ActronAir Classic 2 Series User manual

Classic Series 2
Split Ducted Unit
Installation and Commissioning Guide - Indoor
Model Numbers
Single Fan Coil Split Fan Coil**
EVA100S*
EVA130S
EVA150S
EVA170S
EVA200S
EVA230S
EAA130S & EFA130S
EAA150S & EFA150S
EAA170S & EFA170S
EAA200S & EFA200S
EAA230S & EFA230S
* Above unit illustration shown is an EVA130S unit.
EVA100S has a single fan configuration.
** Split fan coil has a separate coil and fan section.
IMPORTANT NOTE:
Please read this manual carefully before installing or operating your air conditioning unit.
That’s better. That’s Actron.

Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
Installation and Commissioning Guide Split Ducted Indoor Units
2
Table of Contents
01. Introduction ................................................................................................................................. 03
01.01. Information About This Guide 03
01.02. Product Inspections 03
01.03. Codes, Regulations And Standards 03
01.04. Important Safety Symbols And Labels 03
02. Safety Instructions .........................................................................................................................4
03. Components Overview ................................................................................................................... 5
03.01. Indoor Unit Components Overview 5
03.02. Indoor Unit Electrical Panel Overview 5
04. Unit Dimensions and Clearances ....................................................................................................6
04.01. EVA100S 6
04.02. EVA130S 7
04.03. EVA150S 8
04.04. EVA170S 9
04.05. EVA200S 10
04.06. EVA230S 11
05. Two-Piece Fan Coil ........................................................................................................................12
05.01. Coil Section 12
05.02. Fan Section 16
06. Installation Instructions ................................................................................................................19
07. Unit Lifting Procedures ..................................................................................................................21
07.01. Crane Lifting Method 21
07.02. Fork Lift Method 22
08. Safety Drain Tray ......................................................................................................................... 23
09. Zone Barrel Mounting Instructions ............................................................................................... 24
10. Electrical Installation .................................................................................................................... 25
11. Indoor Unit Wiring Diagram ......................................................................................................... 26
12. Split Unit Electrical Connection .................................................................................................... 27
13. Maximum Cable Lengths .............................................................................................................. 29
13.01. Recommended Wiring Configuration 29
13.02. Alternate Wiring Configuration 30
14. Cable Length - Zoning ...................................................................................................................31
15. Wiring Connections ..................................................................................................................... 32
15.01. LR7 Wall Control Wiring Connections 32
15.02. LM-RS Optional Sensor Wiring Connections 32
15.03. AERSS Optional Duct Sensor Wiring Connections 32
16. Maintenance Frequency Checklist .................................................................................................33
17. Key Parts List ................................................................................................................................ 34

Installation and Commissioning Guide Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
3
01. Introduction
CONGRATULATIONS on your purchase of an ActronAir air conditioning system! This unit has been designed and
engineered to provide optimum air conditioning and to achieve maximum energy efficiency.
Your air conditioning system has been manufactured from the highest quality materials. Numerous “in house” and “external”
inspection and test procedures were conducted to your air conditioning to ensure satisfactory operation.
01.01. Information About This Guide
This guide provides installation instructions, specific to your split ducted indoor unit. Read this manual thoroughly and
take into consideration all specifications and instructions to ensure correct installation and safe operation of your air
conditioning system.
IMPORTANT
Keep this document for future reference. Ensure all technicians that work on the unit can refer to this manual at any time.
01.02. Product Inspections
Check your air conditioning unit and all items against the invoice upon receiving your shipment. Inspect the unit,
components and accessories for any sign of damage. If there is any damage to the unit, contact ActronAir Customer
Care Department immediately on: 1300 522 722 to obtain a Goods Return Number.
Check the unit nameplate to verify the model, serial number, electrical rated specifications are correct.
01.03. Codes, Regulations And Standards
The installer and/or contractor assumes responsibility to ensure that unit installation complies with the relevant
council, state / federal codes, regulations and building code standards. All electrical wiring must be in accordance with
current electrical authority regulations and all wiring connections to be as per electrical diagram provided with the unit.
01.04. Important Safety Symbols And Labels
Safety Symbols and labels appear at appropriate sections throughout this manual to indicate immediate or potential
hazards. Pay full attention and comply to the safety information and instructions. Failure to follow safety instructions
increases the risks of personal injury, death and/or property damage. Damages to the product as a result of such failure
may void warranty.
ActronAir has endeavoured to provide sufficient safety warnings and recommendations, however current and
prevailing WH&S regulations must be observed and will take precedent whenever performing the installation
instructions discussed in this manual.

Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
Installation and Commissioning Guide Split Ducted Indoor Units
4
02.Safety Instructions
•Only licensed HVAC technicians* should install and service this air conditioning equipment. Improper service or
alteration by an unqualified technician could result in significant and major damage to the product or property which
may render your warranty null and void. Such unqualified service could also lead to severe physical injury or death.
Follow all safety instructions in this literature and all warning labels that are attached to the equipment.
•Prevailing WH&S regulations must be observed and will take precedence to the safety instructions contained on this
manual. Safe work practices and environment must be the paramount importance in the performance of all the service
procedures.
•Ensure that unit installation complies with relevant council regulations and building code standards.
•All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to be
as per electrical diagram provided.
•Secure the fans against accidental contact. Beware of pinch point and sharp edges which can cause cutting injury.
•Always wear appropriate PPE, remove any dangling jewellery and protect long hair by wearing a cap.
•Make sure that safety guards and panel covers are always firmly secured and not damaged.
•This appliance is not intended for use by young children or infirm persons unless they have been adequately supervised
by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure
that they do not play with the appliance.
•Installer must incorporate a means of electrical disconnection (isolator) in the sub mains fixed wiring in accordance
with AS/NZS 3000:2018 (also known as Australian Wiring Rules).
•Secure the power cords and control cables that goes in/out the unit. Use the cable ties provided in the control box.
*Qualifications required will be appropriate Electrical, Refrigeration and Refrigerant Handling License and Training
dependent on local State/Territory regulations.
DANGER
Hazardous Voltage - Risk of Electrocution.
TURN-OFF the power from main isolator before proceeding with any service work of the unit. Observe proper LOCK-OUT/
TAGOUT LOTO) procedures for electrical appliances in order to prevent accidental switching-on of the power supply.
CAUTION
Beware of Rotating Fans!
Ensure that indoor and outdoor fans are isolated and have come to a complete stand still before servicing the equipment.
Beware of pinch point and sharp edges which can cause cutting injury. Secure the fans against accidental contact.
Always wear appropriate PPE and remove any dangling jewellery and protect long hair by wearing a cap. Ensure that no loose
clothing can be caught / entangled in moving parts.
VISUAL INSPECTION AND WORK ASSESSMENT
Work areas and conditions must first be assessed and evaluated for any potential hazardous conditions. It is also important to be
familiar with the unit parts and components before proceeding with any service task.

Installation and Commissioning Guide Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
5
03. Components Overview
03.01. Indoor Unit Components Overview
EC MOTOR
INDOOR
UNIT
ID FAN
(Single Fan for EVA100S)LID CONTROL
PANEL
ID COIL
INDOOR
CONTROL PANEL
03.02. Indoor Unit Electrical Panel Overview
INDOOR UNIT
CONTROL BOARD
EMC FILTER
(for some models) TRANSFORMER

Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
Installation and Commissioning Guide Split Ducted Indoor Units
6
04.Unit Dimensions and Clearances
04.01. EVA100S
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EVA100S 41
TOP VIEW OVERALL NOMINAL DIMENSION H X W X L
= 410 X 850 X 595
SUPPLY DUCT H X W = 175 X 235 NO FLANGE
RETURN DUCT = 340 X 660
CONDENSATE DRAIN CONNECTION = 20mm OD
770
SUPPLY
AIR
660
575
RETURN
AIR
65
45
410
O/A
175
20
20
810
235 267.5267.5
850 O/A
42
595 O/A
535 40
340
20
50
INDOOR
FAN
INDOOR COIL
SUPPLY
AIR
135
RETURN
AIR
GAS PIPE
15.9 mm (5/8") SWAGED
SAFETY DRAIN TRAY
20 mm ID
BSP SOCKET
LIQUID PIPE
9.5 mm (3/8") SWAGED
CONDENSATE DRAIN
20 mm OD
BSP FEMALE THREAD
40
FRONT VIEW
SIDE VIEW
HEIGHT CLEARANCE = 340mm
DUCT WORK
DUCT WORK
850 mm
SERVICE
CLEARANCE
850 mm
SERVICE
CLEARANCE
(ELECTRICALS)
770
SUPPLY
AIR
660
575
RETURN
AIR
65
45
410
O/A
175
20
20
810
235 267.5267.5
850 O/A
42
595 O/A
535 40
340
20
50
INDOOR
FAN
INDOOR COIL
SUPPLY
AIR
135
RETURN
AIR
GAS PIPE
15.9 mm (5/8") SWAGED
SAFETY DRAIN TRAY
20 mm ID
BSP SOCKET
LIQUID PIPE
9.5 mm (3/8") SWAGED
CONDENSATE DRAIN
20 mm OD
BSP FEMALE THREAD
40
EC
ID FAN
INDOOR COIL
RF
LFLR
RR
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
NOTES:
1. Do not scale drawing. All dimensions are
in mm unless specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested minimum
based on the condition that the spaces around the
units are free from any obstructions and a walkway
passage of 1000mm between the units or between
the unit and the outside perimeter is available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir will not be
held liable for any extra charges incurred due to lack
of access.
THIRD ANGLE
PROJECTION

Installation and Commissioning Guide Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
7
04.02. EVA130S
900
715
INDOOR COIL
1090 O/A
148
575
45 66
148
1050 115
80
412
O/A 340
22
50
RETURN
AIR
300
72
40
SUPPLY
AIR
615 O/A
53540 40
SUPPLY AIR
EC
INDOOR
FAN
EC
INDOOR
FAN
TOP VIEW
FRONT VIEW
SIDE VIEW
OVERALL NOMINAL DIMENSION H X W X L
= 412 X 1090 X 615
SUPPLY DUCT H X W = 300 X 715
RETURN DUCT = 340 X 900
CONDENSATE DRAIN CONNECTION = 20mm OD
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EVA130S 56
NOTES:
1. Do not scale drawing. All dimensions
are in mm unless specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested minimum
based on the condition that the spaces around
the units are free from any obstructions and a
walkway passage of 1000mm between the units
or between the unit and the outside perimeter is
available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir will not
be held liable for any extra charges incurred due
to lack of access.
THIRD ANGLE
PROJECTION
RF
LFLR
RR
DUCT WORK
DUCT WORK
850 mm
SERVICE
CLEARANCE
850 mm
SERVICE
CLEARANCE
(ELECTRICALS)
EC
ID FAN
EC
ID FAN
INDOOR COIL
HEIGHT CLEARANCE = 340mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES

Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
Installation and Commissioning Guide Split Ducted Indoor Units
8
04.03. EVA150S
NOTES:
1. Do not scale drawing. All
dimensions are in mm unless
specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested
minimum based on the condition that the
spaces around the units are free from any
obstructions and a walkway passage of 1000mm
between the units or between the unit and the
outside perimeter is available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir will not
be held liable for any extra charges incurred due
to lack of access.
THIRD ANGLE
PROJECTION
RF
LFLR
RR
DUCT WORK
DUCT WORK
850 mm
SERVICE
CLEARANCE
850 mm
SERVICE
CLEARANCE
(ELECTRICALS)
EC
ID FAN
EC
ID FAN
INDOOR COIL
HEIGHT CLEARANCE = 340mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
OVERALL NOMINAL DIMENSION H X W X L
= 412 X 1290 X 615
SUPPLY DUCT H X W = 300 X 715
RETURN DUCT = 340 X 1100
CONDENSATE DRAIN CONNECTION = 20mm OD
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EVA150S 59
1100
80
715
20 20
INDOOR COIL
412
O/A
615 O/A
1250
40
300
72
40
340
22
50
115
247.5 247.5
575
SUPPLY
AIR
RETURN
AIR
1290 O/A
40
535
70
50
EC
INDOOR
FAN
EC
INDOOR
FAN
SUPPLY AIR
TOP VIEW
FRONT VIEW SIDE VIEW

Installation and Commissioning Guide Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
9
04.04. EVA170S
NOTES:
1. Do not scale drawing. All dimensions
are in mm unless specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested minimum
based on the condition that the spaces around
the units are free from any obstructions and a
walkway passage of 1000mm between the units
or between the unit and the outside perimeter is
available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir will not
be held liable for any extra charges incurred due
to lack of access.
THIRD ANGLE
PROJECTION
RF
LFLR
RR
DUCT WORK
DUCT WORK
850 mm
SERVICE
CLEARANCE
850 mm
SERVICE
CLEARANCE
(ELECTRICALS)
EC
ID FAN
EC
ID FAN
INDOOR COIL
HEIGHT CLEARANCE = 410mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
OVERALL NOMINAL DIMENSION H X W X L
= 412 X 1290 X 615
SUPPLY DUCT H X W = 300 X 715
RETURN DUCT = 340 X 1100
CONDENSATE DRAIN CONNECTION = 20mm OD
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EVA170S 60
1100
80
715
20 20
INDOOR COIL
412
O/A
615 O/A
1250
40
300
72
40
340
22
50
115
247.5 247.5
575
SUPPLY
AIR
RETURN
AIR
1290 O/A
40
535
70
50
EC
INDOOR
FAN
EC
INDOOR
FAN
SUPPLY AIR
TOP VIEW
FRONT VIEW SIDE VIEW

Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
Installation and Commissioning Guide Split Ducted Indoor Units
10
04.05. EVA200S
NOTES:
1. Do not scale drawing. All
dimensions are in mm unless
specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested
minimum based on the condition that the
spaces around the units are free from any
obstructions and a walkway passage of
1000mm between the units or between the
unit and the outside perimeter is available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra charges
incurred due to lack of access.
THIRD ANGLE
PROJECTION
RF
LFLR
RR
DUCT WORK
DUCT WORK
850 mm
SERVICE
CLEARANCE
850 mm
SERVICE
CLEARANCE
(ELECTRICALS)
EC
ID FAN
EC
ID FAN
INDOOR COIL
HEIGHT CLEARANCE = 410mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
OVERALL NOMINAL DIMENSION H X W X L
= 435 X 1420 X 680
SUPPLY DUCT H X W = 300 X 715
RETURN DUCT = 360 X 1140
CONDENSATE DRAIN CONNECTION = 20mm OD
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EVA200S 76
SUPPLY
AIR
715310 310
1420 O/A
114080 120
630
20 20
435
O/A
INDOOR COIL
1375
90
130
SUPPLY AIR
59040 50
680 O/A
360
50
25
110
300
25
RETURN
AIR
EC
INDOOR
FAN
EC
INDOOR
FAN
TOP VIEW
FRONT VIEW SIDE VIEW

Installation and Commissioning Guide Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
11
04.06. EVA230S
NOTES:
1. Do not scale drawing. All dimensions
are in mm unless specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested minimum
based on the condition that the spaces around
the units are free from any obstructions and a
walkway passage of 1000mm between the units
or between the unit and the outside perimeter is
available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir will not
be held liable for any extra charges incurred due
to lack of access.
THIRD ANGLE
PROJECTION
RF
LFLR
RR
DUCT WORK
DUCT WORK
890 mm
SERVICE
CLEARANCE
890 mm
SERVICE
CLEARANCE
(ELECTRICALS)
EC
ID FAN
EC
ID FAN
INDOOR COIL
HEIGHT CLEARANCE = 410mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
OVERALL NOMINAL DIMENSION H X W X L
= 485 X 1470 X 695
SUPPLY DUCT H X W = 380 X 715
RETURN DUCT = 410 X 1190
CONDENSATE DRAIN CONNECTION = 20mm OD
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EVA230S 90
119080 120
715
337.5 337.5
INDOOR COIL
1470 O/A
GAS PIPES
Ø 25.4 mm (1")
SWAGED
LIQUID PIPES
Ø 12.7 mm (1/2")
SWAGED
ELECT
BOX &
ACCESS
PANEL
695 O/A
60540 50
380
70
35
410
25
50
SUPPLY
AIR RETURN
AIR
SAFETY DRAIN TRAY
Ø 25.4 mm (1") ID
CONDENSATE DRAIN
Ø 25.4 mm (1") ID
645
20 20
1430
85
485
O/A
110
SUPPLY AIR
EC
INDOOR
FAN
EC
INDOOR
FAN
TOP VIEW
FRONT VIEW SIDE VIEW

Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
Installation and Commissioning Guide Split Ducted Indoor Units
12
05. Two-Piece Fan Coil
05.01. Coil Section
21 1012 21
345
13
51
77
409 O/A
900 77
302
29
15
23
22 22
81
94
199
284
81
131
284
1054 O/A
11 990
(MTG C-C DIST) 11
131
156
43
344 O/A
25
31
77 900 77
51
345
13
COIL SENSOR HOLE
35mm
CONDENSATE DRAIN TRAY
20mm OD
SAFETY DRAIN TRAY
20mm ID
COIL AIR FLOW
TOP VIEW
FRONT VIEW - SUPPLY AIR
REAR VIEW - RETURN AIR
SIDE VIEW
EAA130S OVERALL NOMINAL DIMENSION H X W X L
= 409 X 1054 X 344
SUPPLY DUCT H X W = 345 X 900
RETURN DUCT = 345 X 900
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EAA130S 27
NOTES:
1. Do not scale drawing. All
dimensions are in mm unless specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested
minimum based on the condition that the
spaces around the units are free from any
obstructions and a walkway passage of
1000mm between the units or between the
unit and the outside perimeter is available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra charges
incurred due to lack of access.
THIRD ANGLE
PROJECTION
850 mm
SERVICE
CLEARANCE
LR
LF
RF RR
TOP VIEW
DUCT WORK
TO FAN SECTION
(0m Min - 6m Max)
COIL SECTION
DUCT WORK
850 mm
SERVICE
CLEARANCE
HEIGHT CLEARANCE = 340mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES

Installation and Commissioning Guide Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
13
21
1212
21
176900
177
51
345
13
409 O/A
131
156
43
25
11
1190
(MTG C-C DIST)
11
344 O/A
1254 O/A
302
94
29
15
23
81
21
199
284
131
81
22 284
13
345
51
177900176
SAFETY DRAIN TRAY
20mm ID
CONDENSATE DRAIN TRAY
20mm OD
COIL SENSOR HOLE
35mm
COIL AIR FLOW
TOP VIEW
FRONT VIEW - SUPPLY AIR
REAR VIEW - RETURN AIR
SIDE VIEW
EAA150S / EAA170S
OVERALL NOMINAL DIMENSION H X W X L
= 409 X 1254 X 344
SUPPLY DUCT H X W = 345 X 900
RETURN DUCT = 345 X 900
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EAA150S 30
EAA170S 32
NOTES:
1. Do not scale drawing. All
dimensions are in mm unless
specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested
minimum based on the condition that the
spaces around the units are free from any
obstructions and a walkway passage of
1000mm between the units or between the
unit and the outside perimeter is available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra charges
incurred due to lack of access.
THIRD ANGLE
PROJECTION
850 mm
SERVICE
CLEARANCE
LR
LF
RF RR
TOP VIEW
DUCT WORK
TO FAN SECTION
(0m Min - 6m Max)
COIL SECTION
DUCT WORK
850 mm
SERVICE
CLEARANCE
HEIGHT CLEARANCE = 340mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES

Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
Installation and Commissioning Guide Split Ducted Indoor Units
14
21
1317
21
13
36261
436 O/A
131 1094 133
158
143
10
25
12
1294
(MTG C-C DIST)
11
342 O/A
1360 O/A
302
15
39
153
28
76
87
237
310
87
130
310
22 22
13
36261
1321094133
SAFETY DRAIN TRAY
20mm ID
CONDENSATE DRAIN TRAY
20mm ID
COIL SENSOR HOLE
35mm
COIL AIR FLOW
TOP VIEW
FRONT VIEW - SUPPLY AIR
REAR VIEW - RETURN AIR
SIDE VIEW
EAA200S OVERALL NOMINAL DIMENSION H X W X L
= 436 X 1360 X 342
SUPPLY DUCT H X W = 362 X 1094
RETURN DUCT = 362 X 1094
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EAA200S 38
NOTES:
1. Do not scale drawing. All
dimensions are in mm unless
specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested
minimum based on the condition that the
spaces around the units are free from any
obstructions and a walkway passage of
1000mm between the units or between the
unit and the outside perimeter is available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra charges
incurred due to lack of access.
THIRD ANGLE
PROJECTION
850 mm
SERVICE
CLEARANCE
LR
LF
RF RR
TOP VIEW
DUCT WORK
TO FAN SECTION
(0m Min - 6m Max)
COIL SECTION
DUCT WORK
850 mm
SERVICE
CLEARANCE
HEIGHT CLEARANCE = 410mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES

Installation and Commissioning Guide Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
15
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EAA230S 43
22
1367
21
14
41061
486 O/A
157 1094 158
1410 O/A
165
160
11
1344
12
342 O/A
13
28
302
360
87
22
131
69
89
238
360
22
18
30
39
153
14
41060
1581094157
SAFETY DRAIN TRAY
25mm ID CONDENSATE DRAIN TRAY
25mm ID
COIL SENSOR HOLE
25mm
COIL A IR FLOW
TOP VIEW
FRONT VIEW - SUPPLY AIR
REAR VIEW - RETURN AIR
SIDE VIEW
EAA230S OVERALL NOMINAL DIMENSION H X W X L
= 486 X 1410 X 342
SUPPLY DUCT H X W = 410 X 1094
RETURN DUCT = 410 X 1094
15
NOTES:
1. Do not scale drawing. All
dimensions are in mm unless specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested
minimum based on the condition that the
spaces around the units are free from any
obstructions and a walkway passage of
1000mm between the units or between the
unit and the outside perimeter is available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra charges
incurred due to lack of access.
THIRD ANGLE
PROJECTION
890 mm
SERVICE
CLEARANCE
LR
LF
RF RR
TOP VIEW
DUCT WORK
TO FAN SECTION
(0m Min - 6m Max)
COIL SECTION
DUCT WORK
890 mm
SERVICE
CLEARANCE
HEIGHT CLEARANCE = 410mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES

Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
Installation and Commissioning Guide Split Ducted Indoor Units
16
05.02. Fan Section
189 168 51
408 O/A
152 240 227 240 152
1012
1074 O/A
4332342
11 990
(MTG C-C DIST)
11
86
271
5
11
990
(MTG C-C DIST)
11
282
362 O/A
282
56 900 56
15
378
15
EFA130S / EFA150S / EFA170S OVERALL NOMINAL DIMENSION H X W X L
= 408 X 1074 X 362
SUPPLY DUCT H X W = 168 X 707
RETURN DUCT = 378 X 900
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EFA130S / EFA150S / EFA170S 35
TOP VIEW
FRONT VIEW - SUPPLY AIR
REAR VIEW - RETURN AIR
SIDE VIEW
1011
NOTES:
1. Do not scale drawing. All
dimensions are in mm unless
specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested
minimum based on the condition that the
spaces around the units are free from any
obstructions and a walkway passage of
1000mm between the units or between the
unit and the outside perimeter is available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra charges
incurred due to lack of access.
THIRD ANGLE
PROJECTION
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
850 mm
SERVICE
CLEARANCE
LR
LF
RF RR
TOP VIEW
FAN SECTION
DUCT WORK
DUCT WORK
FROM COIL SECTION
(0m Min - 6m Max)
850 mm
SERVICE
CLEARANCE
HEIGHT CLEARANCE = 340mm

Installation and Commissioning Guide Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
17
1207
246 327 60 327 246
200207
32367
1269 O/A
26
433 O/A
43
412 O/A
307
307
11 1185
(MTG C-C DIST)
11
11
1185
(MTG C-C DIST)
11
132271
9
56 1095 56
15
403
15
TOP VIEW
FRONT VIEW - SUPPLY AIR
REAR VIEW - RETURN AIR
SIDE VIEW
EFA200S
OVERALL NOMINAL DIMENSION H X W X L
= 433 X 1269 X 412
SUPPLY DUCT H X W = 200 X 714
RETURN DUCT = 403 X 1095
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EFA200S 46
1206
NOTES:
1. Do not scale drawing. All
dimensions are in mm unless
specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested
minimum based on the condition that the
spaces around the units are free from any
obstructions and a walkway passage of
1000mm between the units or between the
unit and the outside perimeter is available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra charges
incurred due to lack of access.
THIRD ANGLE
PROJECTION
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
850 mm
SERVICE
CLEARANCE
LR
LF
RF RR
TOP VIEW
FAN SECTION
DUCT WORK
DUCT WORK
FROM COIL SECTION
(0m Min - 6m Max)
850 mm
SERVICE
CLEARANCE
HEIGHT CLEARANCE = 410mm

Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
Installation and Commissioning Guide Split Ducted Indoor Units
18
EFA230S
OVERALL NOMINAL DIMENSION H X W X L
= 483 X 1269 X 412
SUPPLY DUCT H X W = 305 X 734
RETURN DUCT = 453 X 1095
UNIT MODEL NUMBER UNIT WEIGHT
(kg)
EFA230S 48
1207
236 337 60 337 236
61305
117
483 O/A
90 323 69
1269 O/A
11 1185
(MTG C-C DIST) 11
111185
(MTG C-C DIST)
11
67 271 74
56 1095 56 15
453
14
357
357
412 O/A
TOP VIEW
FRONT VIEW - SUPPLY AIR
REAR VIEW - RETURN AIR
SIDE VIEW
1206
NOTES:
1. Do not scale drawing. All
dimensions are in mm unless
specified.
2. Refer to Field Pipe connection details on
specifications sheet.
3. Service Clearances given are suggested
minimum based on the condition that the
spaces around the units are free from any
obstructions and a walkway passage of
1000mm between the units or between the
unit and the outside perimeter is available.
4. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra charges
incurred due to lack of access.
THIRD ANGLE
PROJECTION
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
890 mm
SERVICE
CLEARANCE
LR
LF
RF RR
TOP VIEW
FAN SECTION
DUCT WORK
DUCT WORK
FROM COIL SECTION
(0m Min - 6m Max)
890 mm
SERVICE
CLEARANCE
HEIGHT CLEARANCE = 410mm

Installation and Commissioning Guide Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
19
06.Installation Instructions
The installation instructions provided below are intended as a guide only and does not supersede the relevant council,
state and federal codes, regulations and building code standards. Compliance and consultation with the authorities having
jurisdiction with the installation of this equipment is the responsibility of the installer. ActronAir will not be held liable for
any damages or costs as a result of the installer’s failure to comply. Please refer to the matching outdoor unit Installation and
Commissioning Guide for further information and details.
Lifting The Unit
The installation instructions provided, in Section 07, adhere to WH&S regulations for safe and secure lifting practices in order
to prevent physical injury.
Suggested lifting procedures are outlined in Section 07 as a reference guide to safely lift and transport the unit, however,
this does not over rule the industry WH&S practices.
Location
This unit is intended for indoor installation only. It is highly recommended that this indoor unit and accessories, particularly
zone barrels, be mounted in the roof cavity.
Mount the unit in a stable and rigid support wherein the weight is properly distributed, such as roof joist and rafters. Take
into consideration the minimum service access clearances provided in the unit drawings.
Locate the indoor unit away from the areas where noise is a critical factor. Use rubber mounting pad (not supplied) in order
to minimize the transfer of noise and vibration into building structures.
An optional hanging bracket assembly and rubber grommet (supplied as standard with EVA230S) is also available to secure
the indoor unit into the roof rafters. This installation configuration is most suitable for installation that require the unit to be
rigidly secured up from the roof joist.
Condensate and Safety Tray Drainage
An integrated safety drain tray is provided as a standard inclusion to your indoor unit in order to reduce the potential of
condensate damage to the roof. Drain Kit (not included on EVA230S) is provided for the condensate drain to be externally
trapped from the indoor unit. Suggested condensate and safety tray drainage instructions are provided at the proceeding
page for your reference.
Supply Air and Return Air Duct
The indoor unit is supplied with duct flange (except EVA100 ) as standard in order to facilitate the system’s duct connection
into the unit. Supply and return air duct works must be adequately sized to meet the system’s air flow and static pressure
requirements. Refer to the unit drawing for supply air and return air duct dimensions, specific to your requirement.
NOTE
Fit a flexible duct connection in between the unit and the duct system, where noise and vibration is a critical consideration.
Return Air Filter
Air filters must be provided in the return air side of the unit to maintain the efficiency and prolong the operation of the unit.
These are also paramount to satisfy requirement for a clean and hygienic room condition. Return Air filters must be placed in
an easily accessible location for service and maintenance.
NOTES
• Return Air filters are not supplied with the unit as individual air filtration requirements vary.
• Ensure that filters are cleaned / replaced regularly.

Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074 Ver. 1 190925
Installation and Commissioning Guide Split Ducted Indoor Units
20
Air Plenums / Duct Plates (Optional)
Supply Air and Return Air plenums and duct plates (twin-spigot) are available as an option in order to facilitate your duct
system connection to the indoor unit. The supply air plenums come in 1-way, 2-way and 3-way options, which offer a wider
solutions to your different air distribution requirements.
Split Fan Coil System (Optional)
The ActronAir innovative 2-piece fan coil system provides a solution to your difficult and tight roof space installation
requirement. This versatile system has a separate fan and coil sections. Each of the compact and lightweight section is
simply installed in two separate locations and joined by flexible duct system. Air ducts are attached to each section of the
split fan coil by both of the supply air plenum and the twin spigot duct plate.
Fan Coil With Vertical Discharge (Optional)
An upright Fan Coil with vertical supply air discharge is also available wherein installation applications require the placement
of the unit down in a closet, basement or garage. Please refer to the Technical Catalogue of your indoor unit for dimensions,
installation details and specifications.
Field Pipe Connections
Specifications and installation requirements for field pipe connections are contained in the Installation and Commissioning
Guide of the outdoor unit that matches your indoor unit. Please refer to this guide and thoroughly understand the
procedures for safe and correct indoor and outdoor connection.
Field Electrical Connection
The power supply and control communication data to the indoor unit are supplied via the outdoor unit. Please refer to the
wiring diagram supplied with the outdoor unit for specifications.
All electrical work must be performed by a licensed electrician and must conform with the wiring diagram and all relevant
electrical authorities.
Other manuals for Classic 2 Series
1
This manual suits for next models
16
Table of contents
Other ActronAir Fan manuals
Popular Fan manuals by other brands

Bestron
Bestron AFT45SW/Z instruction manual

Helios
Helios KWL 170 W Installation and operating instructions

LU-VE
LU-VE EAV5 Installation and maintenance instruction

QUORUM INTERNATIONAL
QUORUM INTERNATIONAL Mykonos 72" installation instructions

Costway
Costway ES10001US user manual

Derale Perfomance
Derale Perfomance 16016 Installation instructions manual