
LONG TERM STORAGE
When storing the DPMU for long periods of time:
Check all systems and interior/exterior lighting for proper performance
Thoroughly clean, disinfect all interior surfaces, accessories, parts, etc. – use flooring cleaners
approved for vinyl flooring.
Allow interior and all items to dry completely before sealing door
Check that all inventory is present and properly stowed
Close and lock refrigeration door and transport doors
Check and perform all required generator and refrigeration unit maintenance
Add appropriate amount of diesel fuel additive designed specifically for long-term storage to
generator fuel tank and run generator for 5 minutes (minimum)
Make any repairs as necessary
NOTE: When storing outside, shore power is not required The battery will be maintained by means of a
rooftop solar panel battery charger
If storing without plugging into shore power, immediately after positioning, inspect and clean the rooftop
solar panel battery charger. Check and clean every 30 days (minimum). Keep free from debris and shade.
If storing while plugged into shore power, simply plug unit in and ensure AC circuit breakers are in the ON
(up) positions and the refrigeration unit is turned OFF.
Start and run generator and refrigeration unit for a minimum of 20 minutes every 30 days
NOTE: Long-term storage and maintenance services are available by calling Acela at (800) 940-
0508
TROUBLESHOOTING
DPMU is plugged in, and/or generator is running, power light is illuminated but no power is being
supplied to refrigeration unit – Check that 240VAC circuit breaker is in the ON position. Check again
that refrigeration unit has power by turning the refrigeration unit ON at the control head. Probe switched
side of AC circuit breaker – if no power then check transfer switch and circuit breaker.
DPMU is plugged in but power light is not illuminated – Check for AC power by probing inputs to the
transfer switch or checking that the cooling fan inside the power distribution box is running. If DPMU
has AC power, check for faulty light.
Generator is running but power light is not illuminated - Check for AC power by visually confirming that
the cooling/exhaust fan inside the power distribution box is running or by probing inputs to the transfer
switch. If AC power is detected, check for faulty light or broken wire. If no AC power is detected, check
generator main panel circuit breaker(s) are ON and if necessary, check the main fuse (behind the main
panel). Service generator if required.
AC Loss of Power Alarm is activated (red light is flashing and beeper [could be] sounding) (NOTE:
audible alarm can be turned off with yellow switch on side of power distribution box) – Indicates that
DPMU has power (from shore power source or generator) but no 240VAC is being provided to
refrigeration unit. Check 240VAC circuit breaker is in the ON (up) position. Check transfer switch for
proper operation. Replace circuit breaker if required.
No interior/exterior lights – Check that 12VDC Master Light Switch is in the ON (up) position and
indicator light is illuminated. Check that battery is charged.