TRM500
Temperature controller
TRM500_0283_EN
© All rights reserved. Subject to technical changes and misprints.
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
Tel: +49 (0) 511 16 59 6720 · www.akytec.de
1 Functional description
The TRM500 is a versatile temperature controller with switching current up to 30 A. The device has a
universal input for a wide range of resistance thermometers and thermocouples as well as a digital
input. It is provided with a relay output, an alarm output, a DC logic output. The outputs can be
configured for different tasks (see Appendix A). The controller can be quickly configured by using three
keys.
Functions:
– On-Off or PID control (see Fig. 1)
– Manual control
– 20 mm, 4 digit display, 2nd display optional
– Digital input filter with an adjustable time constant
– Custom 2-point linearization
– Digital input (remote start/stop or setpoint change) (see Appendix D)
– Temperature range alarm
– Auxiliary alarm output
– Additional logic output (SSR)
– Configurable outputs (see Appendix A)
– Autotuning function (see Appendix C)
– Cold junction compensation
– Input calibration (see Appendix E)
– 9 status LEDs
Ordering key:
2 Safety precautions
Make sure that the device is fully disconnected from auxiliary power before
starting any commissioning or repair work.
CAUTION Connect the power supply only after the wiring has been completed.
DANGER Do not use the device where it is subjected to flammable or explosive gas.
3 Specifications
Table 1 General data
230 (96…264) V AC; 50 (47...63) Hz
Pt50, Pt100, Pt500, Pt1000, Ni100, Ni500, Ni1000
Sampling time for 2- / 4-wire
30A / 250 V AC (resistive),
20A / 30 V DC
5A / 250 V AC, 3A / 30 V DC (resistive)
up to 80% (non-condensing)
Fig. 1 Control
Fig. 2 Block diagram
4 Installation and electrical wiring
Fig. 3 Mounting and dimensions
Fig. 4 Electrical wiring
The maximum wire size is 0,75 mm².
5 Maintenance
Technical maintenance should be performed on the device at least every six months by maintenance
personnel and comprising the following tasks:
– Removing dust, dirt and foreign matter from the housing.
– Checking mounting of device
– Checking connections
The safety guidelines in Section 2 must be observed when performing maintenance.
6 Transportation and storage
The device must be transported in closed transport boxes.
Protective measures against shocks, vibrations and humidity must be observed.
Storage temperature range -30…+60 °C.
There may be no chemically active substances in the air.
7 Package content
– Temperature controller TRM500 1
– User manual 1
Appendix A. Output configuration
Appendix B. Displays and control elements
30A - relay 30 A, display with 20 mm digit height
+display with 10 mm digit height
TRM500-X
t, s
t, s
0
0
t, s
t, s
ON/OFF control PID control
T °C T °C
SP+∆
SP
SP - ∆
SP
Relay
ON
OFF
0000
0000
SENSOR
DI
Control
Alarm
OUT2
Relay 5 A
OUT1
Relay 30 A
OUT3
SSR
Alarm
Pulse
control
Load
Load
Temperature
sensor
TRM500
OUT1 OUT2 OUT3
30 A, 230 VAC
20 A, 30 VDC
N
L1 N
L1 NL1
DI SENSOR
SSR
230 VAC
LOAD
5 A, 230 VAC
3 A, 30 VDC
25-40 mA
0/5 VDC
LOAD
RTD
2-wire
RTD
3-wire
RTD
4-wire
TC
REMOTE
POWER
SUPPLY
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ConF=1.U
ConF=3.U
ConF=2.U
t
t
t
t
Alarm logic
DI
DI
DI
Control
Alarm
Alarm
Alarm
OUT1
Relay 30 A
OUT2
Relay 5 A
OUT3
SSR
OUT2
Relay 5 A
OUT3
SSR
OUT1
Relay 30 A
OUT2
Relay 5 A
Control
Control
I
II
III
or
ConF=1.
or
ConF=2.
OUT2
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OUT2
OUT2
OUT1
(inside range)
U (outside range)
U.Lo U.Hi
Output configuration
U
U
U
Display D1
- measuring value (Operation)
- setpoint (Operation)
- control signal (Manual)
- parameter group (Setup)
- parameter name (Setup)
Display D2
- setpoint (Operation)
- measuring value (Manual)
- control signal (Manual)
- parameter name (Setup)
- parameter value (Setup)
- parameter value (Setup)
— — — error (sensor failure, CJC failure,
exceedance of the measuring range)
TRM500
°C
TEMPERATURE TRANSMITTER
T
UP
T
NORM
T
DOWN
SP1
SP2
AUTO
MAN
ON
ALARM
PROG
SP1
- lit when SP1 or SP1 + SP2 is activ
- flashes when correction setpoint
SP2
- lit when SP2 or SP1 + SP2 is activ
- flashes when correction setpoint
AUTO
- lit when control is activ
- flashes when PID autituning
MAN
- lit when manual control is activ
Shotly - increasing of parameter value
Shotly - selecting a menu item (Setup)
- next parameter
Shotly - decreasing of parameter value
- previous parameter
- cancel modification (Setup)
- confirmation of the modification and switch
to the next parameter (Setup)
> 3 s - end of menu ( oUt)
> 3 s - switch to the Setup mode (Operation)
PROG
T
UP
T
NORM
T
ON
ALARM
DOWN
- lit when sensor failure and/or exceeding alarm limits
- lit when OUT1 or OUT3 is ON
- lit when T < lower alarm limit
- lit when T inside the alarm limits
- lit when T > upper alarm limit