Adamczewski AD-LU 60 FE User manual

Power transducer
AD-LU 60 FE
AD-LU 60 FE-D
AD-LU 60 FE-B
AD-LU 60 FE-DB
Operating manual
Version 1.1, Issue 2017-01-17, Production

Contents
1 About this manual 4
1.1 Structureofnotes ............................ 4
2 Safety 5
2.1 IntendedUse............................... 5
2.2 Foreseeable misapplication . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Safehandling............................... 5
2.4 Qualificationofstaff........................... 6
2.5 Changestotheproduct ......................... 6
2.6 Use of spare parts and accessories . . . . . . . . . . . . . . . . . . . . 6
2.7 Liabilitynotes .............................. 6
3 Product description 7
3.1 Scopeofdelivery............................. 7
3.2 Features ................................. 7
3.3 Orderingcode .............................. 8
3.4 Howitworks............................... 8
3.5 Updaterates............................... 9
3.6 Behavior of the device in the event of a fault . . . . . . . . . . . . . . 9
3.7 Display and control elements . . . . . . . . . . . . . . . . . . . . . . 9
4 Technical specifications 10
4.1 Currentinputs .............................. 10
4.2 Voltageinputs .............................. 10
4.3 Digitaloutputs.............................. 10
4.4 RS-485Interface............................. 11
4.5 Accuracy................................. 11
4.6 Casing .................................. 12
4.7 Environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . 12
4.8 EMC, safety regulations, product standard . . . . . . . . . . . . . . . 12
4.9 Galvanic isolation, test voltages . . . . . . . . . . . . . . . . . . . . . 13
5 Installation and commissioning 14
6 Operation 15
6.1 Displays ................................. 15
6.2 Menue .................................. 17
7 Configuration 18
7.1 Symbols ................................. 18
7.2 Parameters................................ 18
7.2.1 Current and voltage transformers . . . . . . . . . . . . . . . . 19
7.2.2 Filter............................... 19
2

7.2.3 Digital function at AD-LU 60 FE-D, AD-LU 60 FE-DB . . . . 20
7.2.4 RS-485Interface......................... 21
7.2.5 Options.............................. 21
8 Modbus 23
8.1 Generalinformation ........................... 23
8.2 Dataformat ............................... 23
8.3 Datatypes................................ 24
8.4 Supportedfunctions ........................... 24
8.4.1 Read Holding Registers . . . . . . . . . . . . . . . . . . . . . 24
8.4.2 Write Multiple Registers . . . . . . . . . . . . . . . . . . . . . 25
8.5 ExceptionCodes............................. 25
8.6 Datalists................................. 26
8.6.1 Measuredvalues......................... 26
8.6.2 Counter ............................. 27
8.6.3 Digitaloutputs.......................... 27
9 Connection diagram 28
10 Appendix 30
10.1 Maintenance and Service . . . . . . . . . . . . . . . . . . . . . . . . . 30
10.2Disturbances............................... 30
10.3Revisions................................. 30
10.4Addresses................................. 30
3

1 About this manual
This manual is part of the product.
•Be sure to read the operating instructions before using the product.
•Keep the operating manual for the entire life of the product and keep it ready
for reference.
•Pass the manual to each subsequent owner or user of the product.
1.1 Structure of notes
INFO General note
Highlighting special instructions and information that are neces-
sary for operation of the product.
WARNING Warning note
Possible damage to the device or risk of injury if the instructions
are not observed.
HAZARD Hazard statement
Possible damage to the device, risk of injury or life if the instruc-
tions are not observed.
4

2 Safety
2.1 Intended Use
WARNING Damage to property
The operating and maintenance conditions in this manual must
strictly adhere.
Any other use is not intended! Unauthorized modifications and modifications to the
product lead to considerable safety risks and are prohibited for safety reasons! Adam-
czewski elektronische Messtechnik GmbH shall not be liable for any damage resulting
from this or for damages resulting from the non-intended use.
Malfunctions that can affect safety are to be rectified immediately! The installer must
make the operating instructions accessible to the operator. Installer and operator must
have read and understood the operating instructions before beginning their work.
2.2 Foreseeable misapplication
This product may not be used in any of the following cases:
•In explosive atmosphere. Operating in potentially explosive atmospheres may
result in sparks, fire or explosions.
•Use on humans and animals.
2.3 Safe handling
This product complies with the state of the art and the recognized safety regulations.
Each unit is tested to verify functionality and safety.
Operate this product only in perfect condition, taking into account the operating
instructions, the usual regulations and guidelines as well as the applicable safety regu-
lations and accident prevention regulations.
Extreme environmental conditions affect the function of the product.
•Protect the product from shocks
•Use only in indoor areas
•Protect from moisture
5

2.4 Qualification of staff
Installation, commissioning, operation, maintenance and disposal may only be carried
out by qualified personnel. Work on electrical parts may only be carried out by a
trained electrician in accordance with the applicable regulations and Guidelines.
2.5 Changes to the product
Unauthorized modifications to the product can lead to malfunctions and are prohibited
for safety reasons.
2.6 Use of spare parts and accessories
Use of unsuitable spare parts and accessories may damage the product. Please use
only original spare parts and accessories from the manufacturer.
2.7 Liability notes
The manufacturer assumes no liability or guarantee for damage and consequential
damage caused by non-observance of the technical regulations, instructions and rec-
ommendations. The manufacturer and the sales company are not liable for any costs
or damages caused to the user or to third parties by the use of this device, especially
if the device is used improperly, misused or interfered with the connection, faults of
the device or of the connected devices. For non-intended use adheres neither the
manufacturer nor the sales company.
6

3 Product description
The AD-LU 60 FE and its variants is a measurement and display unit for front panel
mounting. It measures all values in the three-phase network with neutral conductors.
For correct measurement, the current must be detected in each phase directly or via a
current transformer. See chapter ??. The power cables must be looped to the device
via a plug-in current transformer.
The measured values are displayed in color on a graphical TFT display and are divided
into different displays. They can be scrolled through manually or time-controlled.
There is a basic variant as a pure display device and variants with Modbus interface
and digital outputs for counting pulses or limit values.
The device parameters such as the currents of the connected current transformers can
be achieved via a menu on the device itself or via the optional RS-485 interface.
3.1 Scope of delivery
•AD-LU 60 FE or one of the variants -D, -B or -DB
•This manual
3.2 Features
•Connection of 3 phases with neutral conductor, any load
•Measurement of P1, P2, P3, Ptot, Q1, Q2, Q3, Qtot, S1, S2, S3, Stot, I1, I2,
I3, U1, U2, U3, F, PF1, PF2, PF3, PFtot
•Low power loss during current measurement thanks to integrated through-current
transformers
•Display of measured values on a graphical TFT display
•Counters for the total applied / back-fed active energy and inductive / capacitive
reactive power
•Two switching outputs as optocouplers with configurable function as limit value
or S0 (device variants -D, -DB)
•RS-485 interface with Modbus-RTU protocol for reading the measured values
and configuring the device parameters with the Configuration program AD-
Studio (device variant -B, -DB)
7

3.3 Ordering code
Device variant TFT-Display Digital
Outputs
RS-485,
Modbus/RTU
AD-LU 60 FE •- -
AD-LU 60 FE -D ••-
AD-LU 60 FE -B •-•
AD-LU 60 FE -DB •••
3.4 How it works
k1
l1
k1
l1
k1
l1
N
L1
L2
L3
ADC uC
~=
RS-485
A
BM1
M2
M3 1
2
3
1
2
3
4
4
3
2
1
=
_
Display
AD-LU 60 FE
AD-LU 60 FE-D
AD-LU 60 FE-B
AD-LU 60 FE-DB
1
2
E1
K2
E2
K1
(3)
(1)
(2)
(4) (5) (6)
(7)
(9)
(8)
(10)
(10)
(10)
(9)
GND
The measuring voltages are divided by a voltage divider (1) and fed to the analog-
to-digital converter (4). The AC/DC converter (3) is simultaneously fed from the
measuring voltages. The AC / DC converter (3) supplies the analog-to-digital con-
verter (4) on the input side and the circuits on the output side.
The currents are first fed via the ring core current transformer (10) present on the
outside of the device. The mA signals on the secondary side are measured via shunts
(2) and are also fed to the analog-to-digital converter (4).
The analog-to-digital converter (4) transmits all raw data to the output side via a
galvanic separation (5). Here, they are scaled by the microcontroller (6) to the power
values, currents, voltages, etc. The scaled values are displayed on the display (7). For
the device variants with RS-485 interface (8), these values can also be read out via
the Modbus protocol. With the device variants with open-collector output (9), limits
8

or pulses can also be output.
3.5 Update rates
All measured values are recorded in a fixed time interval of 0.5s. The display output
is updated once per second.
3.6 Behavior of the device in the event of a fault
The AD-LU 60 FE verifies whether the signal voltage is present on phase L1. If this
is not the case, the AD-LU 60 FE goes into the error state. The device variants
AD-LU 60 FE-D, AD-LU 60 FE-DB switch off their outputs, ie the transistors are not
conductive.
3.7 Display and control elements
TFT-Display
Up SetDown
The AD-LU 60 FE has a color-coded TFT display for displaying the data and three
buttons for operation and configuration.
9

4 Technical specifications
4.1 Current inputs
Description Value Unit
Rated current ranges 0 ... 1/5/20 1A AC
Maximum conductor diameter 4,8 mm
1Currents up to 20A can be measured directly with the straight-through transformer of the device.
4.2 Voltage inputs
Description Value Unit
connections L1, L2, L3, N
Rated voltage range 80 ... 253 V AC, L-N
Impact overload 600 V AC, 1s, L-N
Input resistor 500 kΩ
INFO Connection of the neutral conductor
The AD-LU 60 FE is designed for connection to 3-wire networks
with neutral conductor. If the neutral wire is not connected, the
device will not work properly.
4.3 Digital outputs
The variants AD-LU 60 FE-D, AD-LU 60 FE-DB also have two open-collector outputs.
Description Value Unit
Number, type 2, NPN
Switching voltage 5 ... 30 V DC
Maximum switching current 50 mA DC
Short circuit proof no
Reverse polarity protected no
INFO Polarity reversal or overload
The switching outputs of the AD-LU 60 FE-D, AD-LU 60 FE-
DB are not protected against polarity reversal and overload. A
wrong auxiliary voltage or a too high switching current can lead
to the destruction of the output.
10

4.4 RS-485 Interface
The variants AD-LU 60 FE-B, AD-LU 60 FE-DB also have an RS-485 interface.
The connection to the other devices must be established via a twisted shielded bus
cable. The order of the devices among each other is arbitrary. For reasons of electro-
magnetic compatibility, the shield is to be connected at both ends to a large area and
to be connected with a protective shield. The wiring must be in a bus structure. Stops
longer than 5 m should be avoided. The two ends of the bus line must be terminated
with a resistance of 120 ohms, especially with longer bus lines.
If the device is to be operated in a bus segment that already has devices other than
Modbus slaves, the baud rate, parity and slave address may need to be adjusted. These
settings can be made directly from the device menu.
Description Value Unit
Standard RS-485
Baudrate 2400, 4800, 9600, 14400,
(19200), 28800, 38400,
57600, 76800, 115200
bps
Databits 8
Parity1(even), odd, none
Protocol Modbus-RTU
Max. Leitungsl¨ange 1200 m
1Without parity bits, two stop bits are output automatically.
4.5 Accuracy
Description Value Unit
Accuracy class 10,5 %
Temperature Influence +/-200 ppm/K
Frequency influence 0,2 %, 40 ... 60 Hz
Influence of phase angle 0,2 %, 0 ... 90◦
1Under reference conditions
11

4.6 Casing
Description Value Unit
Type of housing Switchboard housing acc
IEC 61554
Housing size HxBxT 96 x 96 x 44 mm
Control panel cutout 92(+0,8) x 92(+0,8) mm
Protection class IP20
Connection technology Screw terminals,
pluggable
Cross-section 2,5
4
mm2, Fine-
stranded
mm2, Solid
Weight 350 g
4.7 Environmental conditions
Description Value Unit
Overvoltage category 300 V CAT III
Degree of pollution 2
Protection class II 1
Ambient temperature 0...50 ◦C
Transport and Storage -10...70 ◦C
1No protective conductor.
4.8 EMC, safety regulations, product standard
Description Value Unit
Discharge of static electricity IEC 61000-4-2
Electromagnetic fields 1IEC 61000-4-3
Fast transients, Burst IEC 61000-4-4
Surge voltages, Surge IEC 61000-4-5
Conducted RF signals IEC 61000-4-6
Interference emission EN55011, CISPR11
Klasse B, Wohnbereich
Safety regulations EN61010-1
Product family standard EN 60688
1Low signal deviations are possible during interference.
12

4.9 Galvanic isolation, test voltages
Description Value Unit
Measurement inputs to RS-485 4 kV, 1 Min.
Measuring inputs for open collec-
tor outputs
4 kV, 1 Min.
RS-485 to open-collector outputs 4 kV, 1 Min.
13

5 Installation and commissioning
HAZARD Danger to life by electric shock
The terminals of the voltage inputs are hazardous to contact.
•Disconnect power supply
•Check absence of voltage
•Insert the device into the intended opening of the front panel
•Connect the power inputs and RS-485 interface
•Lead current carrying wires by the current transformer on the rear panel
•Switch on the voltage
•Configure the device from the menu or Configuration program AD-Studio
•Check function
•Disconnect power supply
•Connect digital outputs 1
•Reconnect power supply
•Check current through the current transformers
1The Open-Collector outputs should be connected after the function test in order to avoid unwanted
switching or fault messages.
INFO Observe the current conductor K/L via the current transformers
When passing through the current transformers on the rear side,
the energy flow direction from K to L must be taken into account.
K = infeed side, L = load side. See also the chapter ??. If you
do not have a PV system installed that feeds energy back into
the grid, all the active powers must be positive. Please check
this in the relevant display. When e.g. The value for the active
power in L2 is negative, the current conductor for I2 is probably
wrongly inserted by the current transformer.
14

6 Operation
There are basically the operating modes Display and Menu. When switched on, the
AD-LU 60 FE is always in display mode.
From the display mode, press ’Set (long)’ to enter the menu. In the menu you can
also return to the display mode by pressing the ’Set (long)’ key again or by selecting
’<<’ from the main menu.
Anzeigen Menü
Set(lang)
6.1 Displays
During operation, you can scroll through the displays with the ’Up’, ’Down’ and ’Set’
buttons.
Use the ’Up’ / ’Down’ keys to change the display level of the displayed values.
Press the ’Set’ key to scroll between the instantaneous values, the filter values, the
min values and the max values of the display levels. The function is circulating, that
is, the instantaneous values return to the max values.
15

INFO Filter, min and max values
Filter values are displayed in the header with the red reference
text ’AVG’ for ’Average’. A red ’MIN’ or ’MAX’ appears for the
min and max values. There are no sensible filter min- or max-
values for the meters.
U1
U2
U3
f
Ströme
Wirk-
leistungen
Blind-
leistungen
Schein-
leistungen
Leistungs-
faktoren
Phasen-
winkel
Zähler
I1
I2
I3
IN
P1
P2
P3
Ptot
Q1
Q2
Q3
Qtot
S1
S2
S3
Stot
PF1
PF2
PF3
PFtot
phi1
phi2
phi3
EPtot, Bezug
EPtot, Rück
EQtot, ind
EQtot, kap
Spannungen
Momentanwerte
U1
U2
U3
f
I1
I2
I3
IN
P1
P2
P3
Ptot
Q1
Q2
Q3
Qtot
S1
S2
S3
Stot
PF1
PF2
PF3
PFtot
phi1
phi2
phi3
Filterwerte
U1
U2
U3
f
I1
I2
I3
IN
P1
P2
P3
Ptot
Q1
Q2
Q3
Qtot
S1
S2
S3
Stot
PF1
PF2
PF3
PFtot
phi1
phi2
phi3
Min-Werte
U1
U2
U3
f
I1
I2
I3
IN
P1
P2
P3
Ptot
Q1
Q2
Q3
Qtot
S1
S2
S3
Stot
PF1
PF2
PF3
PFtot
phi1
phi2
phi3
Max-Werte
up
down
set
V
V
V
Hz
V
V
V
Hz
V
V
V
Hz
V
V
V
Hz
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kvar
kvar
kvar
kvar
kvar
kvar
kvar
kvar
kvar
kvar
kvar
kvar
kvar
kvar
kvar
kvar
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
°
°
°
°
°
°
°
°
°
°
°
°
16

6.2 Menue
The device parameters can be changed in the menu. For a detailed description of the
parameters, see 7.2
Wandler
Filter
Digitalfunktion1
Grenzwert1
Primärstrom
Sekundärstrom
Primärspannung
Sekundärspannung
Signal Grenzwert1
Unterer Grenzwert1
Oberer Grenzwert1
Anzug erzögerung1
Abfall erzögerung1
Impulsausgang1
Signal Impulsausgang1
Impulsbewertung2
Impulslänge2
Digitalfunktion2
Grenzwert2
Signal Grenzwert2
Unterer Grenzwert2
Oberer Grenzwert2
Anzug erzögerung2
Abfall erzögerung2
Impulsausgang2
Signal Impulsausgang2
Impulsbewertung2
Impulslänge2
RS485
Baudrate
Parität
Sla eadresse
Optionen
Helligkeit
Helligkeit Ruhe
Sprache
Benutzer
Reset Min/Max
Reset Zähler h
Reset Zähler P/Q/S
Grenzwert Lastzähler
Impulsausgang1
17

7 Configuration
The parameters of the AD-LU 60 FE-B, AD-LU 60 FE-DB in chapter 7.2 can be se-
lected via the device menu itself or with the Configuration program AD-Studio . The
values in the chapter ??. Can be read, viewed or logged. This can be very helpful
especially during commissioning.
For the AD-LU 60 FE and the AD-LU 60 FE -D, the parameters can only be set on
the device menu itself.
7.1 Symbols
The following symbols are used.
P1 ... P3 Active powers in phases L1 ... L3 in kW.
Q1 ... Q3 Reactive powers in phases L1 ... L3 in kvar.
S1 ... S3 Apparent powers in the phases L1 ... L3 kVA.
Ptotal Total active power in phases L1 ... L3 in kW.
Qtotal Total reactive power in phases L1 ... L3 in kvar.
Stotal Total apparent power in phases L1 ... L3 kVA.
I1 ... I3 Currents in phases L1 ... L3 in A.
U1 ... U3 Voltages in the phases L1 ... L3 in V.
FFrequency in phase L1 in Hz.
PF1 ... PF3 Power factor in phases L1 ... L3. PFn =|P n|/Sn.
PFtotal Power factor of the entire phases in the network. P Ftotal =|Ptotal |/Stotal.
7.2 Parameters
This is followed by a reference to the parameter that can be changed via the menu on
the device or by the Configuration program AD-Studio . The table columns have the
following meaning.
Name Parameter name as found in the configuration program.
Default value In the delivery state and after setting the factory settings, the param-
eter has this value.
18

Valid Range Limits for the smallest and largest input value. For lists, a list of all
elements.
Unit Physical unit of the value.
Comments Comments or explanations.
7.2.1 Current and voltage transformers
The current and voltage converters, which are connected to the AD-LU 60 FE , are
taken into account in the calculation of the currents, voltages, power and counter and
must be known.
Name Default Range Unit
Primary current 5 1 ... 10000 A
Secondary current 5 1 ... 20 A
Primary voltage 230 50 ... 500000 V
Secondary voltage 230 50 ... 500 V
7.2.2 Filter
All measured values are filtered. The larger the filter number, the higher the effect of
the attenuation. Each measured value is filtered according to the following relationship.
Mt=Mt−1+Mt−Mt−1
F
where
•MtMeasured value at time t.
•Mt−1Measured value at time t-1, ie the last measured value.
•FValue of the filter number.
A filter number of 1 returns the current measured value unfiltered. A filter number of
2 gives the arithmetic mean value between the current and the last measured value.
The measured values are cyclically filtered. The attenuation depends on the cycle time
and the filter number. The timing is explained in chapter ??.
The relationship between settling time, cycle time and filter number is
t90 =F∗2,26 ∗tz
where
•t90 Settling time of the filtered measured value to 90 % with a signal change in
the input from 0 to 100 %.
•tzCycle time in seconds.
The desired settling time t90 can be entered directly in seconds as a parameter for
filtering the signals. The AD-LU 60 FE calculates the filter number from the settling
time and the sampling rate itself.
19

Name Default Range Unit
T90 900 1 ... 3600 s
7.2.3 Digital function at AD-LU 60 FE-D, AD-LU 60 FE-DB
The digital outputs n = 1 ... 2 can be used with various functions. The function is
disabled by default.
Name Default Range Unit
Digital function[n] off off,
Limit,
S0
Digital function ’Limit’
The following parameters apply to the digital function ’limit value’. The parameter
’Signal source’ selects the input signal to which the limit values are set. The output
is activated when the upper limit is exceeded and deactivated when the lower limit is
fallen below.
Name Default Range Unit
Signal source[n] Ptotal Ptotal, Qtotal,
Stotal, PFtotal,
U1, U2, U3,
IN, I1, I2, I3,
F, phi1, phi2, phi3
Lower Limit[n] 1 -1E6 ... 1E6 1
Upper Limit[n] 2 -1E6 ... 1E6 1
ON delay[n] 0 0 ... 3600 s
OFF delay[n] 0 0 ... 3600 s
1The unit depends on the selected source, so as ’KW’.
Digital function ’S0’
The following parameters apply to the digital function ’S0’. With this function, energy
pulses are output.
Name Default Range Unit
Signal source[n] Counter P obtain Counter P obtain
Counter P return
Counter Q ind
Counter Q cap
Counter S
Pulse value[n] 1 0,001 ... 1000 kWh/Imp,
kvarh/Imp
or kVA/Imp
1
Pulse length [n] 0,25 0,1 ... 10 s
20
This manual suits for next models
3
Table of contents