Admag AXF User manual

User’s
Manual
Yokogawa Electric Corporation
AXF
Magnetic Flowmeter
Integral Flowmeter/
Remote Flowtube
[Hardware Edition]
Manual Change No. 13-009-E
Aug. 30, 2013
Please use the attached sheets for the pages listed below in IM 01E20D01-01E (10th).
Page and Item
Page 1-2, 1-3
1.1 Using the Magnetic Flowmeter Safety
Page 1-4, 1-5, 1-6
1.3 Combination Remote Converters
1.4 ATEX Documentation
Page 3-3
Figure 3.2.1, Lifting Flowmeter
Page 4-4
(3) Precautions for Wiring of Power
Supply Cables
Page 4-6
Figure 4.1.10, 4 to 20 mA DC Output
Connection
Figure 4.1.12, Active Pulse Output Con-
nection (Optional code EM)
Page 4-8
4.2 Wiring the Remote Flowtube
Page 6-10
Withstand Voltage
Page 6-11
Safety Requirement Standards
Page 8-5
8.3 CSA
Contents of Correction
Added the warning notes in (1) installation, (3)
Operation, and (4) Maintenance.
Changed the page number.
Changed the page number.
Added another horizontal position figure.
Changed the numbers of “IEC” in warning note.
Changed the value of maximum load resistance.
Changed the figure.
Added the important note on “wiring”.
Changed the values of the withstand voltage.
Added the number of “EN” standard.
Changed the number of Applicable Standard
in (1) Technical Data.

IM 01E20D01-01E
1. INTRODUCTION
IMPORTANT
An IMPORTANT sign denotes that attention is
required to avoid damage to the instrument or
system failure.
NOTE
A NOTE sign denotes information necessary for
essential understanding of operation and fea-
tures.
Protective grounding terminal
Functional grounding terminal
(This terminal should not be used as a protective
grounding terminal.)
Alternating current
Direct current
1.1 Using the Magnetic
Flowmeter Safely
(1) Installation
WARNING
•Installation of the magnetic flowmeter must be
performed by expert engineer or skilled person-
nel. No operator shall be permitted to perform
procedures relating to installation.
• The magnetic flowmeter must be installed
within the specification conditions.
•The magnetic flowmeter is a heavy instrument.
Be careful that no damage is caused to person-
nel through accidentally dropping it, or by
exerting excessive force on the magnetic
flowmeter. When moving the magnetic flowme-
ter, always use a trolley and have at least two
people carry it.
•When the magnetic flowmeter is processing hot
fluids, the instrument itself may become ex-
tremely hot. Take sufficient care not to get
burnt.
•Where the fluid being processed is a toxic
substance, avoid contact with the fluid and
avoid inhaling any residual gas, even after the
instrument has been taken off the piping line for
maintenance and so forth.
•Do not apply excessive weight, for example, a
person stepping on the magnetic flowmeter.
•All procedures relating to installation must
comply with the electrical code of the country
where it is used.
(2) Wiring
WARNING
•The wiring of the magnetic flowmeter must be
performed by expert engineer or skilled person-
nel. No operator shall be permitted to perform
procedures relating to wiring.
•When connecting the wiring, check that the
supply voltage is within the range of the voltage
specified for this instrument before connecting
the power cable. In addition, check that no
voltage is applied to the power cable before
connecting the wiring.
•The protective grounding must be connected
securely at the terminal with the mark to
avoid danger to personnel.
(3) Operation
WARNING
•When opening the cover, wait for more than 10
minutes after turning off the power. Only
expert engineer or skilled personnel are permit-
ted to open the cover.
• Do not open the cover in wet weather or humid
environment. When the cover is open, stated
enclosure protection is not applicable.
•Be sure to set parameters as “Protect” on the
write protect function after finish of parameter
setting work.
Under extremely rare case, the infra-red
switches may respond unexpectedly in such
conditions as sticking ball of water or extrane-
ous substances on the surface of display panel
glass according to the principle of infra-red
switch operation.
Its probability rises in such cases as sticking
rain water by storm or other similar situation
and washing up work near flowmeter installa-
tion place.
Either to illuminate or stop illuminating the infra-
red switches by the flashlight may cause the
mis-reaction.
Refer to Chapter 6 “Menu P: Parameter Protec-
tion Items” in the manual IM 01E20C02-01E
and section “5.2.2” reading the write protect
function in detail.
1-2

IM 01E20D01-01E
1. INTRODUCTION
(4) Maintenance
WARNING
•Maintenance of the magnetic flowmeter should
be performed by the trained personnel having
knowledge of safety standard. No operator
shall be permitted to perform any operations
relating to maintenance.
•When opening the cover, wait for more than 10
minutes after turning off the power.
• Do not open the cover in wet weather or humid
environment. When the cover is open, stated
enclosure protection is not applicable.
•Always conform to maintenance procedures
outlined in this manual. If necessary, contact
Yokogawa.
•Care should be taken to prevent the build up of
dirt, dust or other substances on the display
panel glass or data plate. If these surfaces do
get dirty, wipe them clean with a soft dry cloth.
(5) Explosion Protected Type Instrument
WARNING
•Magnetic flowmeters with the model name
AXFⵧⵧⵧC are products which have been
certified as explosion proof type instruments.
Strict limitations are applied to the structures,
installation locations, external wiring work,
maintenance and repairs, etc. of these instru-
ments. Sufficient care must be taken, as any
violation of the limitations may cause danger-
ous situations.
Be sure to read Chapter 8 “EXPLOSION
PROTECTED TYPE INSTRUMENT” before
handling the instruments. The description in
Chapter 8 is prior to the other description in this
user’s manual.
For TIIS flameproof type instruments, be sure
to read “INSTALLATION AND OPERATING
PRECAUTIONS FOR TIIS FLAMEPROOF
EQUIPMENT” at the end of this manual.
•Only trained persons use this instrument in the
industrial location.
•The protective grounding must be connected
to a suitable IS grounding system.
•Take care not to generate mechanical spark
when access to the instrument and peripheral
devices in hazardous locations.
(6) European Pressure Equipment Directive
(PED)
WARNING
•When using the instrument in compliance with
PED, be sure to read Chapter 7 before use.
1.2 Warranty
•The terms of this instrument that are guaranteed are
described in the quotation. We will make any repairs
that may become necessary during the guaranteed
term free of charge.
•Please contact our sales office if this instrument
requires repair.
•If the instrument is faulty, contact us with concrete
details about the problem and the length of time it
has been faulty, and state the model and serial
number. We would appreciate the inclusion of
drawings or additional information.
•The results of our examination will determine
whether the meter will be repaired free of charge or
on an at-cost basis.
䊏The guarantee will not apply in the following
cases:
•Damage due to negligence or insufficient mainte-
nance on the part of the customer.
•Problems or damage resulting from handling,
operation or storage that violates the intended use
and specifications.
•Problems that result from using or performing
maintenance on the instrument in a location that
does not comply with the installation location
specified by Yokogawa.
•Problems or damage resulting from repairs or
modifications not performed by Yokogawa or
someone authorized by Yokogawa.
•Problems or damage resulting from inappropriate
reinstallation after delivery.
•Problems or damage resulting from disasters such as
fires, earthquakes, storms, floods, or lightning strikes
and external causes.
䊏Trademarks:
ADMAG, AXF and ADMAG AXF are registered
trademarks of Yokogawa Electric Corporation.
Company names and product names used in this
material are registered trademarks or trademarks of
their respective owners.
1-3

IM 01E20D01-01E
1. INTRODUCTION
1.3 Combination Remote
Converters
IMPORTANT
•The AXF remote flowtube (size 2.5 (0.1 in.) to
400 mm (16 in.)) should be used in combina-
tion with one of the following converters:
- AXFA11 remote converter
- AXFA14 remote converter
Contact Yokogawa before using it in combina-
tion with converters other than those listed
above.
•The AXF remote flowtube (size 500 (20 in.) to
2600 mm (104 in.)) should be used in combina-
tion with AXFA11 remote converter.
Contact Yokogawa before using it in combina-
tion with converters other than AXFA11.
•In case of TIIS Flameproof type, a remote
flowtube is available for combined use with the
AXFA14 remote converter only.
•If the converter combined with the AXF mag-
netic flowmeter’s remote flowtube is changed
from the AXFA11 to AXFA14 or vice versa, the
meter factor of the remote flowtube must be
readjusted according to its flow calibration.
1-4

IM 01E20D01-01E
1. INTRODUCTION
1.4 ATEX Documentation
This procedure is only applicable to the countries in
European Union.
GB
All instruction manuals for ATEX Ex related products
are available in English, German and French. Should
you require Ex related instructions in your local
language, you are to contact your nearest Yokogawa
office or representative.
DK
Alle brugervejledninger for produkter relateret til
ATEX Ex er tilgængelige på engelsk, tysk og fransk.
Skulle De ønske yderligere oplysninger om håndtering
af Ex produkter på eget sprog, kan De rette
henvendelse herom til den nærmeste Yokogawa
afdeling eller forhandler.
I
Tutti i manuali operativi di prodotti ATEX
contrassegnati con Ex sono disponibili in inglese,
tedesco e francese. Se si desidera ricevere i manuali
operativi di prodotti Ex in lingua locale, mettersi in
contatto con l’ufficio Yokogawa più vicino o con un
rappresentante.
E
Todos los manuales de instrucciones para los productos
antiexplosivos de ATEX están disponibles en inglés,
alemán y francés. Si desea solicitar las instrucciones de
estos artículos antiexplosivos en su idioma local,
deberá ponerse en contacto con la oficina o el
representante de Yokogawa más cercano.
NL
Alle handleidingen voor producten die te maken
hebben met ATEX explosiebeveiliging (Ex) zijn
verkrijgbaar in het Engels, Duits en Frans. Neem,
indien u aanwijzingen op het gebied van
explosiebeveiliging nodig hebt in uw eigen taal, contact
op met de dichtstbijzijnde vestiging van Yokogawa of
met een vertegenwoordiger.
SF
Kaikkien ATEX Ex -tyyppisten tuotteiden käyttöhjeet
ovat saatavilla englannin-, saksan- ja ranskankielisinä.
Mikäli tarvitsette Ex -tyyppisten tuotteiden ohjeita
omalla paikallisella kielellännne, ottakaa yhteyttä
lähimpään Yokogawa-toimistoon tai -edustajaan.
P
Todos os manuais de instruções referentes aos produtos
Ex da ATEX estão disponíveis em Inglês, Alemão e
Francês. Se necessitar de instruções na sua língua
relacionadas com produtos Ex, deverá entrar em
contacto com a delegação mais próxima ou com um
representante da Yokogawa.
F
Tous les manuels d’instruction des produits ATEX Ex
sont disponibles en langue anglaise, allemande et
française. Si vous nécessitez des instructions relatives
aux produits Ex dans votre langue, veuillez bien
contacter votre représentant Yokogawa le plus proche.
D
Alle Betriebsanleitungen für ATEX Ex bezogene
Produkte stehen in den Sprachen Englisch, Deutsch
und Französisch zur Verfügung. Sollten Sie die
Betriebsanleitungen für Ex-Produkte in Ihrer
Landessprache benötigen, setzen Sie sich bitte mit
Ihrem örtlichen Yokogawa-Vertreter in Verbindung.
S
Alla instruktionsböcker för ATEX Ex (explosionssäkra)
produkter är tillgängliga på engelska, tyska och
franska. Om Ni behöver instruktioner för dessa
explosionssäkra produkter på annat språk, skall Ni
kontakta närmaste Yokogawakontor eller representant.
GR
ATEX Ex
, .
Ex
Yokogawa .
1-5

IM 01E20D01-01E
1. INTRODUCTION
LT
LV
PL
EST
SLO
H
BG
RO
M
CZ
SK
1-6

IM 01E20D01-01E
3. INSTALLATION
• Mounting orientation
IMPORTANT
If electrodes are perpendicular to the ground, air
bubbles near the top or precipitates at the
bottom may cause measurement errors. Ensure
that the terminal box of a remote flowtube and
converter of an integral flowmeter are mounted
above the piping to prevent water from entering
them.
F0306.EPS
Correct
Incorrect
Electrode
Air bubble
Precipitate
Electrode
Incorrect
Water can
seep into
the terminal
box.
Figure 3.1.6 Mounting Orientation
3.2 Handling Precautions
WARNING
The magnetic flowmeter is a heavy instrument.
Be careful that no damage is caused to person-
nel through accidentally dropping it, or by
exerting excessive force on the magnetic flow-
meter. When moving the magnetic flowmeter,
always use a trolley and have at least two
people carry it.
NOTE
This chapter describes the remote flowtube as
an example. The same attention must be paid to
the integral flowmeter.
3.2.1 General Precautions
(1) Precaution during Transportation
The magnetic flowmeter is packed tightly. When it is
unpacked, pay attention to prevent damaging the
flowmeter. To prevent accidents while it is being
transported to the installing location, transport it to the
site in its original packing.
CAUTION
In order to lift a magnetic flowmeter that is fitted
with eyebolts, proceed as in Figure 3.2.1. Never
lift it using a bar passed through the flowtube as
this damages the liner severely.
Horizontal position Vertical position,
using block and tackle
F0307.EPS
Figure 3.2.1 Lifting Flowmeter
(2) Avoid Shocks from Impact
CAUTION
Care should be taken not to drop the flowmeter
or expose it to excessive shock. In particular, be
careful not to subject the flange surface to
shock. This may lead to liner damage which will
result in inaccurate readings.
(3) Flange Protection Covers
IMPORTANT
Keep the protective covering (i.e. the corrugated
cardboard or other cushioning material) in place
over the flange except when mounting the
flowmeter to the pipe.
3-3

IM 01E20D01-01E
4. WIRING
•Install an external switch or circuit breaker as a
means to turn the power off (capacitance; 15A,
conforming to IEC60947-1 and IEC60947-3).
Locate this switch either near the instrument or
in other places facilitating easy operation. Affix
a “Power Off Equipment” label to this external
switch or circuit breaker.
Wiring Procedure
1. Turn the instrument's power off.
2. Wire the power supply cable and the functional
grounding cable to the power supply terminals.
F0407.EPS
+
SUPPLY
DIO
POWE
-
+
/
LN
/
I
-++
-
D
-
Functional grounding cable
Power supply
cable
Figure 4.1.7 Electric Cable Wiring
(4) DC Power Connection
When using DC power as the power supply for the
converter, give attention to the following points.
1) Connecting Power Supply
IMPORTANT
Do not connect power supply with reversed
polarities.
L/+ terminal: connect +
N/
–
terminal: connect
–
IMPORTANT
Do not connect power supply with 100 to 240 V
AC or 100 to 120 V DC in the case of a 24 V
power supply version (power supply code 2).
It will give a damage to the converter.
2) Required Power Supply Voltages
IMPORTANT
When using a 24 V power supply, the specifica-
tion for the supply voltage is 24 V (–15% to
+20%), but the input voltage of the converter
drops due to cable resistance therefore it must
be used within the following ranges.
Supply Voltage and Cable Length
020.4 22 24 26 28.8
200 ( 660)
446 (1460)
600 (1970)
796 (2610)
F0408.EPS
Cable cross section area: 1.25 mm
2
Cable cross section area: 2 mm
2
Allowable cable length m(ft)
Usable range E (V)
3) Setting Power Supply Frequency
IMPORTANT
Set the local commercial power frequency in
order to eliminate the effect of induction noise
from the power supply.
Refer to “Chapter 6: Parameter Description” in
the user’s manual of the AXF Integral Flowmeter
[Software Edition] (IM 01E20C02-01E).
Parameter No.: J30 and J31
(5) Grounding
CAUTION
Be sure to connect the protective grounding of
the AXF integral flowmeter with a cable of 2mm2
or larger cross section in order to avoid electrical
shock to the operators and maintenance engi-
neers and to prevent the influence of external
noise.
Connect the grounding wire to the mark.
The grounding should satisfy Class D require-
ments (ground resistance, 100 or less).
In case of TIIS Flameproof type, the grounding
should satisfy Class C requirements (ground
resistance, 10 or less) or class A requirements
(ground resistance, 10 or less).
4-4

IM 01E20D01-01E
4. WIRING
Connect the AXF integral flowmeter terminal to
external instruments, giving attention to the following
points.
For FOUNDATION Fieldbus protocol, please refer to IM
01E20F02-01E.
For PROFIBUS PA protocol, please refer to IM
01E20F12-01E.
䊉4 to 20 mA DC Current Output
Resistive load max. 750 Ω
Receiver
Instrument
AXF integral flowmeter l+
l-
F0411.EPS
Communication
Resistive load
BRAIN
HART
250 to 450
Ω
250 to 600
Ω
Figure 4.1.10 4 to 20 mA DC Output Connection
䊉Pulse Output
IMPORTANT
• As this is a transistor contact (insulated type),
give attention to proper voltage and polarity
when wiring.
• Do not apply a voltage larger than 30V DC or a
current larger than 0.2A in order to prevent
damage to the instrument.
• When input filter constant of the electronic
counter is large in relation to the pulse width,
the signal will decrease and the count will not
be accurate.
• If the input impedance of the electronic counter
is large, an induction noise from the power
supply may result in inaccurate counts. Use a
shield cable or sufficiently reduce the input
impedance of the electronic counter within the
electromagnetic flowmeter pulse output specifi-
cation range.
• The active pulse output (Optional code EM)
cannot be used in conjunction with the standard
pulse output.
• When the active pulse output (Optional code
EM) is selected, do not be short-circuit between
the DO+ and DO– terminals to avoid damaging
the instrument.
• When the active pulse output (Optional code
EM) is selected, the range of pulse rate must
be set to 2 pps maximum.
• To avoid communication (BRAIN/ HART)
failure, it is recommended to use the shield
cable.
NOTE
For pulse output from the DO terminals, param-
eters must be set. Refer to “Parameter Descrip-
tion” in the user’s manual of the AXF Integral
Flowmeter [Software Edition] (IM 01E20C02-
01E).
F0412.EPS
Mechanical Counter
Electronic Counter
Load
Protective diode
30V DC, 0.2A. max
PULSE OUT
PULSE OUT
AXF integral flowmeter
AXF integral flowmeter
DO+
DO-
DO+
DO-
Figure 4.1.11 Pulse Output Connection
F0413.EPS
Protective diode
PULSE OUT
AXF integral flowmeter
AXF integral flowmeter
DO+
DO-
DO+
DO-
Output voltage: 24 V DC ⫾20%
Current: 150 mA or less
Pulse rate: 0.0001 to 2 pps
Pulse width: 20, 33, 50, 100 ms
Mechanical Counter
Electronic Counter
Load
PULSE OUT
Figure 4.1.12 Active Pulse Output Connection
(Optional code EM)
4-6

IM 01E20D01-01E
4. WIRING
4.2 Wiring the Remote
Flowtube
This section describes the wiring of the remote
flowtube only. For information relating to the wiring of
the converter, refer to the user’s manual of the
AXFA11 Magnetic Flowmeter Remote Converter (IM
01E20C01-01E) or the AXFA14 Magnetic Flowmeter
Remote Converter (IM 01E20C02-01E).
WARNING
The wiring of the magnetic flowmeter must be
performed by expert engineer or skilled person-
nel. No operator shall be permitted to perform
procedures relating to wiring.
CAUTION
Once all wiring is complete, check the connec-
tions before applying power to the instrument.
Improper arrangements or wiring may cause a
unit malfunction or damage.
4.2.1 Wiring Precautions
Be sure to observe the following precautions when
wiring:
CAUTION
• In cases where the ambient temperature
exceeds 50°C (122°F), use external heat-
resistant wiring with a maximum allowable
temperature of 70°C (158°F) or above.
• Do not connect cables outdoors in wet weather
in order to prevent damage from condensation
and to protect the insulation, e.g. inside the
terminal box of the flowtube.
• Do not splice the cable between the flowtube
terminal and the converter if it is too short.
Replace the short cable with a cable that is the
appropriate length.
• All the cable ends must be provided with round
crimp-on terminals and be securely wired.
• The signal cables must be routed in separate
steel conduit tubes 16 (JIS C 8305) or flexible
conduit tubes 15 (JIS C 8309).
• Keep conduits or flexible tubes watertight using
sealing tape.
• Ground the remote flowtube and the converter
separately.
• Cover each shield of the signal cable with vinyl
tube or vinyl tape to avoid contact between two
shields or between a shield and a case.
• When waterproof glands or union equipped
waterproof glands are used, avoid tightening
the glands with an excessive torque.
• Be sure to turn the power off before opening
the terminal box cover.
• Before turning the power on, tighten the
terminal box cover securely.
• The terminal box cover of size 2.5 mm to 1000
mm is locked by the special screw. In case of
opening the terminal box cover, use the hex-
agonal wrench attached. For handling the
locking screw, refer to Figure 4.2.8.
• Be sure to lock the cover of size 2.5 mm to
1000 mm by the special screw using the
hexagonal wrench attached after installing the
cover. For handling the locking screw, refer to
Figure 4.2.20.
• Explosion protected types must be wired in
accordance with specific requirement (and, in
certain countries, legal regulations) in order to
preserve the effectiveness of their explosion
protected features.
•When submersible type or optional code DHC
is selected, waterproof glands, signal and
excitation cables are attached.
In order to preserve the effectiveness of
waterproof features, the terminal box cover and
waterproof glands must not be detached from
flowmeter.
IMPORTANT
Prepare the signal cable and the excitation cable
almost the same length. It is recommended to
lay them together closely.
4-8

IM 01E20D01-01E
6. OUTLINE
Polyurethane Rubber /Natural Soft Rubber /
EPDM Rubber Lining:
Size mm (in.)
V 0.3 (1.0) 1.0 mm/s
0.3 V 10
(1.0) (33) 0.35% of Rate
25 (1.0)
to
400 (16)
Flow Velocity
V m/s (ft/s)
Standard Accuracy
(Calibration code B)
V 0.3 (1.0) 1.75 mm/s
0.3 V 1
(1.0) (3.3)
1 V 10
(3.3) (33) 0.35% of Rate
0.25% of Rate 1 mm/s
500 (20)
to
1000 (40)
V 0.3 (1.0) 2.2 mm/s
0.3 V 1
(1.0) (3.3) 0.4% of Rate 1 mm/s
1 V 10
(3.3) (33) 0.5% of Rate
1100 (44)
to
2000 (80)
V 1 (3.3) 8.5 mm/s
1 V 10
(3.3) (33) 0.85% of Rate
2200 (88)
to
2600 (104)
T09.EPS
Enhanced dual frequency excitation(Option code HF2) :
Standard accuracy 1 mm/ s
Size 25 mm (1.0 in.) to 400 mm (16 in.)
1.2
1.0
0.8
0.6
0.4
0.35
0.2
0
012 6810
V[m/s]
High grade Accuracy
High grade Accuracy
Standard Accuracy
F14.EPS
Pulse
Output
Accuracy
% of Rate
Size 500 mm (20 in.) to 1000 mm (40 in.)
1.2
1.0
0.8
0.6
0.4
0.35
0.2
0
012 6810
V[m/s]
F16-1.EPS
Pulse
Output
Accuracy
% of Rate
High grade Accuracy
High grade Accuracy
Standard Accuracy
Size 1100 mm (44 in.) to 2000 mm (80 in.)
1.2
1.0
0.8
0.6
0.4
0.2
0
012 6810
V[m/s]
F16-2.EPS
Pulse
Output
Accuracy
% of Rate
0.5
High grade Accuracy
High grade Accuracy
Standard Accuracy
Size 2200 mm (88 in.) to 2600 mm (104 in.)
2.4
2.0
1.6
1.2
0.85
0.8
0.4
0
012 6810
V[m/s]
F16-3.EPS
Pulse
Output
Accuracy
% of Rate
High grade Accuracy
High grade Accuracy
Standard Accuracy
Current Output “䉫”: Pulse output accuracy plus
0.05% of Span
Repeatability:
0.1% of Rate (V 1 m/s (3.3 ft/s))
0.05% of Rate 0.5 mm/s (V < 1 m/s (3.3 ft/s))
Maximum Power Consumption:
Integral Flowmeter: 12W
Remote Flowtube: Combined with AXFA11: 20W
Combined with AXFA14: 12W
Insulation Resistance (*1):
Integral Flowmeter:
Between power supply terminals and ground
terminalm : 100MΩat 500V DC
Between power supply terminals and input /output
terminals : 100MΩat 500V DC
Between ground terminal and input/output
terminals : 20MΩat 100V DC
Between input/output terminals : 20MΩat 100V DC
Remote Flowtube:
Between excitation current terminal and signal /common
terminals : 100MΩat 500V DC
Between signal terminals : 100MΩat 500V DC
Between signal terminals and common terminal (C) :
100MΩat 500V DC
Withstand Voltage (*1):
Integral Flowmeter
Between power supply terminals and ground terminal :
1400V AC for 2 seconds
Between power supply terminals and input/output
terminals : 1400V AC for 2 seconds
Remote Flowtube (option code JF3, KF2, CF1, and SF2)
Between excitation current terminal and ground terminal
: 1500V AC for 1 minute
Between signal terminals and ground terminal :
1500V AC for 1 minute
Between signal terminals and excitation current terminal
: 2000V AC for 1 minute
Remote Flowtube (option code FF1)
Between signal terminals and ground terminal : 500V
AC for 1 minute or 600V AC for 1 second
Between signal terminals and excitation current terminal
: 2000V AC for 1 minute or 2400V AC for
1 second.
6-10

IM 01E20D01-01E
6. OUTLINE
CAUTION
*1: When performing the Insulation Resistance Test or the
Withstand Voltage Test, please obey the following
caution.
•Following the relevant test, wait for more than 10
seconds after the power supply has been turned off
before removing the cover.
•Remove all wires from terminals before testing.
•When the power terminal has a lighting protector
(optional code A), remove the short bar at the ground
terminal.
•After testing, be sure to discharge by using a resistance
and return all wires and the short bar to its correct
position.
•Screws must be tightened to a torque of 1.18 N-m or
more.
•After closing the cover, the power supply can be
restored.
Safety Requirement Standards:
EN61010-1
EN61010-2-030
•Altitude at installation site: Max. 2000 m above sea leve
•Installation category based on IEC1010:
Overvoltage category II (“II” applies to electrical equip-
ment which is supplied from the fixed installation like
distribution board.)
•Pollution degree based on IEC1010
Pollution degree 2 (“Pollution degree” describes the
degree to which a solid, liquid, or gas which deteriorates
dielectric strength or surface resistivity is adhering. “2”
applies to a normal indoor atmosphere.)
EMC Conformity Standards: ,
EN61326-1 Class A, Table 2 (For use in industrial locations)
EN61326-2-3
EN61000-3-2 ClassA
EN61000-3-3
CAUTION
This instrument is a class A product, and it is designed for
use in the industrial environment.
Please use this instrument in the industrial environment
only.
■NORMAL OPERATING CONDITIONS
Ambient Temperature: –40°to +60°C (–40°to +140°F)
*1: Minimum temperature should also be limited according
to minimum fluid temperature of flow tube’s
specification.
Refer to description of “Fluid Temperature and
Pressure”.
*2: Indicator’s operating range (integral flowmeter): –20°to
+60°C (–4°to +140°F)
*3: Maximum temperature should be +50°C (+122°F) in the
case of power supply code 2 (integral flowmeter).
Ambient Humidity: 0 to 100%
Lengthy continuous operation at 95% or more is not
recommended.
Power Supply (integral flowmeter):
Power supply code 1:
•AC specifications
Rated power supply: 100 to 240 V AC, 50/60 Hz
(Operating voltage range: 80 to 264 V AC)
•DC specifications
Rated power supply: 100 to 120 V DC
(Operating voltage range: 90 to 130 V DC)
Power supply code 2:
•AC specifications
Rated power supply: 24 V AC, 50/60 Hz
(Operating voltage range: 20.4 to 28.8 V AC)
•DC specifications
Rated power supply: 24 V DC
(Operating voltage range: 20.4 to 28.8 V DC)
Supply Voltage and
Cable Length for Power Supply Code 2
020.4 22 24 26 28.8
200 ( 660)
446 (1460)
600 (1970)
796 (2610)
F01.EPS
Cable cross section area: 1.25 mm2
Cable cross section area: 2 mm2
Allowable cable length m(ft)
Usable range E (V)
Fluid Conductivity:
Size 2.5 to 10 mm (0.1 to 0.4 in.): 5 µS/cm or larger
Size 15 to 125 mm (0.5 to 5 in.): 1 µS/cm or larger
Size 150 to 400 mm (6 to 16 in.): 3 µS/cm or larger
Note: For a fluid with large flow noise (pure water, pure
alcohol or others), or a fluid wth low conductivity and
low viscosity, the output fluctuates and is impossible
to measure accurately.
Size 500 to 2600 mm (20 to 104 in.) : 50 µS/cm or larger.
6-11

IM 01E20D01-01E
8. EXPLOSION PROTECTED TYPE INSTRUMENT
Conduit
Magnetic Flowmeter
Sealing Fitting
HAZARDOUS LOCATIONS
18" (457 mm) Max.
F0802.EPS
Figure 8.2.1 Conduit Wiring
8.3 CSA
(1) Technical Data
*AXF002C – AXF400C
Applicable Standard:
For CSA C22.2 Series;
C22.2 No 0, C22.2 No 0.4, C22.2 No 0.5,
C22.2 No 25, C22.2 No 30, C22.2 No 94,
C22.2 No 157, C22.2 No.61010-1-12,
C22.2 No.61010-2-030-12
For CSA E79 Series;
CAN/CSA-E79-0, CAN/CSA-E79-1,
CAN/CSA-E79-7, CAN/CSA-E79-11,
CAN/CSA-E79-18
Certificate: 1481213
Process Sealing Certification:
Dual Seal certified by CSA to the requirements of
ANSI/ISA 12.27.01.
No additional sealing required.
Primary seal failure annunciation;
Deterioration of the flowrate output at nonzero
flow point.
Unstable flowrate output at zero flow point.
(Integral Flowmeter)
For CSA C22. 2 Series
Explosion proof for Class I, Division 1, Groups A,
B, C & D.
Dust-ignition proof for Class II/III, Division 1,
Groups E, F & G.
Intrinsically safe (electrodes) for Class I, Division 1,
Groups A, B, C & D.
“SEAL ALL CONDUITS WITHIN 50 cm OF THE
ENCLOSURE”
“WHEN INSTALLED IN DIV. 2, SEALS NOT
REQUIRED”
Electrode Circuit Um: 250 Vac/dc
Maximum power supply voltage: 250 Vac/130 Vdc
Excitation Circuit: 140V max
Enclosure: Type 4X
Temperature Code:
T27-1.EPS
+70°C (+158°F)
+85°C (+185°F)
Temperature
Code
+120°C (+248°F)
Maximum Process
Temperature
–40°C (–40°F)
–40°C (–40°F)
–40°C (–40°F)
–40°C (–40°F)T6
Minimum Process
Temperature
T4
T5
T3 +130°C (+266°F)
Ambient Temp.: –40°C to +60°C (–40°F to +140°F)
For CSA E79 Series
Flameproof for Zone 1, Ex dme [ia] IIC T6...T3
Intrinsically safe (electrodes), Ex ia IIC T6...T3
Electrode Circuit Um: 250 Vac/dc
Maximum power supply voltage: 250 Vac/130 Vdc
Excitation Circuit: 140V max
Enclosure: IP66, IP67
Temperature Code:
T0807.EPS
+70°C (+158°F)
+85°C (+185°F)
Temperature
Code
+120°C (+248°F)
Maximum Process
Temperature
–40°C (–40°F)
–40°C (–40°F)
–40°C (–40°F)
–40°C (–40°F)T6
Minimum Process
Temperature
T4
T5
T3 +130°C (+266°F)
Ambient Temp.: –40°C to +60°C (–40°F to +140°F)
(Remote Flowtube)
For CSA C22.2 Series
Explosion proof for Class I, Division 1, Groups A,
B, C & D.
Dust-ignition proof for Class II/III, Division 1,
Groups E, F & G.
Intrinsically safe (electrodes) for Class I, Division 1,
Groups A, B, C & D.
“SEAL ALL CONDUITS WITHIN 50 cm OF THE
ENCLOSURE”
“WHEN INSTALLED IN DIV. 2, SEALS NOT
REQUIRED”
Electrode Circuit Um: 250 Vac/dc
Excitation Circuit: 170V max
Enclosure: Type 4X
Temperature Code:
T28-1.EPS
Temperature
Code
Maximum Process
Temperature
–40°C (–40°F)
–40°C (–40°F)
–40°C (–40°F)
–40°C (–40°F)T6
Minimum Process
Temperature
T4
T5
T3
+70°C (+158°F)
+85°C (+185°F)
+120°C (+248°F)
+150°C (+302°F)
Ambient Temp.: –40°C to +60°C (–40°F to +140°F)
For CSA E79 Series
Flameproof for Zone 1, Ex dme [ia] IIC T6...T3
Intrinsically safe (electrodes), Ex ia IIC T6...T3
Electrode Circuit Um: 250 Vac/dc
Excitation Circuit: 170V max
Enclosure: IP66, IP67
8-5
Table of contents
Other Admag Measuring Instrument manuals