Aeotec ZWA039 User manual

AërQ Temperature & Humidity Sensor
(ZWA039)

Quickstart
This is a secure Alarm Sensor. To run this device please insert fresh * CR2477 batteries. Please make
sure the internal battery is fully charged. Triple clicking the central button includes (adds) and excludes
(removes) the device. A click on the central button will wake up the device. The device supports the
Security S framework with unauthenticated and authenticated network keys. The DSK for the S
inclusion can be found inside the sensors packaging. Please follow the instructions on the central
controller when including.
The device also supports SmartStart. Please scan the QR code on the outlet cover of the device and
your controller will add the device automatically when powered up.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in this manual may be
dangerous or may violate the law. The manufacturer, importer, distributor and seller shall not be liable
for any loss or damage resulting from failure to comply with the instructions in this manual or any other
material. Use this equipment only for its intended purpose. Follow the disposal instructions. Do not
dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-WaveTM?
Z-Wave is the international wireless protocol for communication in the Smart Home. This device is
suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message (two-way communication)
and every mains powered node can act as a repeater for other nodes (meshed network) in case the
receiver is not in direct wireless range of the transmitter.
This device and every other certified Z-Wave device can be used together with any other certified Z-
Wave device regardless of brand and origin as long as both are suited for the same frequency range.
If a device supports secure communication it will communicate with other devices secure as long as
this device provides the same or a higher level of security. Otherwise it will automatically turn into a
lower level of security to maintain backward compatibility.
For more information about Z-Wave technology, devices, white papers etc. please refer to www.z-
wave.info.
SmartStart. Available in selected Z-Wave Plus
TM
devices built upon 500 series technology and all
devices built upon 700 series technology, SmartStart lets you setup Z-Wave devices in seconds. Using
SmartStart enabled apps, simply scan the QR code on any compatible app to connect it to your Z-Wave
gateway.

Product Description
This device measures the three air quality parameters temperature, humidity and dew point and reports
them to a central controller. Besides this, the device can directly control groups of other Z-Wave devices
on over- and undershooting a set temperature and/or humidity parameter. This can be used to establish
control loops for temperature and humidity. The device wakes up every 15 minutes to measure the
values and it will send unsolicited reports when values change. Additionally, the device will report all
values on request.
The AërQ Sensor is actively monitoring the danger of mould in a room based on the temperature and
humidity and will issue alarm warnings when critical air conditions met. Wireless Alarm and red and a
green blinking LED will indicate a mould condition. This local LED warning function is also available
when the device is not included in any Z-Wave network and works stand alone.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory default state. Please make
sure to reset the device into factory default. You can do this by performing an Exclusion operation as
described below in the manual. Every Z-Wave controller is able to perform this operation however it is
recommended to use the primary controller of the previous network to make sure the very device is
excluded properly from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave controller. This procedure
should only be used when the primary controller is inoperable.
Keep the button pressed for 10 seconds. Then the green LED will start blinking. Release the button,
when the LED stops blinking. Your device is reset to factory default now.
Safety Warning for Batteries
The product contains batteries. Please remove the batteries when the device is not used. Do not mix
batteries of different charging level or different brands.
Installation
Just place the device on any flat surface. Please keep in mind that the temperature may be different in
different locations inside the room. If placed too close to the heating both temperature, humidity and
dew point values may be wrong. The device is IP 0 rated. This means that is must not be exposed to
direct water (rain). It is safe to use the device in a humid environment such as a bathroom or dedicated
washing facility.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The device needs to be added to
an existing wireless network to communicate with the devices of this network. This process is
called Inclusion.
Devices can also be removed from a network. This process is called Exclusion. Both processes are
initiated by the primary controller of the Z-Wave network. This controller is turned into exclusion

respective inclusion mode. Inclusion and Exclusion is then performed doing a special manual action
right on the device.
Inclusion
1. Insert the battery.
. Press the button quickly three times in a row.
Exclusion
1. Press the button quickly three times in a row.
Product Usage
Once the device is powered up it will start monitoring the air parameters and warn of mould using the
local red and green LED. Pushing the button will force an immediate measurement and the LEDs will
indicate the danger of mould.
green: no danger of mould in the room
red: danger of mould, open the windows to lower the humidity
The device contains two sensors with the following accuracy measures:
Relative Humidity: precision ± 3% RH (max), range 0 to 80% RH
Temperature: precision ±0.8 °C (max), range -10 to 65 °C
Dew Point: precision ±0.8 °C (max), range -10 to 65 °C (calculated from other sensor values)
The device sends the following notifications to the central controller:
Weather Alarm - Moisture Alarm (0x10 - 0x0 )
Power management - Replace battery now (0x08 - 0x0b)
Heat Alarm - Overheat Unknown Location (0x04 - 0x0 )
Heat Alarm - Underheat Unknown Location (0x04 - 0x06)
For getting the status of the device on the network you need insert a battery to device. And you see
result: - "The GREEN LED will blink one time in case of success or RED LED will blink five times in case of
failure".
Quick trouble shooting
Here are a few hints for network installation if things don’t work as expected.
1. Make sure a device is in factory reset state before including. In doubt exclude before include.
. If inclusion still fails, check if both devices use the same frequency.
3. Remove all dead devices from associations. Otherwise you will see severe delays.
4. Never use sleeping battery devices without a central controller.
5. Don
‘
t poll FLIRS devices.
6. Make sure to have enough mains powered device to benefit from the meshing

Firmware-Update over the Air
This device is capable of receiving a new firmware 'over the air'. The update function needs to be
supported by the central controller. Once the controller starts the update process, perform the following
action to confirm the firmware update: Wake Up the device by pressing the central button once.
Association - one device controls another device
Z-Wave devices control other Z-Wave devices. The relationship between one device controlling another
device is called association. In order to control a different device, the controlling device needs to
maintain a list of devices that will receive controlling commands. These lists are called association
groups and they are always related to certain events (e.g. button pressed, sensor triggers, ...). In case the
event happen all devices stored in the respective association group will receive the same wireless
command wireless command, typically a 'Basic Set' Command.
Association Groups:
Group Number
Maximum
Nodes Description
5
Lifeline
2
5
High
Temperature
Notification
3
5
Low
Temperature
Notification
4
5
High
Humidity
Notification
5
5 Low Humidity Notification
6
5 Air Temperature (A multilevel sensor report is sent to the
nodes in this group)
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can
adapt the function better to user needs or unlock further enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range
1 8 ... 55 the value sent in the application shall be the desired value minus 56. For example: To set a
parameter to 00
it may be needed to set a value of 00 minus 56 = minus 56. In case of a -byte value
the same logic applies: Values greater than 3 768 may needed to be given as negative values too.
Parameter : Minimum Temperature change to report
This value defines the minimum change of temperature to cause an unsolicited report of temperature to
the central controller using Lifeline. If the value is set to 0, there will be no reports sent to the controller,
when the temperature changes. However, periodic reports, managed by configuration parameter 4, may
still be active.
Size: 1 Byte, Default Value: 0 ( degree), Unit=0.1 degree (US is Fahrenheit degree, EU is Celcius
degree)
Setting
Description

0
disabled
-
0
0
0.1
-
10 degree
Parameter 2: Minimum humidity change to report
This value defines the minimum change of humidity to cause an unsolicited report of humidity to the
central controller using Lifeline. If the value is set to 0, there will be no reports sent to the controller, when
the humidity changes. However, periodic reports, managed by configuration parameter 4, may still be
active.
Size: 1 Byte, Default Value: 5
Setting
Description
0
disabled
-
20
1
-
0
%
Parameter 3: Check interval for minimum change on parameter and 2.
This value
determines how often aerQ Sensor checks for minimum change in temperature or humidity
on Parameter 1 and or when the Sensor wakes up by button pressing. Value is set in minutes.
Size: 1 Byte, Default Value: 15
Setting
Description
-
255
1 - 255 minutes
Parameter 4: Periodic Reports
This parameter defines the time interval to send an unsolicited report. If the value is set to 0, there will be
no periodic reports sent to the controller. However, reports on temperature/humidity changes, managed
by configuration parameters 1 and may still be active.
Size: Byte, Default Value: 43 00
Setting
Description
0
disabled
30
-
65535
Seconds
Parameter 5: Temperature Upper Watermark value
This parameter defines a temperature. If the measured temperature surpasses this watermark, a BASIC
command is sent into Association Group . The Sensor will check the watermark value for an interval set
by Parameter 16 or when the Sensor wakes up by button pressing.
Size: Byte, Default Value: 0, Unit=0.1 degree
Setting
Description

0
disabled
-
000
0.1
-
100
degree
Parameter 6: Temperature Lower Watermark value
This parameter defines a temperature. If the measured temperature drops below this watermark, a
BASIC command is sent into Association Group 3. The Sensor will check the watermark value for an
interval set by Parameter 16 or when the Sensor wakes up by button pressing.
Size: Byte, Default Value: 0, Unit=0.1 degree
Setting
Description
0
disabled
-
200
-
000
-
0
-
100
degree
Parameter 7: Humidity Upper Watermark value
This parameter defines a relative humidity. If the measured relative humidity surpasses this watermark, a
BASIC command is sent into Association Group 4. The Sensor will check the watermark value for an
interval set by Parameter 16 or when the Sensor wakes up by button pressing.
Size: 1 Byte, Default Value: 0
Setting
Description
0
disabled
-
90
1
-
90
%
Parameter 8: Humidity Lower Watermark value
This parameter defines a relative humidity. If the measured temperature drops below this relative
humidity a BASIC command is sent into Association Group 5. The Sensor will check the watermark value
for an interval set by Parameter 16 or when the Sensor wakes up by button pressing.
Size: 1 Byte, Default Value: 0
Setting
Description
0
disabled
-
90
1
-
90
%
Parameter 9: Low Temperature Trigger BASIC Set Command Value
This defines what BASIC command shall be sent out into association group 3.
Size: 1 Byte, Default Value: 55

Setting
Description
0
-
255
Value
Parameter 0: High Temperature Trigger BASIC Set Command Value
This defines what BASIC command shall be sent out into association group
Size: 1 Byte, Default Value: 0
Setting
Description
0
-
255
Value
Parameter : Low Humidity Trigger BASIC Set Command Value
This defines what BASIC command shall be sent out into association group 5
Size: 1 Byte, Default Value: 55
Setting
Description
0
-
255
Value
Parameter 2: High Humidity Trigger BASIC Set Command Value
This defines what BASIC command shall be sent out into association group 4
Size: 1 Byte, Default Value: 0
Setting
Description
0
-
255
Value
Parameter 3: Offset value for Mould danger notification
This value allows to increase the humidity threshold for mould danger notification by max 10%
Size: 1 Byte, Default Value: 0
Setting
Description
0
-
0
0
-
10
%
Parameter 4: Offset value for Temperature
Can add or minus this setting value to calibrate temperature when checked.
Scale is defined by Param 64. e.g. Value 15 means 1.5C or 1.5F.
Size: Byte, Default Value: 0
Setting
Description

-200 ~ 200
-
0
-
0
degrees
Parameter 5: Offset value for Humidity
Can add or minus this setting value to calibrate humidity when checked.
Unit: %.
Size: 1 Byte, Default Value: 0
Setting
Description
-50 ~ 50
-
50
-
50
%
Parameter 6: Check interval for Upper/ Lower Watermark value on Parameter 5 ,6,7 and 8.
This value
determines how often aerQ Sensor checks for upper/lower watermark value in temperature
or humidity on Parameter 5 ,6,7 and 8. Value is set in minutes.
Size: 1 Byte, Default Value: 15
Setting
Description
-
255
1 - 255 minutes
Parameter 64: Switch the unit of Temperature report.
This value allows to switch between Celcius and Fahrenheit unit of temperature report.
Size: 1 Byte, Default Value: 1 (EU version) or (US version).
Setting
Description
Celcius
2
Fahrenheit
Parameter 65:
Sensor
report
after
inclusion.
This value determines which sensor report will be sent after the inclusion is complete.
Size: 1 Byte, Default Value: 15.
Setting
(
bit
field
)
Description
Bit 0
Battery report.
(0 = d
isable
, 1 = e
nable
)
Bit
T
emperature sensor report
.
(0 = d
isable
, 1 = e
nable
)
B
it 2
H
umidity sensor report. (0 = d
isable
, 1 = e
nable
)
B
it 3
D
ew point
sensor report. (0 = d
isable
, 1 = e
nable
)

Parameter 255: Reset Parameter
This parameter helps reset configuration parameters and the device to factory defaults
Size: 4 Byte, Default Value: 0
Setting
Description
–
4294967294
Reset all Parameter settings to their default settings.
4294967295
Completely factory reset sensor and send device reset locally notification.
Technical Data
Dimensions
34x34x16 mm
Hardware Platform
ZGM130S
IP Class
IP 0
Battery Type
1 * CR 477
Device Type
Notification Sensor
Generic Device Class
GENERIC TYPE SENSOR NOTIFICATION (0x07)
Specific Device Class
SPECIFIC TYPE NOTIFICATION SENSOR (0x01)
Network Operation
Reporting Sleeping Slave
Firmware Version
.00
Z
-
Wave Version
07.15.1.0
Z
-
Wave
Product Id
0371, 000 (EU)/010 (US)/0 0 (AU), 0009
Frequency
EU - 868,4 Mhz, US – 908,4 Mhz, AU – 9 1,4 Mhz
Maximum transmission
power
5 mW

Supported Command Classes
Binary Sensor Command Class, Version (highest granted security level)
Configuration Command Class, Version 4 (highest granted security level)
Multilevel Sensor Command Class, Version 11 (highest granted security level)
Multi Channel Association Command Class, Version 3 (highest granted security level)
Association Group Information Command Class, Version 3 (highest granted security level)
Device Reset Locally Command Class, Version 1 (highest granted security level)
Z-Wave Plus Info Command Class, Version (non-Secure)
Notification Command Class, Version 8 (highest granted security level)
Manufacturer Specific Command Class, Version (highest granted security level)
Powerlevel Command Class, Version 1 (highest granted security level)
Firmware Update Meta Data Command Class, Version 5 (highest granted security level)
Battery Command Class, Version 1 (highest granted security level)
Wake Up Command Class, Version (highest granted security level)
Indicator Command Class, Version 3 (highest granted security level)
Association Command Class, Version (highest granted security level)
Version Command Class, Version 3 (highest granted security level)
Security Command Class, Version 1 (highest granted security level)
Supervision Command Class, Version 1 (non-Secure)
Transport Service Command Class, Version (non-Secure)
Explanation of Z-Wave specific terms
Controller — is a Z-Wave device with capabilities to manage the network. Controllers are typically
Gateways, Remote Controls or battery-operated wall controllers.
Slave — is a Z-Wave device without capabilities to manage the network. Slaves can be sensors,
actuators and even remote controls.
Primary Controller — is the central organizer of the network. It must be a controller. There can be
only one primary controller in a Z-Wave network.
Inclusion — is the process of adding new Z-Wave devices into a network.
Exclusion — is the process of removing Z-Wave devices from the network.
Association — is a control relationship between a controlling device and a controlled device.
Wakeup Notification — is a special wireless message issued by a Z-Wave device to announces
that is able to communicate.
Node Information Frame — is a special wireless message issued by a Z-Wave device to
announce its capabilities and functions.
Table of contents
Other Aeotec Security Sensor manuals
Popular Security Sensor manuals by other brands

B.E.G.
B.E.G. LUXOMAT PD2N-KNX-ST-UP Mounting instructions

Rotech
Rotech FJC-DL001 user manual

DigiSpec
DigiSpec VMD-1001 Operation manual

Hytronik
Hytronik HIR23 Installation and instruction manual

Fire Innovations
Fire Innovations COMANCHE NFPA ESCAPE BELT Instructions for use

Rielta
Rielta Ladoga MK-RK installation guide