Aidcall Astra 6000 User manual

DocNo.FM5610issueBPage1
Touchsafe®Pro
WirelessNursecallSystem
_________________________________________________________________________________________________
Astra6000PagerTransmitter
InstallationGuide
Aidcalloperatesapolicyofcontinualproductimprovementand
reservestherighttomodifythespecificationofitsproducts.
Ifanyvariationtothedetailsinthisdocumentaresuspectedplease
contactAidcall’sTechnicalSupport.
Aidcall,abusinessunitofLegrandElectricLtd
CowleyRoad,BlythRiversideBusinessPark,Blyth,Northumberland,NE245TF.
T:+44(0)1670357431www.aidcall.co.uk
________________________________________________________________

DocNo.FM5610issueBPage2
CONTENTS
SectionTopicPage
1ProductOverview2
2ImportantSafetyInstructions3
3RegulatoryInformation 4
4Maintenance&Care4
5TransmitterKitFeatures5
6Installation6
7PanelSetup 9
8ReplacingthePSUBattery11
9Specification12
CONTENTS
1. PRODUCTOVERVIEW
TheAstra6000PagerTransmitterkit(AidcallP/No.E40104)includesthetransmitterandantennacomplete
witha12VDCbatterybackedpowersupplyunit.Pagersareboughtseparately,there’snolimithowmany
canbeusedpersystem.
Note:theJ25wasreplacedbytheScopemodelinJuly2016–botharecompatiblewithAstraPagers.
TheTransmitterrequiresconnectiontothePSUandthePagerPortonaTouchsafeProNursecallPanel.
StaffwillthenbealertedtoacallnomatterwheretheyareviatheirportablePagers.
ThesystemcanbesetupsoallcallsarereportedtoallPagersatalltimes,orday/nightgroupscanbesetso
differentPagerscanbealerteddependingonthetimeofday.Thetypesofcallthatarereportedtothe
Pagerscanbesetalongwiththebeeppatterntoidentifydifferentcalltypes.FurthermorePagerscanbe
configuredintozonessocallsareonlynotifiedtothestaffresponsibleforspecificareas.
RefertotheJ25PagerUserGuide(AidcallDocNo.FM5615)orScopePagerUserGuide(Aidcall
DocNo.FM5620)fordetailsonsetupandhowthePagersoperate.
J25Pager
(AidcallPartNo.W07280)
ScopePager
(AidcallPartNo.W07600)

DocNo.FM5610issueBPage3
2. IMPORTANTSAFETYINSTRUCTIONS
Readandunderstandtheseinstructionsbeforeuse.Keeptheseinstructionsforfuturereference.
Takecarewhenworkingonstepladdersduringinstallationorservice.
IsolatethemainssupplybeforeremovingthePSUcover.
Donotdisassemblethetransmitter/PSUorattempttorepairityourself.
Nouserserviceablepartsinside.Referallservicingtoqualifiedservicepersonnel.
ThePSUshouldonlybeconnectedtoa220‐240VAC50/60Hzmainssupply.Ifyouareunsureofthetype
ofpowersupplyconsultyourlocalpowercompany.
DangerofexplosionifthePSUrechargeablebatteryisincorrectlyreplaced.Useonlymanufacturer
approvedbatteryasidentifiedinsection8ofthismanual.
Onlyusemanufacturerapprovedcableduringinstallation.Seesection6ofthismanualfordetailsof
cabletype,recommendedcolourcodeandcablelengthrestrictions.
Thisproductshouldbelocatedatleast2metresawayfromanyotherelectronicequipment.
Failuretoprovidethisseparationmayresultinreducedradiorange.
Donotlocatethisproductabovearadiatororotherheatsource.
Donotexposetodirectsunlight.
Donotsubmergeinwateranddonotuseindamporhumidconditions.
Donotexposethisproducttodrippingorsplashingwater.
Liquidscancauseafailureand/orafirehazard.
Cleanwithadampclothandanon‐abrasivecleaningproduct.Polishwithadryduster.DONOTusea
wetcloth.
Avoidusingharsh,abrasiveorcorrosivecleaningagentsordetergents(e.g.scouringpowders,bleaches,
polishes,etc.)whencleaningthisproduct.
Attheendofitslifethisproductshouldbedisposedofandrecycledinaccordancewiththe
environmentalregulations.SeetheRegulatoryInformationinsection3below.

DocNo.FM5610issueBPage4
3. REGULATORYINFORMATION
ThissymbolontheproductindicatesitcomplieswithallrelevantEUDirectivesasrequiredbylaw.
DTIApproval;MPT1305
LowVoltage;2006/95/EC
ElectroMagneticCompatibility;EMC2004/96/EC
RestrictionofHazardousSubstances;RoHS2011/65/EU
ThissymbolontheproductindicatesitisclassedasElectricalorElectronicEquipmentandshouldnotbe
disposedofwithothercommercialwasteattheendofitsworkinglife.
TheWasteofElectricalandElectronicEquipment(WEEE)Directive(2012/19/EU)hasbeenputinplace
torecycleproductsusingthebestavailablerecoveryandrecyclingtechniquestominimiseimpactonthe
environment,treathazardoussubstancesandavoidincreasinglandfill.
Forproductdisposalpleasecontactyoursupplierandcheckthetermsandconditionsofthepurchase
contractandensurethisproductisnotmixedwithothercommercialwastefordisposal.
Thissymbolonbatteriesindicatesseparatecollection.Batteriescontainchemicalsthatcanbe
hazardoustohealthandtheenvironmentandshouldnotbedisposedofinthewastebin.
TheEUDirective(2006/6/EC)hasbeenputinplacetoensurethesafedisposalandrecyclingof
batteries.
Returnusedbatteriestoyoursupplierordrop‐offatyourlocalmunicipalwasterecyclingdepot.
NTENTS
4. MAINTENANCE&CARE
ForpeaceofmindandtoensureyoursystemismaintainedtothehigheststandardAidcallrecommendan
annualmaintenancecontract.Thiswillprovidevitalassistanceintimesofneedfromanationwideteamof
trainedServiceEngineerswhospecialiseinwirelessNursecallsystems.
Apreventativemaintenancevisit(PMV)isalsoavailablefromAidcall,thiscoversthereplacementofall
batteries,afullsystemtest,softwareupdates(whereapplicable)andaServiceCertificate.
FormoreinformationonMaintenanceContractPackagesandPMV’spleasecontactourcustomerservices
teamon01670357431orvisitourwebsite;www.aidcall.co.uk/healthcare/support/maintenance
MONTHLYMAINTENANCE
AstraPagerTransmittersdonotrequireanyregularmaintenance,ifaunitshowssignsofexternaldamage
itshouldbereplacedimmediatelybyaServiceEngineer.Productsneedingrepaircanbereturnedviathe
website;www.aidcall.co.uk/healthcare/support/repair
ANNUALMAINTENANCE
TherechargeablebatteryinthePSUshouldbetestedeveryyearbyaServiceEngineerandreplacedevery5
years.Seesection8fordetailsofbatterytype.

DocNo.FM5610issueBPage5
5. TRANSMITTERKITFEATURES
TheAstra6000Transmitterkit(AidcallPartNo.E40104)includesthetransmitter&antenna,a12V/1A
boxedpowersupply,a2metremainsleadanda12V/1.2Ahrechargeablebattery.
TRANSMITTERLED’s
TheREDPOWERLEDshouldbepermanentlyilluminatedwhenthe12VPSUisconnected.
TheGREENTRANSMITTINGLEDwillonlyilluminatewhenasignalistransmittedtothePagers.
POWERSUPPLYLED’s
TheGREENPOWERLEDshouldbepermanentlyilluminatedwhentheMainssupplyishealthy.
TheREDFAULTLEDwillilluminateifthe12Voutputorbatteryfusehasblown.
HelicalAntenna
(165mmhigh)
Red PowerLED
WallMountedEnclosure
210x144x39mm(HxWxD)Green TransmittingLED
BNCConnector
RemovableLid(4ScrewFixings)
CableEntry
WallMountedEnclosure
200x230x80mm(HxWxD)
12V1.2AhRechargeableBattery
2mMainsLead&13AUKPlug
GreenPowerLED
Red FaultLED
Transmitter&Antenna
12V/1APowerSupply
HingedLid(1ScrewFixing)

DocNo.FM5610issueBPage6
6. INSTALLATION
Thetransmittermustbesitedinadrysecurearea;itisNOTsuitableforoutdoorlocations.
Thetransmittermustbewithin20metrescablerunofaTouchsafeProDisplayPanel.
Note:Iftherearemultiplepanelsconnecttotheonewhichismostcentrallylocatedonthesite.
Thetransmittershouldbepositionedashighaspossiblewiththeantennaaminimumof300mmfromthe
ceilingandatleast2metresawayfromanyotherelectronicequipment.
IMPORTANT:AVOIDLOCATINGTHETRANSMITTER…
WITHIN2METRESOF
OTHERELECTRONIC
EQUIPMENT
DIRECTLYABOVEA
HEATER
INDIRECTSUNLIGHT NEARTOSPLASHING
WATER
RADIORANGE
Constructionmaterialssuchasfoilbackedplasterboard,reinforcedconcreteorstonewallswillreduce
range.Environmentalconditionssuchashighlevelsoftransmissionatnearbyfrequenciesoremissions
fromotherelectricalequipmentmayfurtherreducerange.Clearline‐of‐sightwillgiveamaximumradio
rangeof1kilometreradiusfromthetransmitter.

DocNo.FM5610issueBPage7
6.INSTALLATION
Thetransmitterrequiresapoweranddataconnection;poweristakenfromthe12V/1AbatterybackedPSU
anddatacomesfromthePagerPortonanyTouchsafeProDisplayPanel.
POWERSUPPLYUNIT
Undothesinglelidfixingscrewandopenthelid.
Note:ifthelidisremovedensuretheSafetyEarthisre‐connected.
PositionthePSUwithin2metresofanun‐switched13Amainssocket.
Fixthepowersupplyunittothewallusingthe3holes“A”asshownbelow.
Connectthemainsleadprovidedtothepowersupplyunitmainsterminals
usingthecolourcodeinthetablealongside.
Note:theplugisfittedwitha240VAC5ABS1362fuse.
ThePSUshouldonlybeopenedduringinstallationandservice–thelidmustbescrewed
shutatallothertimestopreventtheriskofelectricshock.NeverleavealivePSU
unattendedwiththelidopen.
TRANSMITTER
Undothe4screwsandremovethelidfromthetransmitter.
Seethepreviouspageforinformationonsitingthetransmitter.
Fixthetransmittertothewallusingthe4holes“A”asshownbelow.
MainsConnection
ColourTerminal
BrownL
BlueN
Green/YellowE
IMPORTANT
MountTransmitter
withAntennaVertical
UP
120mm
122mm
Cable
Entry
AA
AA
160mm
65mm
145mm
A
AA
PSU
(NOTTOSCALE)
12V/1A Boxed PSU
ASTRA
TRANSMITTER
E
N
L
O/P
+‐

DocNo.FM5610issueBPage8
6.INSTALLATION
SITEWIRING
CONNECTIONDETAILS
CABLESPEC&COLOURCODE
ThetransmittershouldbewiredusingLSF(LowSmokeandFume)screenedTCCA8corealarmcable.
Usethecolourcodesshownbelow…
CableColourPSUAstraPanel
PowerRedO/P++N/C
BlackO/P‐ ‐ N/C
DataYellowN/CRXDTX
Black N/C ‐0V
ThiscableisavailablefromAidcallbythemetre;PartNo.YW1730.
NTS
E40104
AstraTransmitterKit
IMPORTANT
LooptheCableonce
throughtheFerriteSleeve
p
rovidedwiththePanel
DisplayPanel
PagerConnections
Astra6000Pager
Transmitter
PSU
Output+/‐
Max20mcablelengthbetweenPanelandPager

DocNo.FM5610issueBPage9
7. PANELSETUP
GototheTouchsafeProMasterPanel(ID1),LogonasanEngineerandselectthePanelDetailsoption…
StillonTouchsafeProMasterPanel(ID1),selecttheCommonPagersoption…
Alternatively,PagerscanbesettooperatebyZone‐seenextpage…
S
NotesonPagerID’s
J25Pagerscanbeprogrammedwithupto6differentID’s
ScopePagerscanbeprogrammedwithupto8differentID’s
TheseID’sare7digitslongbutthefirst4digitsmustbe0012fortheAstraPager
Onlyenterthelast3digitsoftheID’sintheboxesabove
RefertotheJ25PagerUserGuide(AidcallDocNo.FM5615)formoreinformation
RefertotheScopePagerUserGuide(AidcallDocNo.FM5620)formoreinformation
Selectwhich PanelIDtheAstraPager
Transmitterisbeingconnectedtofrom
thePagingPanelpull‐downbox.
Note:thisonlyneedstobesetonthe
MasterPanel(ID1).
PresstheSavebuttonthenClosetoexit.
Enterthe3digitPagerID’sintheboxes
alongsideeachcalltypegroup(Cardiac,
Emergency,etc.)foronesyouwanttobe
notifiedduringtheDay,Night1andNight2
modes.
Thekeypadwillbedisplayedwhenyouclick
onaboxtoenterapagerID‐youmayneed
topressthe123#?buttontoselectthe
numerickeypad.
PresstheSavebuttonthenClosetoexit.

DocNo.FM5610issueBPage10
7.PANELSETUP
StillonTouchsafeProMasterPanel(ID1),selecttheZonedPagersoption…
GototheTouchsafeProPanelwiththeAstraPagerTransmitterconnected,LogonasanEngineerandselect
thePagingSetupoption…
BEEPCODETABLE
AstraBeepCodeJ25PagerBeepPattern Scope PagerBeepPattern
0,1,3,4,5,6,7,86doublebeeps8doublebeeps
28triplebeeps8triplebeeps
9high/lowbeeps+vibrate8fourbeeps
EntertheBeepCodetochoosethebeeppatternthePagerwillsoundforeachcalltype.
SettheProtocoloptiontoAstra/Bluebell.
SelecttheBeepCodesyouwantthePager
tosoundfromthepull‐downboxes
alongsideeachcalltype.
Note:only3differentbeeppatternsare
availablewiththeAstraoption‐seethe
BeepCodetablebelow.
SettheRe‐PagingDelayfromthe
pull‐downbox;ifanalarmcallisnot
acceptedwhenthisperiodexpiresthe
Pagerswillbenotifiedagain.
PresstheSavebuttonthenClosetoexit.
SelectaZonefromthepull‐downboxthen
enterthe3digitPagerID’syouwanttobe
notifiedduringtheDay,Night1andNight2
modesintheboxesalongsideeachcalltype
group(Cardiac,Emergency,etc.).
See“NotesonPagerID’s”onpage9.
Thekeypadwillbedisplayedwhenyouclick
onaboxtoenterapagerID‐youmayneed
topressthe123#?buttontoselectthe
numerickeypad.
PresstheSavebuttonthenClosetoexit.

DocNo.FM5610issueBPage11
8. REPLACINGTHEPSUBATTERY
Theboxed12VDC1ApowersupplyunitprovidedwiththeAstraPagerTransmitterincludesa12V1.2Ah
rechargeablebattery.Thisbatterywillmaintainnormaloperationforseveralhoursintheeventofamains
powerfailure.
TherechargeablebatteryshouldberemovedandtestedbyaServiceEngineeronanannualbasisand
replacedevery5years.
Withthebatterydisconnected;checkthechargevoltageacrossthebatteryleadsisbetween13.6VDCand
14.2VDC(13.8Vnominal).
Ifthebatteryshowsanysignsofdamage,swellingorleakageduringanannualinspectionitshouldbe
replacedimmediately.
OnlyreplacewiththeManufacturersApprovedbatterytype:
YuasaNP1.2‐12:12V1.2AhSealedLeadAcidRechargeableBattery
ReplacementbatteriesareavailablefromAidcall;orderPartNo.F00619
IMPORTANT:alwaysmarkthebatterywiththedateitwasreplacedforreferenceonfutureServicevisits.
Seesection3ofthismanualforRegulationsregardingthesafedisposalofusedbatteries.
12VDC1A
PowerSupply12V1.2AhLeadAcid
RechargeableBattery

DocNo.FM5610issueBPage12
9. SPECIFICATION
Transmitter
Manufacturer/ModelMBElectronics‐ Astra6000
DTIApprovalMPT1305
TransmissionFrequency459.2750MHz
TransmissionRangeUpto1km
TransmissionProtocolPOGSAG512bps
AntennaHelical(165mmhigh)
AntennaConnectorBNC
SerialInterfaceRS232 (AckermanProtocol)
LEDIndicatorsRed=PowerandGreen=Transmitting
OperatingVoltage12VDC
OperationalCurrent200mA
StandbyCurrent30mA
EnclosureMaterialAluminium(Finish:PaintedLightGrey)
IngressProtectionRatingIP40
Dimensions210mmx144mmx39mm(HxWxD)
Weight625grams
OperatingTemperatureRange ‐5oCto40oC
PowerSupplyUnit
Manufacturer/ModelElmdeneG13801N‐A
ComplianceLowVoltage:2006/95/EC,EMC2004/96/EC,WEEE2002/96/EC
TypeSwitchModePSUwithElectronicOverloadProtection
InputVoltage90Vto264VAC50/60Hz
OutputVoltage/Current13.6Vto14.2VDC@1A(Nominal13.8V)
OutputRipple150mVpeaktopeak
LEDIndicatorsGreen=MainsSupplyHealthyandRed=Fault(FuseBlown)
MainsFuseProtectionT2.0A20mmHRC
LoadFuseProtectionF1.0A20mmGlass
BatteryFuseProtectionF1.0A20mmGlass
EnclosureMaterialMildSteelwithHingedLid(Finish:StoveEnamelledWhite)
IngressProtectionRatingIP40
Dimensions200mmx230mmx80mm(HxWxD)
Weight1.85kilograms(excludingbattery)
RelativeHumidity95%RHnon‐condensing
OperatingTemperatureRange ‐10oCto40oC
StandbyBattery
Manufacturer/ModelYuasaNP1.2‐12
Type12V1.2AhRechargeableLeadAcid
Dimensions97mmx48mmx54.5mm(LxWxH)
Weight580grams
OperatingTemperatureRange ‐15oCto50oC
MainsLead
ApprovalsBS1363/A,VDEandKEMA
Cable 2metreslong3core0.752mm(Colour:Black)
PlugBS1363mouldednon‐rewireable13AUKPlug
FuseType/RatingBS13621”240VAC5A
This manual suits for next models
1
Table of contents
Other Aidcall Transmitter manuals
Popular Transmitter manuals by other brands

COBHAM
COBHAM C406-2 SERIES Abbreviated component maintenance manual

i3-TECHNOLOGIES
i3-TECHNOLOGIES i3SYNC quick start guide

Listen
Listen LP-3CV-072 installation guide

CVW
CVW BeamLink-Lite quick start guide

Pfeiffer Vacuum
Pfeiffer Vacuum CPT 100 operating instructions

IDTOLIGHT
IDTOLIGHT MILWAUKEE installation instructions

Siemens
Siemens SITRANS TH100Slim Compact operating instructions

Primex
Primex XR TIME SYNCHRONIZATION Installation & user guide

Monacor
Monacor IMG Stage Line TXS-820LT quick guide

Emerson
Emerson Rosemount 644 FOUNDATION Reference manual

Emerson
Emerson Rosemount 5081-T instruction manual

Invonics
Invonics EN1501-EXT installation instructions