2ADVANCED CONTROL TECHNOLOGIES, INC.
Indianapolis, Indiana 46278 (800) 886-2281
AIM1InstallationInstructions
P/D071897 Rev.A
2) Ifthe24voltACpowerissharedwithdevicesthathavecoilssuchasrelays,solenoids,orother
inductors, each coil must have a MOV, Transorb, or other spike snubbing device across each
of the shared coils. Without these snubbers, coils produce very large voltage spikes when
de-energizing that can cause malfunction or destruction of electronic circuits.
3) The secondary voltage should be isolated from earth ground, chassis ground, and neutral leg
of the primary winding. Grounding should be to the system common only. If you do not follow
these procedures improper operation can result.
4) Youshould measure the actual voltageoutput of the secondary. If theoutput is not fully loaded
you may read a higher voltage than the circuit board can handle.
FUNCTION SELECTIONS
STEP 1) INPUT TYPE
SetjumperblockJ1for0-5Volts,0-10Volts,or0-20milliampsinput signal. See Figure A on page
1 for details.
STEP 2) OUTPUT TYPE
Set jumper block J2 and J3 for 0-5 Volts, 0-10 Volts, or 0-20 milliamps output signal. See Figure
B on page 1 for details.
CALIBRATION AND CHECKOUT
The AIM1 is factory calibrated as follows, unless otherwise specified: 0-5 Volts Input Signal
1:1 Input to Output Signal Ratio, 0-5 Volts Output Signal
STEP 3) WIRING CONNECTIONS (for "source" input and output)
With the power OFF, make the following connections:
Connect a 24 VAC power supply to the 24 VAC terminals of the AIM1.
For inputs from powered current devices, and voltage input signals, connect signal common (-) to
the 3 signal input terminal of the AIM1, and the signal positive (+) to the 2 signal input terminal
of the AIM1.
For 2-wire current inputs to AIM1 requiring power see Figure C on page 1 for hook-up details.
Connect the output signal common (-) terminal O3 and the output signal positive terminal O2 to
their respective terminals on the controlled device.
For current "sink" output from AIM1, see Figure D on page 1 for hook-up details.
STEP 4) POWER UP
Turnonthe24VACpowersupply. BothPrimaryPower(PRIPOWER)andSecondaryPower(2ND
POWER) LED indicators on the AIM1 will light.
STEP 5) OPERATION
The AIM1 will now accept an input signal and produce an isolated and proportional output signal.
(Example, a 5.0 volt input signal will produce a 5.0 (+/- .05 volts) volt DC output signal.)
PowerConsumption: 100mAmax.
InputImpedance: 0-5 Vdc,0-10Vdc<20,000 ohm
0-20mA/250ohm
OutputImpedance: Voltage-5000ohmmin
Current-500ohmmax