Valve Instructions
ABC motorized ball valves powered open
by line voltage and motor-driven closed by
a built in capacitor, when power is removed
from the valves.
Plumbing Installation
• Formaximumweatherprotection,thevalve
should be mounted in a horizontal pipe run
with actuator above the ball valve.
• ABCvalvescanhavetheowpass
through in either direction.
• Astrainerupstreamisrecommendedif
installation will have high particulate to
prevent damage.
• Isolationandbypassvalvesarealso
recommended for maintenance.
Wiring
• Valveswiththe100-240VACactuator
will operate off of a line voltage within this
range.
• Linevoltageoutsideoftheratedrangewill
damage actuator.
• Blackwireconnectstoneutralandredto
hot.
• Whenlinevoltageisapplied,valvewill
open and when voltage is removed, it will
close.
Specications
Max Temp............................................. 140oF
Pressure ........................................ 0-225PSI
Valve Body .................. ChromePlatedBrass
Ball & Stem.................. ChromePlatedBrass
Seals .................................................... EPDM
Shipping Weight ....................................3 lbs
Standard Electrical......................... 120VAC
Sizes Available....................1/4,1/2,3/4&1”
Max Torque.............................................2NM
Max Power................................................ 5W
Current............................................ 25±5mA
Cycle Time..................................5-7seconds
Actuator Housing .................................. ABS
Rating .................................................... 1P67
Cycle Life.......................................... 80,000+