7Marvair MGA3090-3120 I&O Manual 03/2021 Rev.6
Note: Follow local codes and standards when designing duct runs to deliver the required airow.
Minimize noise and excessive pressure drops caused by duct aspect ratio changes, bends, dampers and
outlet grilles in duct runs.
Basic Model Cooling BTUH1EER2Rated Air Flow (CFM)3
MGA3090A 89,000 10 3,500
MGA3120A 118,000 10 4,000
1Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air. 2EER=Energy Efciency Ratio
3CFM=Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage
from that of the rating point will affect performance and air ow.
Table 1. Efficiency and Capacity Ratings at ANSI/AHRI Standard 390
MGA3090A (Stage 1)
Return Air DB/WB Sensible Cooling
Capacity
Outside Air Temperature ºF (ºC)
75 (24) 80 (27) 85 (30) 90 (32) 95 (35)
79/66
BTUH
40,953 40,416 39,874 39,339 38,800
75/61 42,039 40,581 39,164 37,706 36,248
80/63 43,700 42,201 40,662 39,164 37,665
85/65 45,320 43,781 42,201 40,662 39,083
MGA3120A (Stage 1)
Return Air DB/WB Sensible Cooling
Capacity
Outside Air Temperature ºF (ºC)
75 (24) 80 (27) 85 (30) 90 (32) 95 (35)
79/66
BTUH
68,061 65,732 63,372 61,043 58,684
75/61 61,999 59,848 57,758 55,608 53,457
80/63 64,448 62,238 59,968 57,758 55,548
85/65 66,837 64,567 62,238 59,968 57,638
Table 2. Sensible Capacities - Single Compressor Operation
MGA3090A (Stage 2)
Return Air
DB/WB
Sensible Cooling
Capacity
Outside Air Temperature ºF (ºC)
75 (24) 80 (27) 85 (30) 90 (32) 95 (35) 100
(38)
105
(41)
110
(43)
115
(46)
120
(49)
125
(52)
130
(54)
79/66*
BTUH
74,445 73,149 71,827 70,547 69,274 67,701 66,718 65,451 64,829 64,256 63,684 63,114
75/61 77,983 76,678 75,416 74,126 72,843 71,567 70,298 69,071 68,443 66,928 65,326 63,724
80/63 87,060 85,763 84,439 83,158 81,884 79,477 76,184 72,802 71,200 69,598 67,996 66,394
85/65 96,006 94,720 92,738 89,356 85,885 82,414 79,032 75,561 73,870 72,268 70,666 69,064
MGA3120 (Stage 2)
Return Air
DB/WB
Sensible Cooling
Capacity
Outside Air Temperature ºF (ºC)
75 (24) 80 (27) 85 (30) 90 (32) 95 (35) 100
(38)
105
(41)
110
(43)
115
(46)
120
(49)
125
(52)
130
(54)
79/66*
BTUH
99,115 97,304 95,482 93,696 91,900 90,117 88,369 86,611 85,748 84,954 84,162 83,373
75/61 103,575 101,753 99,994 98,197 96,412 94,639 92,878 91,178 90,307 89,440 88,462 86,293
80/63 115,351 113,540 111,693 109,907 108,134 106,373 103,166 98,586 96,417 94,247 92,078 89,909
85/65 126,948 125,152 123,321 121,003 116,303 111,602 107,023 102,322 100,032 97,863 95,694 93,524
Table 3. Sensible Capacities - Dual Compressor Operation