the meter setting screen. Press “H” to move the
flashing cursor to the right, press “P” to decrease the number by 1 once a time, press
“E” to increase the number by 1 once a time, press “V/A” to accept the change and
move to the next screen. Before accessing the parameter setting mode, a four digit
password is required every time. The default password is 0000. The below fig would
show the pass page.
3 phase 4 wire(3LN, 3CT) 3 phase 3 wire(2LL, 3CT)

9
In the basic parameter setting mode, by setting the correct meter address,
communication baud rate and parity (Acuvim-CL/DL/EL/KL only), we can
engage in normal communication. The connection mode by setting the voltage,
current connection mode, the voltage transformation ratio PT1, PT2, the voltage
transformation ratio CT1, CT2 in order to achieve accurate measurement of the basic
amount. Please refer to the specific setting "Acuvim-L User's Manual".
Communication
The meter has a standard RS485 communication port when the meter type is
Acuvim-CL/DL/EL/KL. The meter supports dual communication which means the
RS485 serial communication can be used together withother RS-485 in extend
module when the Acuvim-CL/DL/EL selected.
Serial communication terminals are A, B, S (14, 15, 16). A is dierential signal+, B is
dierential signal – and S is shield. Up to 32 devices can be connectedon a RS485
bus. The overall length of the bus cannot exceed 1200m (4000ft). When multiple
meters are connected serially on the same RS485 bus, each meter shall have a
different device address. Enter basic parameter setting page to set the device
address. This address can be any integer between 1 and 247.
Baud rate can be selected from one of the six values: 1200, 2400, 4800, 9600, 19200
and 38400 bps. Parity needs to set one of the followings: Odd, Even, None1 (stop bit 1),
None2 (stop bit 2).
I/O Options (if equipped)
Two types of IO modules with dierent IO combinations are available.
IO parameters can be set or viewed either from the meter front or through
communication using utility software. Please refer to Acuvim-L user's manual for
operation details.
Digital Input (DI)
DI is a dry point, no external power supply. DI can be used as pulse counter, to
monitor switch status or to monitor sequence of events.

10
Time of Use (Acuvim-EL only)
Acuvim-EL has time of use (TOU) function and can be set via meter’s utility soware
through communication. User can assign up to 4 dierent taris (sharp, peak, valley
and normal), 12 TOU seasons, 14 TOU schedules and 14 TOU segments according to
billing requirements. The meter will calculate and accumulate energy to dierent
taris according to the meter’s internal clock timing and TOU settings. Please refer
to Acuvim-L user’s manual for more details.
DIN Rail Installation
Except the LCD display and the front panel control keys, the meter with DIN rail
mount option includes the same functions as the panel mount version. The default
device address, the default baud rate and the default check of the DIN rail meter are
1, 9600 and NON1. Those default values will always be used for the first minute aer
the meter is powered on. The device address, the baud rate and the default check of
the meter will change to the user defined values aer the first minute.
90.00 (3.543)
55.60 (2.189)
19.50 (0.768)
Unit: mm (inches)
Digital Output(DO)
Two modes available: alarm output, energy pulse output. two modes could be used
independently in one module. The alarming mode and energy pulse mode can be
set from the utility soware or from the meter front soware.

Power Supply
Power supply 100~415Vac, 50/60Hz; 100~300Vdc
Power consumption 3W@230Vac
Withstand 3250Vac, 50/60Hz 1min
Altitude 2000m
24DC Auxiliary Power Supply
Operating Range 24Vdc
Nominal consumption 1W
Isolation voltage 1000V
Voltage Input
Nominal Full Scale
400LN/690LL Vac RMS (3-phase)
400LN Vac RMS (single-phase)
With 20% overage (3LN or 2LN wiring)
Installation Category III, Pollution Degree 2
Metering Frequency 45~65Hz
Overload 2 times(continuously); 2500Vac per second (no recurrence)
Voltage range through PT 1000KV highest at primary side
PT burden <0.2VA
Measuring True-Rms
Accuenergy Corporation
Los Angeles-Toronto-Beijing
North America Toll Free: 1-877-721-8908
Web: www.accuenergy.com
Document#1030E3301 Revision Date: Nov., 2015
Specification
Current Inputs
Current rating 5Amp AC (1Amp AC Optional)
Current range 50000A highest at primary side
Overload 10A
CT Burden
Measuring True-Rms