manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ADEMCO
  6. •
  7. Security System
  8. •
  9. ADEMCO 5600 Alert II User manual

ADEMCO 5600 Alert II User manual

Other ADEMCO Security System manuals

ADEMCO VISTA User manual

ADEMCO

ADEMCO VISTA User manual

ADEMCO VISTA-20PS Assembly instructions

ADEMCO

ADEMCO VISTA-20PS Assembly instructions

ADEMCO Vista-128FB  User manual

ADEMCO

ADEMCO Vista-128FB User manual

ADEMCO Vista 4140XMPT User manual

ADEMCO

ADEMCO Vista 4140XMPT User manual

ADEMCO Ademco N7001V2 User manual

ADEMCO

ADEMCO Ademco N7001V2 User manual

ADEMCO 4180 User manual

ADEMCO

ADEMCO 4180 User manual

ADEMCO VISTA-120 User manual

ADEMCO

ADEMCO VISTA-120 User manual

ADEMCO 4080 User manual

ADEMCO

ADEMCO 4080 User manual

ADEMCO 4140XMPT2 User manual

ADEMCO

ADEMCO 4140XMPT2 User manual

ADEMCO 676 User manual

ADEMCO

ADEMCO 676 User manual

ADEMCO Vista 4130XT User manual

ADEMCO

ADEMCO Vista 4130XT User manual

ADEMCO LYNXR24 User manual

ADEMCO

ADEMCO LYNXR24 User manual

ADEMCO LYNXR24 User manual

ADEMCO

ADEMCO LYNXR24 User manual

ADEMCO Vista 4140XMPT User manual

ADEMCO

ADEMCO Vista 4140XMPT User manual

ADEMCO 4110XM User manual

ADEMCO

ADEMCO 4110XM User manual

ADEMCO VISTA-20SE User manual

ADEMCO

ADEMCO VISTA-20SE User manual

ADEMCO Vector User manual

ADEMCO

ADEMCO Vector User manual

ADEMCO LYNX User manual

ADEMCO

ADEMCO LYNX User manual

ADEMCO VISTA-32FB User manual

ADEMCO

ADEMCO VISTA-32FB User manual

ADEMCO VISTA-32FB Assembly instructions

ADEMCO

ADEMCO VISTA-32FB Assembly instructions

ADEMCO Vista-10 User manual

ADEMCO

ADEMCO Vista-10 User manual

ADEMCO VISTA User manual

ADEMCO

ADEMCO VISTA User manual

ADEMCO VISTA-50P Installation guide

ADEMCO

ADEMCO VISTA-50P Installation guide

ADEMCO V12C Operating instructions

ADEMCO

ADEMCO V12C Operating instructions

Popular Security System manuals by other brands

Polon-Alfa 4000 Installation and maintenance manual

Polon-Alfa

Polon-Alfa 4000 Installation and maintenance manual

Nexcom NViS 14162 Series user manual

Nexcom

Nexcom NViS 14162 Series user manual

Eminent EM8670 Quick install

Eminent

Eminent EM8670 Quick install

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

urmet domus

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

SmartPool YardGuard YG03 manual

SmartPool

SmartPool YardGuard YG03 manual

DSC PC5964 Mounting instructions

DSC

DSC PC5964 Mounting instructions

Secure USAB-1 operating instructions

Secure

Secure USAB-1 operating instructions

B&B 480 SERIES Operation & maintenance manual

B&B

B&B 480 SERIES Operation & maintenance manual

Inner Range Concept 2000 user manual

Inner Range

Inner Range Concept 2000 user manual

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Johnson Controls

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Aeotec Siren Gen5 quick start guide

Aeotec

Aeotec Siren Gen5 quick start guide

Swann SW-P-MC2 Specifications

Swann

Swann SW-P-MC2 Specifications

Ecolink Siren+Chime user manual

Ecolink

Ecolink Siren+Chime user manual

EDM Solution 6+6 Wireless-AE installation manual

EDM

EDM Solution 6+6 Wireless-AE installation manual

Siren LED GSM operating manual

Siren

Siren LED GSM operating manual

Detection Systems 7090i Installation and programming manual

Detection Systems

Detection Systems 7090i Installation and programming manual

FRIEDLAND MA10 Installation and operating instructions

FRIEDLAND

FRIEDLAND MA10 Installation and operating instructions

Se-Kure Controls MicroMini SK-4841 instructions

Se-Kure Controls

Se-Kure Controls MicroMini SK-4841 instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

These InstructIons are applicable only to a system utilirlng a late production
Wp. 5620 Receiver/Control
(No. 5620-1, as denoted on the unit's Summary of
Connections label).
References to the Receiver/Control as the "No. 5620" have been retained herein
for brevity.
Sectlon Subject Page No.
I
III
IV
V
VI
VII
VIII
IX
X
GENERAL INFORMATION ......................................
2
SYSTEM FEATURES..........................................
2
DESCRIPTION
OF SYSTEM COMPONENTS......................... 4
A. No. 5620 Receiver/Control ............................. 4
B. No. 5621 Security Console ............................. 5
C. (Optional) No. 5608 Remote Keypad Transmitter ......... 7
0. Transmitter/Sensors ................................... 7
FUNCTIONAL DESCRIPTION OF No. 5621 SECURITY CONSOLE
AND No. 5608,REMOTE KEYPAD TRANSMITTER ................... 8
SYSTEM PROGRAMMING.......................................
A. Preliminary PROM Data ................................. ;22
B. Transmitter Programming ...............................
SYSTEM INSTALLATION AND
WIRING........................... if
A. Preliminary Considerations ............................ ,17
B. Preliminary Programning/Location Test ................. 18
C. Installation pi Wiring of No. 5620 Receiver/Control .... 21
0. Installation & Wiring of No. 5621 Security Console .... 23
E. Installation of Transmitters ..........................
SYSTEM FINAL TEST AND CHECKOUT
........................... 22;
TURNING SYSTEM OVER TO HOMEOWNER......................... 29
TROUBLESHOOTING.......................................... 29
GENERAL
SPECIFICATIONS...................................
32
Diagrams, Tables, Worksheets
Diagram 1: No. 5620 RECEIVER/CONTROL ........................... 38
Diagram 2: No. 5621 SECURITY CONSOLE
Diagram 3: No. 5608 REMOTE KEYPAD/TRANSMITTER............................................. ::
Diagram 4: TRANSMITTERS ........................................
Diagram 5: I.D. SWITCH SETTINGS ................................ t:
Diagram 6: SUMMARYOF CONNECTIONS.............................. 43
Diagram 7: SIREN SPEAKER CONFIGURATIONS.........: .............. 44
Diagram 8: No. 5603, WIRING CONNECTIONS........................ 44
Diagram 9: No. 5610, INSTALLATION DETAILS ...................... 45
Diagram 10: No. 5611, 5614 INSTALLATION DETAILS ................. 47
TABLE A:
PRELIMINARY
PROM PROGRAMMINGDATA
..................... 36
TABLE B: TRANSMITTER DATA CARD
.................................
37 .
www.PDF-Zoo.com
I:
The 5600 Wireless Alarm System is a sophisticated residential security system
that provides burglary, fire and panic (police/emergency) protection. Alarm,
status and control information Is transmitted via Ultra High Frequency
(UHF) rad.io transmission at 345 MHz to the receiver/control unit which
contains an RF receiver and a microprocessor based control unit which
recognizes alarms,
required response. status messages and control signals and produces the
An installation may include the following:
node1
No. 5620-l
No. 562;
No. 5608
No. 5603
No. 6610
hf. 5611
No. 5614
No. 5650
.No. 5605
Description Quantity
Receiver/Control 1
Security Console (wired) 1 (plus optional 2nd)
Remote Keypad/Transmitter (Optional, no max.)
Door/Window Transmitter 29 (max.) if no
Door Transmitter (Slimline Design) smoke detectors
used.
Window Transmitter (Slimline Design)
Entry/Exit Transmitter (Slimline 25 (max.)
if max. number
Design) of smoke detectors
Passive Infrared Detector/Transmitter used.
Smoke Detector Adapter/Transmitter 4 (max. total)
as req'd
No. 591TX
No. 5601
and/or
Smoke Detector for use with No. 5605 1 per No. 5605
Emergency (Panic) Transmitter
No. 5606(future) Dual Emergency (Panic) Transmitter As req'd
(no
max.)
In addition, optionally, a digital communicator (e.g. No. 678), long range
radio,transmitter (e.g. No. 7621/7622), or Derived Channel Subscriber Terminal
Unit (e.g. No. 698) may be used for remote notification of trouble and alarm
conditions.
Note:
Above does not include contacts, foil etc. that may be used with
Nos. 5603, 5611 or 5614.
II SYSTEM
FEATURES:
1.
Wireless Operation:
Burg1 ary., fire and emergency status (contact
open, contact closed, supervision check, low battery) is sent to
the No. 5620 Receiver/Control via battery powered radio transmitters.
794
687-2
www.PDF-Zoo.com
2. House Identification:
The No. 5620 recognizes 1 of 32 available house
identification numbers. Only transmitters set for and sending ,the
number set in the No. 5620 are processed. This prevents transmitters
in different residences from activating this receiver/control.
3. Transmitter Identification:
Each burglary and fire transmitter sends
a unique I.D. nunber to the No. 5620 Receiver/Control, which is displayed
on the No. 5621 Security Console in case of supervision check, low
battery, alarm or open contact. The No. 5620 can identify up to
29 different transmitters, as well as its No. 5608 Remote Keypad/Trans-
mitter(s) and up to 2 emergency (panic) zones (for low battery and
alarm) and a problem on its one wired zone.
0. Supervised Burglary and Fire Zones:
No. 5620 expects a regular,
automatic check-in message from each burglary and fire transmitter.
If no messages are 'received from a particular transmitter during
an installer-programable monitored check-in Interval (24 hours is
recommended), the No. 5621 annunciates a check-in TROUBLE message.
5. Separate Entry/Exit, Interior. and Perilleter
*burglary zones.
6. Delayed burglary protection for entry/exit zone:
Entry time can be _.
independent of exit time. INSTANT function allows entry delay to
be eliminated for greater security when the user is in residence
or away for an extended period.
7. Lou Battery Honi tori ng :
All transmitters automatically test their
batteries at regular intervals and transmit a low battery condition
when it occurs. At that time the battery will have approximately
30 days of life remaining, depending on usage.
8. Fail Safe Arming:
Burglary protection may not be turned on if any
burglary transmitter is reporting an open condition (which can be
identified on the No. 5621's display). If fault cannot be cleared,
the faulted transmitter(s) in that zone may be bypassed at the No. 5621.
9:
Plaster (Permanent) Access Code:
Al 1 keypad functions except Ready
can be activated only after entering a 4 digit access code, which
is securely maintained at the No. 5620 Receiver/Control.
10. Temporary Access Code,
which can be changed from any keypad as often
as desired for visitors, babysitters, etc..
11. Ambush digit
entered in place of last access code digit causes a
silent police alarm message to be sent to a central station (optional)
while the requested keypad function is normally executed (e.g. disarming).
12. Installation Options in PRDk
Master access code, ambush digit, entry
time, exit time, burglary siren/bell delay and cutoff times, house
I.D., AC loss warning delay, wired zone programming, "lights on"
option selections, interior zone instant/delayed response selection,
burglary transmitter zone assignments and supervision checki'period
are PROM programmed.
13. Communicator (Dialer) triggers
for the fire, bunglary (with a special
"by zone" option) and panic alarms, for loss of check-in signal,
for low battery, and for receiver/control AC ,power loss.
www.PDF-Zoo.com
14.
.1.5.
16.
17.
18.
19.
Built-in Siren Driver
with different sounds for burglary/audible
emergency (rapid or slow hi-lo) and for fire/auxiliary (interrupted
rapid hi-lo).
Tinrer Speed
Up
feature for installation test purposes.
Snap-Out Terminal Strip
for all external connections to facilitate
.printed circuit board replacement, if necessary.
One Yired Zone
on No. 5620 for convenient protection of opening(s)
nearby that may not warrant a radio transmitter or for interface
of non-wireless sensors (e.g. Inertia Crossbar System for perimeter
protection).
Keypad Timeout:
If more than 2 seconds elapse after a key stroke,
the access code and function must be reentered.
AC Loss Trouble Indication
provided when AC power is off for more
than a PROM programed interval.
III DESCRIPTIONOFSYSTEWC@4PClNENlS:
A. Ro. 5620 Receiver/Control:
(See Diagram 1)
The No. 5620 monitors all transmitters, wired sensors, keypads, and consoles
and generates appropriate output signals. It provides three supervised
zones of burglary protection (entry/exit, perimeter and interior), a supervised
24 hour fire zone, a 24hr .auxiliary/gas alarm zone and two 24hr panic
zones (police and emergency).
A built-in siren driver is provided for connection of external alarm
siren speaker(s). Alternatively, an alarm bell can be connected to the
unit's alarm relay contacts.
There are no switches inside the No.. 5620's cabinet for use during normal
operation;
however,
3 posts (located on the left side of the unit's
large
printed circuit board) are provided for test and installation aid purposes.
-If
the upper post is shorted to the middle one (SUPERVISION TEST posts),
all of the unit's timing intervals are divided by a factor of 60 (exclusive
of AC power loss timing, which becomes instant). That is, all of the
"hour" intervals become "minute" and all of the "minute" intervals become
"second" (see Section
VII
starting on Page 26) If the lower post is shorted
to the middle- posts) the system's microprocessor is reset.
The No. 5620 also contains three system fuses and a connector for an optional
digital communicator (e.g. No. 678) which may be installed in the unit's
cabinet*. The PROM that contains the system configuration is installed
in B plug-in socket on the No. 5620's printed circuit board.
+NWE: For optimum protection against electrostatic transients (e.g. light-
ning, static discharge), the communicator should be mounted
in the same cabinet
as
the receiver/control.
f--Y
.-
www.PDF-Zoo.com
B.
No. 5621 Security Cons~lc:.
(See Diagram 2)
The No. 5621 provides all system status indications and permits
all
system
control functions. The No. 5621's keypad is used to turn the burglary
protection on and off. This protection may be turned on (armed) with
or without entry delay and/or interior zone protection. During the off
(disarmed) state, the CHIME mode that provides audible and visual perimeter
annunciation, may be turned on and off. Problem sensors that are preventing
burglary system arming may be bypassed. A temporary access code may be
assigned and a user TEST mode may be activated. In addition the fire,
police, emergency and auxiliary* alarms may be manually activated at the
No. 5621. A built-in speaker provides audible alarm, check-in signal
loss, AC loss, low battery and annunciation functions and a 2 digit numeric
display gives transmitter identifications. TROUBLE indication denotes
loss of check-in (failure of the No.5620 Receiver/Control to receive periodic
check-in signals from the burglary and fire transmitters).
l NDTE:
"Auxiliary" will activate an alarm (or no alarm if so programed)
and an "all lights on" output.
A second No. 5621 may optionally be connected in parallel with the first
with a separate wiring run from the receiver/control to the console.
DO NOT "DAISY CHAIN WIRE" CONSOLES ON ONE FOUR WIRE RUN.
1.
2,
3.
4.
5.
6.
FIRE; POLICE, EMERGENCYand
AUXILIARY
indicators:
Light when the
corresponding alarms are triggered. If the Silent Police Alarm has
been selected (see Section V;A;21 on Page 14), the POLICE indicator
on the No. 5621 is never illuminated. Turn off these indicators
(and external sounder) by entering the access code followed by OFF.
AYAY and HDUE Indicators
(Red): Never both lit at the same time.
The AWAY indicator is lit while the burglary protection, including
the Interior Zone, is on. The HOME indicator is lit while the burglary
protection, not including the Interior Zone, is on. Either indicator
is turned ofmy entering the access code followed by OFF.
TEST Indicator
(Amber): Lit while the TEST feature is turned on
(see Section XV;14,15 on Page
11).
TEST feature may be turned on
only when burglary protection is off. A single beep will occur once
every 30 seconds as a reminder that the system is in the TEST mode.
BYPASS
Indicator
(Amber'): Llt while burglary protection is on with
one or more faulted transmitters bypassed. May be turned on with
the burglary protection. Always turns off when the burglary protection
is turned off.
INSTAHT
Indicator
(Amber): Lit while the burglary'protection is on
with no entry delay. May be turned on with the burglary protection.
Always turhs off when burglary protection is turned off.
READY Indicator
(Green): Lit when all burglary sensors/transmitters
have reported cl.osed loop status (no faults). May be lit only while
burglary protection is off.
797
687-5
www.PDF-Zoo.com
7.
8.
9.
10.
11.
POWERIndicator
(Green): Lit when AC power is on and out when AC
power is off. If AC power remains off for more than PROM programmed
interval, this indicator will remain out even if AC power is restored;
Then, this indicator can be lit only by entering the.access code
followed by OFF.
TRANSHITTER
IDE~IFKATION
Display:
Two digit numeric .display located
on the right hand side of the No. 5621. When rno-re than one number
must be displayed, they are shown sequentially,.repetitively. Each
number is di,splayed, for approximately 2 seconds. Located just below
this window are 3 back-lit messages which indicate the reason for
the display (see g, 10, 11, below). When the burglary protection
is off, transmitter numbers identifying open sensors may be displayed.
In this case, none of the 3 messages will be lit.
BURGLRY(so-abbreviated) Message:
Lit when a burglary alarm has
been triggered. TRANSMITTER IDENTIFICATION display indicates which
transmitter(s)
caused
the alarm. A "00" indication denotes a wired
loop disturbance. Extinguished (and external sounder silenced) by
turning off burgl.ary protection (enter access code followed by OFF)
and then again entering access code followed by OFF to clear memory
(and silence rapidly beeping No. 5621).
TROUBLEMessage:
If the burglary protection is off (or at 3 time,
if so-programmed), and no other alarms have occurred, the TROUBLE
message will light to indicate a loss of check-in problem and the
TRANSMITTER IDEKTlFICATION~display will indicate which transmitter
failed to report. The TROUBLE and BATTERY messages may be both lit,
indicating that the transmitter battery is too weak for reliable
transmission.
To check the condit,ion of the identified transmitter, force a transmission
by opening and closing the transmitter's loop (or otherwise activating
the transmitter), and enter the access code followed by OFF. If
the TROUBLE message turns off, the transmitter is all right and the
cause of the TROUBLE messa'ge has disappeared. If the same transmitter
keeps reporting TROUBLE messages, it may become necessary to relocate
the transmitter to improve its transmission path or to replace the
transmitter if it is at fault.
BATTERY Wessage:
If the burglary protection is off (or at an-y time,
if so-programmed), and no other alarms have occurred, the BATTERY
message will light to indicate a weak transmitter battery. The TRANS-
MITTER IDENTIFICATION display indicates which transmitter(s) need
new batteries (or that at least one panic transmitter needs a new
battery, if more than one panic transmitter is used with the system).
A "00" indication accompanied by a lit BATTERY message indicates
low battery in a ho. 5608 Remote Keypad/ Transmitter.
When a low BATTERY message appears, approximately 30 days of battery
life remains, but see Section X, starting on Page 32 for replacement
. . .
recommenaatlons.
798
687-6
www.PDF-Zoo.com
To turn off the BATTERY message, replace the weak battery, force
a transmission by opening and closing the loop (or otherwise activating
the transmitter), then enter the access code followed by depression
of the OFF function key. This is don2 while the burglary protection
is off. To restore the LOW BATTERY output trigger, turn burglary
protection on and off as described in Section IV: 6 and 7, page 9.
Note:
Occasionally,,even though a fresh battery has been inserted,
the BATTERY message will remain lit after the above procedure.
If
this occurs, remove the battery in question, inspect the
battery clips and reshape them, if necessary, to ensure good
contact. Reinsert the battery after two or three seconds
and repeat the "turn off" procedure.
C, (Optional) No. 5608 Remote Keypad/Transmitter:
(See Diagram 3)
The No. 5608 permits the burglary protection to be turned on and off remotely,
without interconnecting wires. Fire, police, emergency and auxiliary
alarms may also be triggered and reset from the No. 5608. No audible
or visual system status indications are provided by the No. 5608, nor
are the TEST and BYPASS functions that are on the No. 5621. A single
red indicator LEO lights wh?ie the unit is transmitting.
Note:
Burglary protection can be turned on (armed) from the No. 5608
only if there ar2 no faulted burglary transmitters.
0. Transmitter/Sensors:
(See Diagram 4)
1.
2.
3.
4.
5.
No. 5603 Door/Uindow Transmitter
(Diagram 4a): Permits protection
of doors and windows via a closed protective loop, which may contain
reed type magnetic contacts or foil. Also see Diagram 8.
No. 5610 Door Transmi.tter (Slimline Design)
(Diagram 4b): Provides
door protection with no wiring required. Transmitter unit containing
reed switch mounts on door frame and its accompanying magnet mounts
on door. Also se2 Diagram 9.
ND. 5611 Yindow Transmitter (Slimline Design)
(Diagram 4b): Particularly
convenient for mounting on narrow window frames (unit is less than
1 3/8" wide). Provides protection via a closed protective loop which
may contain reed type magnetic contacts or foil.
No. 5614 Entry/Exit Transmitter (Slimline Design)
(Diagram 4b):
Specifically configured transmission format for use on doors in the
entry/exit zone. Convenient for mounting on or adjacent to door
fram2s. Provides protection via a closed protective loop which contains
reed type magnetic contacts.
No. 5650 Passive Infrared Detector/Transmitter
'(Diagram 4~): Provides
17 zones of wide angle (75" span) coverage with a pattern range of
up to 5D feet. Separate pan and tilt controls permit pattern adjustment
to achieve dosired coverage or avoid hazards. Wall/corner mounting
plate is included for fast and easy installation. Has LED walk test
capability. Complete descriptive and installation information accompanies
the No. 5650.
799
687-7
www.PDF-Zoo.com
6.
No. 5605 Smoke Detector Adapter/Transmitter
(Diagram 4d): Provides
a base for mounting a No. 591TX Smoke Detector. Has removable drawer
for batteries which provide power for adapter's transmitter as'well
as for the smoke detector. Location and other information for the
smoke detector accompanies the No. 591TX and installation information
for the No. 5605 accompanies that unit.
7,
No. 5601 Emergency (Panic) Transmitter
(Diagram 4f): This transmitter
may be carried about the protected area in a pocket or purse or clipped
to a belt. A keyslot hole in its belt/mounting clip permits mounting
in any convenient location if desired.
Momentary activation (even for a fraction of a second) of the unit's
pushbutton will cause a signal transmission. The unit's LED lights
when the pushbutton is activated. The LED may not light if the battery
is weak (as indicated by a low BATTERY message on the No. 5621 Security
Console) but the unit may still transmit.
8.
ho. 5606 Dual Emergency (Panic) Transmitter:
(future addition).
Similar to No. 5601 Transmitter except that it has both Elrlergency
(panic) alarm and Police Alarm button capability.
IV FUNCTIONAL DESCRIPTION OF.No. 5621 SECURITYCONSOLEANDNo. S608 REMOTE
KEYPADTRANSMITTER:
The following describes how to operate the No. 5621 and 5608. Select the desired
function and push the indicated keys for the result described.
Mote :
Several functions cannot be performed from the No. 5608
as
it
is
a keypad/transmitter only and provides no sounds or indications
except a red indicator which lights when it is transmitting.
1. TO TRIC6ER FIRE, POLICE, EMERGENCYAND/OR ‘AUXILIARY ALARM AT ANY
TM:
PUSH BOTH ALARM KEYS
(FIRE-FIRE, POLICE-POLICE, EHERG-EMERG
OR AUX-AUX) AT THE SAME TIME.
External Siren/bell and No. 5621 Security Console speaker's sound
will begin immediately (unless POLICE - Pt'lLICE is pushed and silent
POLICE alarm has been programmed and/or if the Auxiliary zone has
been programmed for "all lights on" operation or just as an interior
audible alarm zone). The LED (No. 5621 only) between the pushed
keys will light. Communicator (optional) will send message to central
station.
2.
TO TRI66ER ACIBUSH
(SILENT
POLICE)
Au\Iw (via optional communicator):
ENTERFIRST
3 DIGITS (ONLY)
OF 4
DIGIT
ACCESS CODE, FOLLOWED BY PROGRAMMED
AMBUSH DIGIT, FOLLOWED BY DEPRESSION OF KEY FOR REOUESTED FUNCTION
(OFF, AMAY, HWE,
ETC).
Silent police alarm will be sent to central station via (optional)
communicator, while desired function is executed.
800
687-8
www.PDF-Zoo.com
3.
4.
5.
6.
7.
TO TURNOFFANYALARM
IN
PROGRESS:
ENTER
4 DIGIT
ACCESS
CODE’IM’IEDIATELY
FOLLOWED BY DEPRESSION OF
DFF
FUNCTION KEY.
Siren/bell will stop, No. 5621's transmitter
I.D.
display will indicate
transmitter(s) that
caused
alarm (alarm memory). Note:
If a
transmitter
is activated during the armed period, the siren/bell will sound for
the programmed time and then turn off. Alarms from that transmitter
(PROM option) are ignored thereafter until the system is disarmed;
however, other transmitters are still capable of initiating an alarm
and an additional siren/bell sounding interval.
To clear display,.enter access code again, followed by depression
of the OFF function key.
TO
CHECKF(IR FAULTEDTRANSUITlER(S) BEFORElURNIN6DNBW6LARY
PROTECTION
(No. 5621
only.): If READY LED IS LIT, NO TRANSMITTERS ARE FAULTED.
DTHERWISE PUSH READY FUNCTION KEY.
Faulted transmitter number(s) will be displayed.
TO TURN ON BURGLARYPROTECTIONWHENHONE
IS
NOT
6OIffi
TO BE OCCUPIED:
ENTER ACCESS CODE IMMEDIATELY FOLLOWED BY DEPRESSION OF
AUAY
FUNCTION
KEY. MAY BE FOLLOWED BY FUNCTION 9 AND/OR 10 BELOW. LEAVE BEFORE
EXIT OELAY PERIOD ENDS.
If
no transmitters are faulted, the No. 5621 will beep twice and
the AWAYindicator will light. Otherwise, one beep is heard (indicating
that the burglary protection.is still off) and the faulted transmitter
number(s) will be displayed.
NOTE: If the system is armed in the HOME mode, it is 'possible
to arm it directly into the AWAY mode when leaving. However,
if a fault is present in the interior zone when this is
attempted, the system's burglary protection will turn off.
TO
TURNON
BURGLARY
PROTECTION
MILE
HOMEIS OCCUPIED:
ENTER ACCESS
CODE IMMEDIATELY FOLLOWED BY DEPRESSION OF
HDHE
FUNCTION KEY. MAY
BE FOLLOWED BY FUNCTION 9 AND/OR
10
BELOW.
If
no transmitters are faulted, the No. 5621 will beep 3 times and
the HOME indicator will light. Otherwise one beep is heard and the
faulted transmitter number(s) will be
displayed.
Interior zone sensors/
transmitters are automatically bypassed.while the rest of the burglary
protection is armed.
jOT&:
If the system is armed in the AWAY mode, it is possible
to arm it directly into the HOME mode upon entering without
causing an alarm.
TO
TURN
OFFBURGLARYPRUTECTIOW:
ENTER 'ACCESS
CODEIM’lEDIAfELY
FOLLOWED
BY DEPRESSION OF OFF FUNCTION KEY (COMPLETE REFGRE ENTRY DELAY PERIOD,
IF ANY, ENDS WHEH REENTERING HOME AFTER BEING AWAY).
801
687-9
www.PDF-Zoo.com
If entering and no alarm(s) had,occurred, the No. 5621's sounder
will begin beeping slowly when home is entered. If alarm(s) had
occurred, it will begin beeping rapidly (or.be silent if the alarm
had occurred in the entry/exit zone). After the burglary protection
is turned off, the No. 5521 will beep once if there had been no alarms.
Otherwise, the faulted transmitter number(s) will be displayed (alarm
memory).
9. TO TURN BURGLARYPROTECTION ON AND BYPASSFAUhD TRANSMITTERS(AS
INDICATEDBY FUNCTION
4
ABOVEAND
ONLY
AT
MO. 5621): PERFORM EITHER
FUNCTION 5 or 6 ABOVE, IMMEDIATELY FOLLOWED BY DEPRESSION OF
BYPASS
FUNCTION KEY.
Same result as either function 5 or 6 above, except BYPASS indicator
will be lit and any faulted transmitters will be bypassed. All bypasses
are automatically removed when the burglary protection is turned
off.
jJOTJ: If the system is armed in the AWAY (HOME) mode and it is
armed directly into the HOME (AWAY) mode, any bypasses
present in the earlier mode are maintained in the later
arming mode only if the BYPASS key is pressed as part of
the later arming procedure.
10. TO TURN BURGLARYPROTECT1ON ON ANDMAKEENTRYZONEAN INSTANTALARH
ZOE (NDENTRYDELAY):
PERFORMEITHER .FUNCTIDN 5 DR.6 ABOVE, IMMEDIATELY
FOLLOWED BY DEPRESSION OF
INSTANT
FUNCTION KEY.
Same result as either function 5 or 6 above, except INSTANT indicator
will be lit and (after expiration of exit delay) .entry will trigger
immediate alarm. When the burglary protection is turned off, the
entry delay is automatically returned to normal.
11. TO ASSIGN
EY TEMPORARY
ACCESSCODE:
ENTER 4 NUMBERS OF MASTER (PER-
MANENT) ACCESS CODE, IMMEDIATELY FOLLOWED BY DEPRESSION OF
ACCESS
FUNCTION KEY, IMMEDIATELY FOLLOWED BY THE ENTRY OF 4 NUMBERS CHOSEN
FOR TEMPORARY ACCESS CODE. CHECK BY ENTERING NEW TEMPORARY ACCESS
CODE FOLLOWED BY DEPRESSION OF
OFF
FUNCTION KEY. INTERIOR SOUNDER
WILL BEEP ONCE IF NEW CODE IS IN EFFECT.
Caution:
The 4th digit chosen for the temporary access code must
be different from the programmed Ambush digit. Ambush
alarms may be triggered with either the master or temporary
access code as described under Function 2 above. If the
4th digit chosen is the same as the programned Ambush digit,
there will be no ambush capability for the temporary access
code until the code is changed to one where the 4th digit
chosen is not the same as the Ambush digit.
The
master
access code, PROM programed at the time of installation,
never changes and can be used at any time. 'Its use should be limited
to the owner of'the system. The
temporary
access code may be changed
whenever desired and allows others temporary access to the home.
Rote:
Burglary protection turned on by using the
master
access code
can only be turned off by using the
master
access code, although
if turned on with the
temporary
access code, it may be turned off
by either the
temporary
or
master
code.
,/-T j
/’
;f-----l
802
687-l 0
www.PDF-Zoo.com