Air+Health Haven Instruction Manual

PLEASE READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY
Scan QR: install guide
INSTALLATION & USER MANUAL
Whole Home Protection™

1
CONTENTS
4 Meet Your New Haven
18 Maintenance
Thank you
We BELIEVE
We are DEDICATED
We STRIVE
airhealth.com
QUESTIONS?
PHONE
FAX
WEB

2
WARNING
•
•
•
•
•
WARNING
•
•
WARNING
•
WARNING
•
•
NOTE: If you touch the glass of the lamp, you should wipe the glass clean
with isopropyl alcohol and a lint free wipe. If the lamp is not cleaned, the lm
of hand oils causes a reducon in the light intensity.
WARNING
Before installing or servicing a humidier, air lter, heat system, this unit,
etc., always turn all power OFF and have unit unplugged. Electrical shock can
cause personal injury or death. Never expose eyes or skin to direct UVC light
from any source.
WARNING
To prevent water damage or electric shock, do not mount unit under
a humidier.
WARNING
This product is designed for indoor installaon only (i.e. acs, crawl spaces,
basements, etc.). For use on gas red, oil red, electric and split system heat
pump forced air systems*. This product is NOT designed to be mounted
outside on gas red or heat pump packaged units**.
*
**
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.

4
Meet Your New Haven
Items included:
1
2 Ballast
3
4
5
Keep for future use when
6 Hole Saw
1
7
8
9
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.
Tools Required:
Ruler
Power Drill
Screwdriver
2
3
4
5

6
Basement Installaon
Air Handlers
AC Condenser Install Locaon
A Coil
Closet Installaon
• DO NOT mount near a return air
register grill.
• DO NOT mount unit on plasc flexible duct.
• Mount unit on metal housing if any metal duct available.
• If a metal housing is not available, you may need to
fabricate a mounng box.
Ac Installaon Heat Pump with Separate
Air Handler
Package System or Heat Pump
(with no separate air handler)
Heat Pump with Separate Air Handler
(in the ac or crawl space)
A/C
CONDENSER
A/C
CONDENSER
A/C
CONDENSER
A/C
CONDENSER
Why is this step important?
Figure A
System Type
H
2000 1 120 60
4000 2 120 60
Notes:
FIGURE A

8
CAUTION
Invesgate and determine the locaon of the A coil prior to drilling holes
in duct for mounng unit.
(Reference Figure B
OR in the return
(Reference Figure B
NOTE: SEAL the joints and seams of the plenum near the mounng
locaon to reduce any direct viewing of UV light.
STOP HERE BEFORE PROCEEDING
If the plenum is made of duct board, refer to the duct board mounng
instrucons on pages 10-11.
If the plenum is made of metal, refer to the metal plenum mounng
instrucons on pages 12-13.
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
Furnace or
Air Handler
Furnace or
Air Handler
Furance or
Air Handler
P/N 46452800 07/03
A Coil
A Coil
HORIZONTAL FLOW
Supply
Air Plenum
Floor
Return
Air Plenum
Air+Health™
Best Locaon
Air+HealthTM
Oponal Locaon
Return
Air Plenum
Supply
Air Plenum
AIR FLOW
Furnace or
Air Handler
A Coil
Supply
Air Plenum
Return
Air Plenum
AIR FLOW
A Coil
DO NOT mount near a
return air register grill
These units are mounted in acs or crawl spaces.
Only
Locaon
Supply
Air Plenum
Return Register Grill Wall
AIR FLOW
AIR FLOW
DOWN FLOW UP FLOW
Furnace or
Air Handler
Furnace or
Air Handler
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.
FIGURE B

10 11
4. Bend tabs into duct.
(See Figure 4
Bend both tabs at the second bend point up or down to pinch
Figure 5
Figure 6
If your chosen locaon to mount the unit is made of so duct board,
follow these steps:
in Figure 1
2. Bend tabs outward.
in Figure 2
3. Cut a rectangle out of the duct board.
See Figure 3
FIGURE 1 FIGURE 2
FIGURE 3
FIGURE 4
FIGURE 6
FIGURE 5
*INSIDE DUCT
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.

12
If your chosen locaon to mount the unit is made of metal,
follow these steps:
Figure 7B
SAFETY PROCEDURE
Please wear supplied safety glasses during installaon. They will help
protect from debris while drilling.
Figure 8
Figure 7A
3. Drill a large hole for the UVC Lamp.
shown in Figure 7A
Figures 9 & 10
4. Drill the view port hole.
¼½
Figure 11
Template Scker
Mount Template
Horizontal or Vercal
Duct
Template Scker
Mount Template
Horizontal or Vercal
Duct
Template Scker
Mount Template
Horizontal or Vercal
Duct
Template Scker
Mount Template
Horizontal or Vercal
Duct
Template Scker
Mount Template
Horizontal or Vercal
Duct
Template Scker
Mount Template
Horizontal or Vercal
Duct
FIGURE 7A
FIGURE 9
FIGURE 7B
FIGURE 8
FIGURE 10
FIGURE 11
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.

14
Connue here aer compleng the previous mounng steps.
SAFETY PROCEDURE
Please wear supplied safety glasses during installaon. They will help
protect from debris while drilling.
WARNING
To prevent water damage or electric shock, do NOT mount unit under
a humidier.
Figure 7A
(Figure 12 & 18
NOTE: DO NOT remove template from duct.
2. Install UVC lamp into ballast.
Figure 13
NOTE: Do not handle the lamp with bare hands. Oils on the hands may
shorten lamp intensity.
Figure 14
Figure 15
VIEW PORT
CORD
VIEW PORT
CORD
VIEW PORT
CORD
FIGURE 14
FIGURE 13
FIGURE 15
FIGURE 12
VIEW PORT
CORD
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.

16
Figures 16 & 17
6. Plug Haven in.
NOTE: The view port hole is made of glass and will not allow any UVC
rays to pass through. A blue glow should be seen in the duct.
TROUBLESHOOT
Make sure that the base is
raised approximately ”, this means the switch is fully engaged.
(See Figure 18
7. Once Haven is working, seal all joints and seams.
8. Place replacement reminder magnet in a safe spot.
TURN CLOCKWISE
LOCKED POSITION
SAFETY SWITCH
SAFETY SWITCH
ENGAGED
SAFETY SWITCH
NOT ENGAGED
TURN CLOCKWISE
LOCKED POSITION
SAFETY SWITCH
SAFETY SWITCH
ENGAGED
SAFETY SWITCH
NOT ENGAGED
TURN CLOCKWISE LOCKED POSITION
SAFETY SWITCH
SAFETY SWITCH
ENGAGED
SAFETY SWITCH
NOT ENGAGED
FIGURE 16 FIGURE 17
FIGURE 18
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.

18
WARNING: UNPLUG
Unplug unit from outlet before commencing inspecon and cleaning.
SAFETY PROCEDURE
Please wear disposable, non-absorbent protecve gloves prior to
inspecon procedure in case of accidental breakage of glass.
1. Inspect and clean UVC lamp every 6 months.
2. Replace UVC lamp annually.
Maintenance
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.
REPLACEMENT PARTS LIST
For replacement parts, contact Air+Health at:
PHONE
FAX
WEB
Scan QR: install guide
airhealth.com/diy-installaon/

20 21
WARNING: UNPLUG
Unplug unit from outlet before starng replacement procedure.
SAFETY PROCEDURE
Please wear disposable, non-absorbent protecve gloves prior to
inspecon procedure in case of accidental breakage of glass.
1. Unlock ballast assembly.
Figure 19 & 20
2. Remove the ballast assembly and lamp.
(See Figure 21
3. Remove old UVC lamp.
(See Figure 22
4. Install replacement UVC lamp.
Figure 23
TURN COUNTERCLOCKWISE
UNLOCKED POSITION
TURN COUNTERCLOCKWISE
UNLOCKED POSITION
FIGURE 19 FIGURE 20
TURN COUNTERCLOCKWISE UNLOCKED POSITION
FIGURE 21
VIEW PORT
CORD
TURN COUNTERCLOCKWISE UNLOCKED POSITION
FIGURE 23
FIGURE 22
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.
Replacement Procedure

22
Figure 24
Figure 25
Figure 26 & 27
Replacement Procedure
8. Plug Haven in.
NOTE: If blue light leaks through any poron of plenum and/or around
mounng plate, unplug power supply cord immediately and seal aected
areas and/or rotate ballast and repeat step #8 above.
9. Dispose of the old UVC lamp according to
WARNING: Never touch broken lamp or internal contents of lamp.
The lamp contains mercury.
NOTE: In case of accidental exposure to internal contents of lamp,
wash hands and any other aected skin area with mild detergent.
Remove aected clothing immediately. If skin surface is pierced,
seek medical aenon immediately.
VIEW PORT
CORD
FIGURE 25
TURN CLOCKWISE
LOCKED POSITION
SAFETY SWITCH
SAFETY SWITCH
ENGAGED
SAFETY SWITCH
NOT ENGAGED
TURN CLOCKWISE
LOCKED POSITION
SAFETY SWITCH
SAFETY SWITCH
ENGAGED
SAFETY SWITCH
NOT ENGAGED
FIGURE 26 FIGURE 27
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.
VIEW PORT
CORD
FIGURE 24

24
UVC LAMP NOT LIGHTING UP:
1.
Figure 18 on page 17.
2.
3.
4.
1.
2.
3.
4.
5.
REPLACEMENT PARTS LIST
For replacement parts, contact Air+Health at:
PHONE
FAX
WEB
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.
Scan QR: install guide
airhealth.com/diy-installaon/

26
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.
Visit link for more warranty info:
THIS WARRANTY IS EXPRESSLY GRANTED IN LIEU OF ALL OTHER
WARRANTIES, INCLUDING BUT NOT LIMITED TO, THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE. AIR+HEALTH SHALL NOT BE LIABLE FOR
ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, WHETHER
DIRECT OR INDIRECT.
Air+Health, LLC
2630 Airport Road,

28
Air+Health Support
airhealth.com/support
Table of contents
Other Air+Health Air Cleaner manuals
Popular Air Cleaner manuals by other brands

FitAir
FitAir JHB-18 user guide

PowerPac
PowerPac IF3255 instructions

IDEAL
IDEAL AP 15 operating instructions

HealthyAir
HealthyAir HA-SSC-G5 owner's manual

Sharper Image
Sharper Image A501 Important instructions & operating manual

AQUAPURE Ozone Technology
AQUAPURE Ozone Technology AOT-D-200 Operation manual