INSTALLATION OF ALARM
Installation of this smoke alarm must conform to all local electrical
codes and Article 760 of the National Electrical Code (NFPA 70)
and NFPA 72. Interconnected units must meet the following
requirements: Total length of wire interconnecting units should be
less than 1000 feet, be #18 gauge or larger and be rated at least
300V. It is recommended that all units be on the same fuse or
circuit breaker. If local codes do not permit, be sure the neutral
wire is common to both phases.
brkcanada.ca
1. Smoke /CO Alarm
2. Ceiling or Wall
3. Power Connector
4. Wire Nut
5. Junction Box
6. Neutral Wire (White)
7. Interconnect Wire (Orange)
8. Hot Wire (Black)
THE PARTS OF THIS ALARM
TECHNICAL SPECS
Alarm Dimensions: 5.0" Dia. x 2.0" H
Weight: 9.3 oz
Operating Voltage:
120V AC 60Hz with 3V alkaline battery backup (two 1.5V)
Operating Current: 0.05 amps (standby/alarm)
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range: 10% to 95% relative humidity (RH)
Audio Alarm: 85dB at 10 feet
Test/Silence: Electronically simulates smoke or CO condition,
causing the unit to alarm. Press and hold test/
silence button.
Alarm Reset: Automatic when smoke or CO clears
Interconnections: Up to 18 units of First Alert or BRK Smoke, CO and
Heat Alarms. Maximum of 12 smoke alarms. See
user’s manual for details.
Smoke Sensor Photoelectric
CO Sensor: Electrochemical
Indicator Lights/Sounds:
AC Power: Constant Green LED
DC Power: Intermittent Green LED
Local Alarm: Red LED ashes rapidly
Remote Alarm: Red LED off
Latching Alarm: Red LED ashes every 5 seconds after local alarm
Low Battery Latch:
“Power” LED ashes green on for 2 sec, off for 2 sec
End of Life: 5 green LED ashes, 5 chirps once per minute
Listing: Certied to ULC STD S531 & CSA 6.19-01
SHIPPING SPECS
Individual Carton Dimensions 5.1" L x 2.4" W x 5.1" H
Weight: 0.8 lbs.
Cube: 0.04 ft3
UPC: 0 29054 00754 4
Master Carton Dimensions 10.6" L x 7.9" W x 10.9" H
Master Pack: 12
Weight: 9.4 lbs.
Cube: 0.6 ft3
I2of5: 700 29054 00754 3
Pallet Information
Cases per Layer: 22
Number of Layers: 4
Cases per Pallet: 88
Units per Pallet: 1,056
Cube: 53.9 ft3
Weight: 875 lbs.
1. Mounting bracket
2. Mounting Slots
3. Locking Pins
4. Hot (Black) AC Wire
5. Neutral (White) AC Wire
6. Interconnect (Orange) Wire
7. Pull-out battery drawer
8. Quick-Connect Plug
CAT. SC7010BA
A. A. Unswitched 120VAC 60 Hz source
B. B. To additional units; Maximum = 18 total
(Maximum 12 Smoke Alarms)
ARCHITECTURAL AND ENGINEERING SPECS
The combination smoke and carbon monoxide alarm shall be a BRK Model SC7010BA and shall provide at a
minimum the following features and functions:
1. A photoelectric smoke sensing chamber and an electrochemical CO sensor both with a 10 year service life.
2. Powered by 120V AC, 60Hz and have a monitored battery backup and a solid state piezo horn rated
at 85dB at 10 ft. and shall be capable of self restoring. The horn shall have a lower and varying horn
frequency to make it easier for the elderly with normal age related hearing loss to better hear the horn.
3. The unit shall have an “End of Life” signal.
4. A visual power-on indicator to conrm unit is receiving AC power or has switched to battery backup
mode. Separate LED’s to indicate a smoke or CO alarm.
5. The CO sensor is adjusted not to detect CO levels below 30 PPM and will not alarm when exposed to
constant levels of 30 PPM for 30 days. It will alarm at the following levels: 400 PPM CO between 4 and
15 minutes, 150 PPM CO between 10 and 50 minutes and 70 PPM CO between 60 and 240 minutes.
6. Two Latching features: Alarm Latch to easily identify initiating alarm after alarm condition has subsided. Low
battery latch: to visually identify which unit is in low battery condition. Two Silence Features: Alarm Silence to
temporarily silence nuisance alarms. Low Battery Silence to silence low battery chirp for up to 8 hours.
7. Two Locking features - tamper resistant locking pins that lock battery drawer and/or alarm to mounting bracket.
8. The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and relative humidity
between 10% and 95%.
9. The unit shall have a plug in connector and be capable of interconnection of up to 18 alarms, 12 of which
can be smoke alarms.
10. The unit shall at a minimum meet the requirements of UL217 and UL2034, CSFM, NFPA 72 and 720
and the ICC.
© 2021 BRK Brands, Inc. All rights reserved.
Distributed by BRK Brands, Inc., Aurora, Illinois 60504.
BRK Brands, Inc. is a subsidiary of Newell Brands Inc.
(NASDAQ: NWL). Rev 10/20