Acksen AL-2VA User manual

Electrocorder AL-2VA
User Instructions
WARNING!
THIS PRODUCT MUST ONLY BE USED BY SUITABLY
QUALIFIED PERSONNEL; DO NOT ATTEMPT TO USE THIS
PRODUCT UNLESS YOU ARE QUALIFIED TO DO SO.
HIGH VOLTAGES THAT CAUSE BURNS AND LETHAL SHOCKS
ARE PRESENT DURING VOLTAGE MONITORING AND
RECORDING!
General Description
Thank you for purchasing the Electrocorder AL-2VA, we hope you enjoy using this
product, this package consists of six main components:
1. Electrocorder logger (1)
The logging unit is housed in a strong ABS case.
2. Voltage Input Lead (1)
A plug and lead is provided to allow easy connection to the mains voltage system.
3. Voltage Output Lead (1)
An output socket to allow you to connect equipment to be recorded.
4. USB Lead (1)
A serial lead is provided to allow connection between the logger and any PC with a USB
port.
5. Software (download free from www.acksen.com)
Electrosoft software is provided free.
6. User Instructions (1)
These User Instructions are provided to give guidance, to qualified personnel.
PC Hardware requirements
To run Electrosoft you must have certain hardware and software installed on your
computer. The system requirements include:-
An IBM®- compatible Personal Computer with a minimum of an 80486 processor.
A hard disk, with at least 5MB spare capacity.
One 1.44MB 3.5” disk drive.
An SVGA 600 x 800 or higher resolution display.
At least 16MB of random access memory (RAM).
A mouse.
Microsoft®Windows 9X, NT4.0, 2000, XP, Vista, Windows 7, 8, 10.
Installing Electrosoft
When you run the Setup program, it will automatically set a path on your hard disk and
install Electrosoft there.
In Windows 9X, NT4.0, 2000, XP, Vista, Windows 7 the Setup program will create an
option in your Programs menu, which is in the Start menu.
Step 1: To install Electrosoft; run Setup.
For Windows 9X, NT4.0, 2000, XP, Vista, Windows 7, 8, 10.
Step 2: From the Taskbar menu click Start and choose Run. The Run dialogue box
appears.
Step 3: Type a:\Setup. Click OK. Follow the instructions on the screen to install
Electrosoft - you will be alerted when the installation is complete.
Getting started
In order to set-up an Electrocorder, you must first run Electrosoft on your PC. Then
connect an Electrocorder to the PC serial port using the correct (supplied) USB lead. In
Electrosoft, use the ‘Setup’ dialog box window and input the details of the location to be
monitored. The Electrocorder does NOT need to be connected in to the mains voltage to
perform this task.
The recording mode is set by default to commence recording when the Electrocorder
detects voltage and to stop recording when the memory is full.
Select the recording method - two options are available:
1. Record to EN50160 standard - the Electrocorder will take a sample once every second for
10 minutes. It then averages the samples taken over that 10 minute period and stores the
value. In this mode the unit will record for approximately 37 days until the memory is full.
2. Take a sample over a discrete period - the Electrocorder can be set to take an average
over a selected period, 1 (one) sec to 60 (sixty) min and also record the max and min during
each period. For example, a unit set to record every 1 (one) second will record for
approximately 2 hours. A unit set to record every 12 seconds will record for approximately
1 day. A unit set to record every 15 (fifteen) minutes will record for approximately 75
days, 60 minutes will give 300 days of logging.
When the required information has been input, download to the connected Electrocorder by
clicking the ‘Write Setup’ icon. The Electrocorder is now ready to monitor voltage.
When the Electrocorder is recording a flashing red light will show and when it has
completed recording, a green light will appear on the unit. The database contained within
Electrosoft will also advise that the unit has completed recording and is ready to be
collected. To download the recorded data connect the Electrocorder to the PC serial port
and click the ‘Read Setup’ icon. The recorded data is displayed for analysis.
This document is produced in conjunction with the Help file contained in Electrosoft, which
contains a detailed explanation of all features and contains information, which should be
studied prior to using this product.
SAFETY TIPS
Ensure the logger and the equipment you wish to monitor are both in good
mechanical and electrical condition, with no external or internal damage.
If either the logger or the equipment to be monitored have any signs of damage, do
not use them. Ensure the items have been inspected and ‘PAT’tested and that their
certification is within its valid date. If in any doubt, or the certification has expired,
have the items inspected by a suitably qualified professional.
Ensure the items are dry and are being used in accordance with the manufacturers’
instructions, if you are unsure, consult a suitably qualified professional.
The voltage leads are double insulated and suitable for voltages up to but not
exceeding 300Vac. Do not use them if there any signs of damage.
Features & Benefits of the AL-2VA Logger System
Feature
Benefit
Unit is small and lightweight.
Easy to install
Easy to use Windows software.
Can be used by non-technical staff.
Electrosoft contains internal
database.
Allows effective management of distributed
loggers.
True RMS measurement.
Complies to EN50160:1994.
Colour Codes Around the World
Phase
IEC Colour
Code
Aus/NZ
Colour Code
US Color
Code
Canadian
Color Code
L1 (A)
Brown
Red
Black
Red
L2 (B)
Black
White
Red
Black
L3 (C)
Grey
Blue
Blue
Blue
N(Neutral)
Blue
Black
White, grey
White
G
(Ground/Earth)
Yellow/Green
Stripe
Yell/Green
Stripe
Green,
Yell/Green
Green, bare
copper
Inputs and Connections on Various Systems
Colour and Input
Terminal
Single
Phase
(2-Wire)
Single
Phase
(3-Wire)
Brown (L1)
X (Live)
X (Live)
Green/Yellow
(G/E)
X (Earth)
Blue (N)
X (Neutral)
X (Neutral)
Power Measurement
The voltage input is labelled ‘Input/Entrada’ and the voltage output is labelled
‘Output/Salida’. This product has an internal current sensor which detects the current being
taken by the equipment connected to the Output socket.
1) Ensure this logger is first set-up with the PC and is ready to record data.
2) Next disconnect the PC and connect the load or equipment to be monitored to the
'Output' socket. Connect this logger's 'Input' to the mains voltage supply and switch the
supply on, press the 'Start‘ button to start recording data.
3) Finally switch on the equipment to be monitored. A flashing green light signifies that the
logger is recording data. A steady red signifies that the logger has finished recording data.
If both green and red lights are illuminated an error has occurred, please consult manual.
To read the data, disconnect the logger from the mains voltage supply, connect the USB
lead to the PC and to the logger. Open Electrosoft, select the correct USB comms port and
click the “Read Logger” button t o upload the recorded data.

Technical Specifications
TECHNICAL SPECIFICATIONS (subject to change without notice)
Measurement range (Vrms)
30Vac to 300Vrms (Ph –N)
Maximum channel input voltage
300Vrms (Ph –N)
Voltage Measurement accuracy
±1% of reading (10 bit) within 50Vac –300Vrms (Ph
–N); else ±3%. (50/60Hz ±2%)
Current Range
0.1A –15A (other ranges can be factory set)
Current Measurement Accuracy
3% of range, 1 to 13A. 0.1 to 1A, +/- 0.1A.
Vmin & Vmax meas time resolution
Always one cycle (50/60 Hz), independent of
selected averaging period.
Sampling frequency
16 samples per cycle 800Hz @ 50Hz or 960Hz @
60Hz
Data recorded
Average voltage/current, max & min voltage/current-
cycle-value during the averaging period
Memory capacity
128kB able to record 32,000 Voltage levels per
channel.
Memory type
Non-volatile SEEPROM
Memory - averaging period & duration
1 sec to 60 mins (1sec. avg gives 2 hrs of logging,
60min. avg gives 300 days of logging)
Real-time clock accuracy
Greater than 0.001%
Lead Lengths
Metric 1.0 metres Imperial 3’ 6” (3 feet, 6 inches)
Battery life (while plugged in)
Unlimited - mains powered & battery backup (9,000
hours, 1 year while unpowered).
Battery Type
Unit contains three 9V Alkaline batteries (E-Block,
PP3, 1604A).
Communications Interface type
USB, baud of 19,200
Electrosoft Software
Windows (9x, 2K, ME, NT, XP, Vista, Win 7, 8);
1024 x768 min resolution
Environmental (temp & sealing)
-20C to +40C /+14°F to +104°F –Indoor use only
Dimensions & Weight
Metric 230 x 140 x 50mm & 400g
Imperial –5.5” x 3.5” x 2” & 1lb
Standards
Recording - EN50160: 1994 - CAT II, maximum
input voltage 300Vac.
Calibration
Each unit is individually calibrated during testing.
Battery life (while connected)
Unlimited - mains powered and battery back up.
Battery life (while unconnected to mains)
The 9V Alkaline batteries should last for at least 9,000 hours (1 year),
Caution
The battery used in this device may present a risk of fire or chemical burn if mistreated.
Do not recharge, disassemble, heat above 100°C or incinerate. Replace with a 9V Lithium
or Alkaline battery IEC Type 6-F22 (PP3, MN1604). Use of another battery may present a
risk of fire or explosion. Dispose of used batteries promptly. Check for signs of battery
(electrolyte) leakage. If leakage has occurred, the PCB must be cleaned in an approved
manner by a competent (trained) person. Keep away from children. When replacing
batteries, ensure the new batteries are secured to the battery holders with cable-ties or
tie-wraps.
Maintenance
Regularly check the Electrocorder casing for signs of damage (cracks, broken or loose
parts) or misuse. If the unit is damaged in any way it must NOT be used and should be
returned to the supplier. The unit must not be used for any other purpose than for that
recommended by the manufacturer. The unit must not be submerged in any liquid.
Cleaning
Wipe the outside of the case with a clean cloth damped with IPA (Isopropyl Alcohol).
Warranty
All Acksen products carry a minimum 1 year’s warranty covering manufacturing defects and
component failures. The device contains no user-serviceable parts and as such should only
be repaired by skilled and authorised personnel. Failure to comply could result in unsafe
operation and should not be attempted under any circumstances. Contact below for a list of
approved service agents.
Note: Any unauthorised repair or adjustment will automatically render the warranty invalid.
Repair and spare parts
Acksen Ltd.
28 Station Road
Whiteabbey
Newtownabbey
Co. Antrim BT37 0AW
United Kingdom
Or an approved repair company.
Returning a product for repair
If returning a product to the manufacturer for repair, it should be sent freight pre-paid to the
appropriate address. A copy of the Invoice and of the packing note should be sent
simultaneously by airmail to expedite clearance through Customs. A repair estimate showing
freight return and other charges will be submitted to the sender, if required, before work on
the device commences.
WEEE
For EU customers Acksen Ltd offer a product take-back service. For customers within the
European Union (only) and products manufactured or sold by us; when those products
reach the end of their life, simply send them back to us at your expense, we will dispose of
them according to the relevant legislation. WEEE Reg. No. WEE/DD2117VU.