Albany ACS-50 User manual

6410T0008_REV_G
USER MANUAL
ACS-50 CONTROL PANEL
ASSA ABLOY ENTRANCE SYSTEMS
975-A Old Norcross Road
Lawrenceville, Ga 30046
800-252-2691 Tel
770-338-5034 Fax
www.albanydoors.com

Part # 6410T0008 Rev.F
-2-
Table of Contents
ACS-50 CONTROLLER SPECIFICATIONS ...................................................................................................................................... 3
ACS-50 ELECTRICAL PRACTICES .................................................................................................................................................. 4
ACS50 Control Panel Interior (Single speed) .................................................................................................. 5
ACS-50 Motherboard Layout .......................................................................................................................... 6
ACS50 Control Panel Interior (Two speed) ..................................................................................................... 6
WIRING TO PANEL ....................................................................................................................................... 9
Incoming Power ............................................................................................................................................................................ 9
Voltage Selector Jumper (J2) ........................................................................................................................................................ 9
Wiring of the Motherboard ........................................................................................................................................................... 9
ACS-50 SETTINGS AND ELECTRICAL STARTUP ...................................................................................................................... 11
CPU Card Switch Settings ............................................................................................................................. 11
(SW2) Rotary Selector Switch for Closing Time ........................................................................................................................ 11
Table 2 – Sw2 Settings ................................................................................................................................... 11
Setting of Opening and Closing Functions .................................................................................................... 12
Table 4 – Led Indication of the CPU Card .................................................................................................... 13
Electrical Start Up .......................................................................................................................................... 14
Micro switch ............................................................................................................................................................................... 14
Contact point ............................................................................................................................................................................... 14
Limit Switch Coarse Adjustment ................................................................................................................................................ 15
Turning on the Door Controller .................................................................................................................................................. 15
Phase Check ................................................................................................................................................................................ 15
Hold-to-Run-Function ................................................................................................................................................................. 16
Input Device Check ..................................................................................................................................................................... 16
Limit Switch Fine Adjustment .................................................................................................................................................... 16
The Crash-Function ..................................................................................................................................................................... 16
Runtime Monitoring .................................................................................................................................................................... 17
Safety Circuit Limit Box (GFA Drives Only) ............................................................................................................................. 17
Photocell Cut-off (GFA Drives Only) ......................................................................................................................................... 17
Inertia Brake Wiring (if Equipped) ............................................................................................................................................. 17
Pressure Switch Adjustment (if Equipped) ................................................................................................................................. 18
TROUBLESHOOTING ...................................................................................................................................................................... 19
WD501-BF002 = ACS50 1 Speed - Bonfiglioi Motor & Limit Diagram – Models 570 & 670 ................................................ 21
WD501-BF003 = ACS50 2 Speed - Bonfiglioli Motor & Limit Diagram - Models 570 & 670 ................................................ 22
WD501-BF007 = ACS50 1 Speed - Bonfiglioli Motor & Limit Diagram - Model 392 ............................................................ 23
WD501-BF006 = ACS50 1 Speed - Bonfiglioli Motor & Limit Diagram Model 230 .............................................................. 24
WD501-BF005 = ACS50 2 Speed - Bonfiglioli Motor & Limit Diagram Model 230.............................................................. 25
WD501-BF008 = ACS50 Bonfiglioi Motor & Limit Diagram – Model 392 .............................................................................. 26
WD501-0V000 = ACS50 Ovitor Motor & Limit Diagram ......................................................................................................... 27
WD501-GF002 – ACS50 GFA Operator Wiring 1-Speed .......................................................................................................... 28
WD501-GF001 - ACS50 GFA Operator Wiring 2-Speed .......................................................................................................... 29
WD502-0000-1 = Door Control Wiring Electric Edge and Crash Sensor .................................................................................. 30
WD503-PC000 = Reversing Photocell Wiring ........................................................................................................................... 31
WD504-0000 = ACS50 Actuator Options .................................................................................................................................. 32
WD502-0000A = Interlocking two ACS50 Units ....................................................................................................................... 33
ACS50 Contactless Safety Edge Wiring (if equipped) ............................................................................................................... 34
Blanking Light Curtain Photocell Wiring ................................................................................................................................... 35
ACS 50 Floor Loop 2Posi Selector Switch ................................................................................................................................. 36
CONTROL PANEL REPLACEMENT PARTS ................................................................................................................................. 37

Part # 6410T0008 Rev.F
-3-
ACS-50 CONTROLLER SPECIFICATIONS
ACS50 SPECIFICATIONS VALUES
SUPPLY VOLTAGE:
208-240 VAC 3-PHASE
440-480 VAC 3-PHASE
575-600 VAC 3-PHASE
MAXIMUM CURRENT:
10 AMPS
TEMPERATURE, MINIMUM:
-4 F, -20 C
TEMPERATURE, MAXIMUM:
+131 F, +55 C
ENCLOSURE PROTECTION CLASS:
NEMA 1, 3R, 4, 12 AND 13
NOTE: 4X STAINLESS OPTIONAL
DIMENSIONS:
11.8“W X 15.75“H X 8.25“ DEEP
WEIGHT:
24 LBS
ALBANY DOOR SYSTEMS RAPID ROLL DRIVE UNITS
1-speed brake motor 2-speed brake motor Unit
Output power 1.5 1.5/1 HP
Voltage 208-240 440-480 550-600
208-240 440-480 550-600 VAC
Current 4.9 2.5 1.85 4.9/3.6 2.5/1.8 1.87/1.36 A
NEMA 12 / 13 12 / 13
Protection Thermal Switch Thermal Switch
WARNING
DO NOT INSTALL, OPERATE, OR SERVICE THIS PRODUCT UNLESS YOU
HAVE READ AND UNDERSTAND THE SAFETY PRACTICES, WARNINGS,
INSTALLATION, AND MAINTENANCE INSTRUCTIONS CONTAINED IN THIS
MANUAL.

Part # 6410T0008 Rev.F
-4-
ACS-50 ELECTRICAL PRACTICES
WARNING
THE ACS-50 CONTROL BOX CONTAINS HIGH VOLTAGE. QUALIFIED ELECTRICAL
PERSONNEL SHOULD PERFORM THE FOLLOWING PROCEDURES ONLY. WIRING AND
CONTROL PANEL MOUNTING (ANCHORING) MUST MEET ALL LOCAL, STATE, FEDERAL,
INTERNATIONAL, OR OTHER GOVERNMENT AGENCY CODES.
FAILURE TO DO SO COULD RESULT IN SERIOUS INJURY OR DEATH.
THE CONTROL PANEL SHOULD BE MOUNTED APPROXIMATELY 48 INCHES OFF OF THE
FINISHED FLOOR FOR EASE OF TROUBLESHOOTING AND SERVICE. WIRING FOR POWER,
(MOTOR AND BRAKE) SHOULD BE A MINIMMUM OF 14AWG. FOR CONTROL WIRING,
SHOULD BE A MINIMUM OF 18 AWG.
1. NOTE: REFERENCE FIGURE BELOW AS A GUIDE FOR MAKING THESE WIRE
CONNECTIONS TO THE UNIQUE WAGO STYLE TERMINALS.
WARNING
A SEPERATE FUSED DISCONNECT IS REQUIRED FOR
PROTECTION OF THE DRIVE AND CONTROL SYSTEM.
THIS DISCONNECT IS TO BE SUPPLIED BY OTHERS. THE
DISCONNECT PROVIDED ON THE CONTROL BOX IS NON-
FUSED. ALL CONDUIT PENATRATIONS MUST BE IN THE
BOTTOM OF THE CONTROL PANEL ENCLOSURE. TOP
PENATRATION OF THE ENCLOSURE CAN VOID
WARRANTY.
1. Insert a mini screwdriver in the operating
slot, located on the top of the terminal, up to the
stop.
2. The screwdriver blade holds the clamping
spring open automatically so that the conductor
can be introduced into the clamping unit
3. Insert the wire into the block.
4. Withdraw the screwdriver – the conductor is
automatically clamped.

Part # 6410T0008 Rev.F
-5-
ACS50 Control Panel Interior (Single speed)

Part # 6410T0008 Rev.F
-6-
ACS-50 Motherboard Layout
The following refers to the layout of the motherboard inside the ACS 50 control box:
ACS50 Control Panel Interior (Two speed)
Contactor
”KM1” and ”KM2”
Control Fuses, FU1 – FU6
Cycle Counter
CPU Card Slot
Brake Rectifier (230VAC)
Panel Disconnect, Non-
fused
Voltage Selector Jumper,
J2
Motherboard
Contactor
”KM3” 2- Speed Only”
Motor lead wiring

Part # 6410T0008 Rev.F
-7-
Figure 7 – Single Speed Motherboard

Part # 6410T0008 Rev.F
-8-
Figure 8 – Two Speed Motherboard

Part # 6410T0008 Rev.F
-9-
WIRING TO PANEL
Incoming Power
Three Phase power coming from a FUSED DISCONNECT is wired into T1, T2, and T3. Located on the
disconnect.
Voltage Selector Jumper (J2)
Check J2 for the proper incoming voltage level. This jumper wire comes from the motherboard and is
terminated on a terminal below the control transformer. This is factory preset and should not normally need
to be changed.
Pneumatic safety edge (if equipped)
The pneumatic edge pressure switch is wired to a set of terminals 7A and 8A for rapid roll doors, which is
mounted on the din rail right below the motherboard. (Required for door operation.) Re-Coil-Away and Rapid
Roll 392 doors do not have this resistor in the control panel but located on the end of the safety edge
Electric Edge Connection (if equipped)
Connect the electric edge directly to terminals 7 and 8 (edge is not adjustable). To test, (turn power on)
bump the rubber safety edge with your hand observe LED 6 (see Figure 5 for location), it should flash on
briefly. The edge is now operational.
Ground Bar
All grounds coming into the panel should be terminated on the ground bar at the bottom of the panel.
Wiring of the Motherboard
The motherboard component layout and numbering is shown in Figure 7 for ONE-speed motors, and in
Figure 8 for TWO-speed motors. Also refer to wiring diagrams on pages 18-30 for the following: Ovitor
motors Figure 9, for Bonfiglioli motors Figure 10, for GFA drives. Table 1 shows the motherboard terminal
listing and descriptions. For any additional external devices consult factory for wiring details.
Figure 10 Figure 11
Figure 9

Part # 6410T0008 Rev.F
-10-
Table 1 - Mother Board Terminal Wiring
Terminal Notice Description
T3, N, N NOT USED Mains output (
NOT USED
)
U,V,W Motor (Single Speed) (Din rail mounted on Version 2 board)
U2,V2,W2 Motor (Two Speed) (Din rail mounted on Version 2 board)
1 & 2 Stop1 N.C.
1A & 2A Inertia Brake if applicable Stop2 N.C.
3 & 4 Open N.O.
3A & 4A Open N.O.
5 & 6 Close N.O.
5A & 6A Close N.O.
7 & 8 Electric Edge option Electric Safety edge, resistor principle, 8,2kOhm
7A & 8A Pneumatic Edge option Pneumatic Safety Edge With Seriesed 8.2kOhm resistor
9 & 10 Limit switch “Door opened”
12 & 13 Limit switch “Door closed”
20
See WD503-PC000 for details
Safety photocell 1 – power (DC-)
21 Safety photocell 1 - power (DC+) Switched for self test
22 Safety photocell 1 - power (DC+)
23 Safety photocell 1 - Signal
20A
See WD503-PC000 for details
Safety photocell 2 – power (DC-)
21A Safety photocell 2 - power (DC+) Switched for self test
22A Safety photocell 2 - power (DC+)
23A Safety photocell 2 - Signal
33 Output, 24VDC Negative
33A
34 Output, 24VDC Positive
34A
35 & 36 Motor Thermal switch contact (jumper to 36 if not used)
37 & 38 Hoist or Brake disengagement (jumper to 38 if not used)
45 & 46 Optional Crash sensor (jumper to 46 if not used)
53 & 54 Reserve, input
55 & 56 Reserve, output
63 & 64 Output, 24V AC
70 & 71 BRAKE 180VDC output (not used on Ovitor motors)
74 Optional Dry contact contact “Door opened” (Common)
Dry contact contact “Door opened” (N.O.)
Dry contact contact “Door opened” (N.C.)
75 Optional
76 Optional
77 Optional Dry contact contact “Door closed” (Common)
Dry contact contact “Door closed” (N.O.)
Dry contact contact “Door closed” (N.C.)
78 Optional
79 Optional
80 Optional Dry contact contact “Warning light”
80A Optional
81 Optional Dry contact contact “Warning light”
81A Optional
82 Optional Dry contact contact “ Alarm, Door not ready to work” (N.O.)
83 Optional Dry contact contact “ Alarm, Door not ready to work” (Common)
84 Optional Dry contact contact “ Alarm, Door not ready to work” (N.C.)
N.O. = Normally Open circuit N.C. = Normally Closed Circuit

Part # 6410T0008 Rev.F
-11-
ACS-50 SETTINGS AND ELECTRICAL STARTUP
CPU Card Switch Settings
(SW2) Rotary Selector Switch for Closing Time
Automatic closing can be set from 1-60 seconds. The potentiometer (SW2) is located on the CPU-card; see Figure 12
and Table 2 for settings.
Note: the SW2 in combination with the SW1 setting also has an effect on the operation sequence as shown in Table 4.
Refer to Figure 12 for switch location.
Table 2 – Sw2 Settings
SW2 Position 0 1 2 3 4 5 6 7 8 9 A B C D E F
Close
Time ↕ 1 2 3 4 5 7 10
13 16 19 22 25 30 45 60
Note: When SW2 is set in position 0, the door will not automatically close. You need to give a new impulse of an OPEN
device to close the door or impulse a CLOSE device.
Jumper J1- Bottom Edge Selector
The Jumper1 is located on the CPU-card as shown on Figure 12. This is factory set as shown below.
FIGURE 12 – CPU Card
1
3
JUMPER
SW2
SW1
EPROM
LED 1
LED 26
LED 17
J1
Top of Board
2
Top of Board

Part # 6410T0008 Rev.F
-12-
Setting of Opening and Closing Functions
In the table below, SW1.1 means switch position 1 on SW1 dipswitch. Likewise, SW1.2 means
switch position 2 on SW1 dipswitch. Refer to Figure 12 for switch location. The greyed out section
below shows the factory settings. You need to change these settings for your particular needs.
Table 3– Setting of Opening and Closing Functions
SW 1.1 SW 1.2 SW 2 Terminal 3(A),4(A)
(Remote Activation)
Terminal 5(A),6(A)
(Remote Activation)
Panel Buttons
UP DOWN
ON ON 0 UP – DOWN UP – DOWN UP DOWN
ON ON 1-F UP – AUTO. + CAP UP – DOWN UP- AUTO DOWN
ON OFF 0 UP UP – DOWN UP DOWN
ON OFF 1-F UP – AUTO. UP – DOWN UP - AUTO DOWN
OFF ON 0 UP + CAP DOWN UP - CAP DOWN
OFF ON 1-F UP – AUTO. UP – AUTO. UP - AUTO DOWN
OFF OFF 0 UP DOWN UP DOWN
OFF OFF 1-F UP – AUTO. DOWN UP - AUTO DOWN
SW1.3
OFF = Does not require reset after safety edge trip.
ON = Requires reset after safety edge trip. Must reset by hold to close by pressing down
button and fully closing the door
LEGEND for Table 3:
AUTO. = Automatic closing from open position. Delay before close time is adjustable from1 sec to
60 seconds depending on SW2 setting as specified in TABLE 2. The UP button (or 3(A) & 4(A)
remote) will reset the timer, and prevent the door from closing until released. The shaded row in the
above table is the most commonly used settings for auto close function.
CAP = Automatic “CLOSE AFTER PASSING” the door photocell. The door will remain open until
the photocell beam is broken and re-established. If the door is in UP – AUTO + CAP mode, it will
then close after a fixed 2-second delay (not adjustable) once the photos have been passed through
and cleared. If the door is in UP –CAP mode, the door will then close after the UP (or 3(A) & 4(A)
remote) or DOWN (or 5(A) & 6(A) remote) buttons are pressed
UP – DOWN = When the door is open, an impulse of the UP button (or 3(A) & 4(A) remote) will
close the door when in this mode.

Part # 6410T0008 Rev.F
-13-
Table 4 – Led Indication of the CPU Card
LED
#
LED
COLOR Wiring Terminals / Notes Function Status
Open
Status
(MID)
Status
Closed
1 Yellow 3(A) & 4(A)
5(A) & 6(A) Signal Open OFF OFF OFF
2 Green 1 & 2 or 1A & 2A
(Jump if not used)
Signal Stop /
Inertia Brake if Applicable ON ON ON
3 Yellow Signal Close OFF OFF OFF
4 Yellow 9 & 10 Limit switch “Door opened” ON OFF OFF
5 Yellow 12 & 13 Limit switch “Door closed” OFF OFF ON
6 Red
7a and 8a if pneumatic
7 and 8 if Electric
(8.2K resistor to bypass into 7 & 8)
Safety edge (on if activated) OFF OFF OFF
7 Green
20,21,22,23
(Jump 21 to 23 to bypass for testing only)
See schematics for color code wiring
Safety photocell 1
(off if beam is blocked or not aligned) ON ON ON
8 Green 35 & 36
(Jump if not used) Thermal contact ON ON ON
9 Green 37 & 38
(Jump if not used) Manual lever or Hoist disengagement ON ON ON
10 Yellow Ribbon cable Open button of the control box OFF OFF OFF
11 Green 45 & 46
(Jump if not used) Crash sensor ON ON ON
12 Red Optional input --- OFF OFF
13 Yellow On while door is closing Test of “close”-relay OFF OFF OFF
14 Yellow Ribbon Cable Close button of the control box OFF OFF OFF
15 Green
20A, 21A, 22A, 23A
(Jump 21A - 23A to bypass for testing only)
See schematics for color code wiring
Safety photocell 2
(Off if beam is blocked or not aligned) ON ON ON
16 Yellow Not Used OFF OFF OFF
17 Yellow (Tab on open contactor will move when
door is opening) Relay “Open” OFF OFF OFF
18 Yellow (Tab on close contactor will move when
door is closing) Relay “Close” OFF OFF OFF
19 Yellow 70 & 71 – (Measure 180 VDC output) Brake OFF OFF OFF
20 Red Red illuminated stop button on the face of
the control box
(FLASHES FOR 3 SECONDS ON STARTUP)
Solid if error. Verify LED’s on this chart OFF OFF OFF
21 Yellow 80 & 81 / 80A & 81A
10A 250VAC DRY CONTACT ONLY
Traffic light or Warning light / horn
(On during open & 2 sec’s priot to & closing) OFF OFF OFF
22 Green 82 & 83 N.O. / 83 & 84 N.C.
10A 250VAC DRY CONTACT ONLY Alarm / Fault Indicator ON ON ON
23 Yellow Optional output OFF OFF
24 Green Test of the photocell ON ON ON
25 Red Check photo wiring for bad connections Error indicator – Photocell has a short circuit OFF OFF OFF
26 Red Dip switch SW 1.3 is set to on Error indicator –
Safety edge requires reset (see SW1.3) OFF OFF OFF

Part # 6410T0008 Rev.F
-14-
Electrical Start Up
WARNING
First you must determine what type of limit box you have. Consult Figures below to determine this.
Figure 14 is the STROMAG limits box. Figure 15 is the TEMEC limit box. Figure 16 is the GFA limit
Box.
Figure 14 Figure 15
Adjustment Screw
Closed
Limit Cam
Open Limit Cam
Microswitches
Microswitches
Top
Limit
Bottom
Limit
Allen Wrench
Figure 17
Contact point
Micro switch
Adjustment point
Cam Lock
Gearbox
Close Limit Cam
Open
Limit Cam
Figure 16

Part # 6410T0008 Rev.F
-15-
Limit Switch Coarse Adjustment
Refer to the Electrical drawing WD501-0V000 for wiring of the Temec/Ovitor limit switch. For the
wiring of the Stromag Limits refer to Electrical drawing WD501-BF000. For GFA LIMIT Boxes refer
to electrical drawing WD501-GF02.
Warning
Rotation of the open limit cam in the wrong direction or incorrect phasing may cause the
bottom beam assembly to jam into the top roll.
1. Remove the limit switch box cover, and manually bring the door down to one foot below the full
open position. Observe the rotation direction of the limit cams while the door moves.
The limit switch box for the TEMEC/Ovitor (figure 15) is located on the gearbox; The Temec
style limit uses the threaded brass bolt to finely adjust limit switch cams. NOTE: A SMALL
CHANGE IN THE CAM POSITION WILL RESULT IN A LARGE CHANGE IN THE
MOVEMENT OF THE DOOR.
The Stromag limits (figure 14) module is attached to the Bonfiglioli Motors via the chain
drive. The Stromag sytle limits use a screwdriver to rotate the adjustment screw
The GFA (figures 16 & 17) limit switch box is located behind the motor and under the
gearbox.) Using the included Allen wrench loosen and then rotate the open limit cam (figure
17 &18) until it makes contact with its associated micro switch. Then lock the cam with the
Allen wrench. The RED open and close safety limit cams are pre-adjusted and are
piggybacked to the Green open and close limit cams. If this safety point needs to be
corrected this can be adjusted using the fine adjustment screw to advance or retard the
position of the red cam in relation to the position of the green cam. The red cams are so the
door stops safely if the direction of the rotation is reversed or the open limit switch fails.
During normal operation the RED cams should never make contact with their switch but
should be close enough to activate if the primary limits fail.
2. Rotate the open limit cam until it makes contact with its associated micro switch.
3. Move the door to one foot from the fully closed position. Observe the rotation direction of the
limit cams while the door moves.
4. Rotate the closed limit cam until it makes contact with its associated micro switch.
Turning on the Door Controller
When the door controller has been wired correctly, the switch SW1 and SW2 settings are complete,
and the coarse limit adjustment is complete, the power may be turned on. Upon power up, the door
controller will do an initial test for 3 seconds to see whether the software and the RAM are working
properly. During this 3-second test, the controller will not respond to any open or close signals and
the door will not open or close and the red illuminated button on the control box will flash.
If the test detects a failure, the red illuminated button will illuminate constantly, the alarm relay will
be activated, and the door controller becomes locked.
When the initial-test is over and no fault has been detected, the controller is ready to work.
Phase Check
Note: in this step it is assumed that the door is still closed from the coarse limit-setting step.

Part # 6410T0008 Rev.F
-16-
1. Be prepared to press the STOP button. (Stop on the front panel is a momentary stop only!
Door can be activated by motion detector, floor loop, or any activation device) It is highly
recommended that ALL automatic or remote activations be disconnected during the
startup of the door. This will eliminate unwanted activations which can create startup
issues.
2. Push the open impulse button. The door should open at full speed.
2.1. If the door starts to close, stop the door immediately by pressing the STOP button and swap
the position of the incoming power wires to T1 & T2.
2.2. If the door opens, make sure it stops at the open limit. If it goes beyond the open limit as set
in the coarse limit-setting step, stop the door immediately and troubleshoot the limit wiring
and/or setting.
3. Repeat this check until the door opens to top limit and stops at the close limit.
Hold-to-Run-Function
If the safety edge or safety photocells (safety circuits) have any fault(s), the door will no longer
close automatically, and the system will go into Hold-to-run mode. An illuminated Stop button on
the control panel indicates hold-to-run mode.
If the Hold-to-run-mode is activated, it is not possible to close the door via external activators or
signals.
It is necessary to push the “Close” button to reset the door controller. Every other signal to reset will
not have any effect.
Reset of the Hold-to-run mode will occur when both safety circuits are working again and pushing
the CLOSE button on the control panel successfully closes the door.
Input Device Check
Press the STOP button to prevent the door from moving. Operate each applicable input device as
listed in Table 3 to verify device wiring. Refer to Table 4 to understand the proper light indication.
When finished, restore the door from hold to run mode as described above.
Limit Switch Fine Adjustment
Refer to the limit switch appendix for details on the specific limit switch type used on your door.
1. Make sure the door can be actuated to open and close properly and that the door stops at the
coarse limit settings.
2. Make small adjustments to the cams and cycle the door open and closed to observe changes in
the limit settings.
3. Continue to finely adjust each cam until the desired door limits are attained. Once the door limits
are adjusted correctly and the door is operating satisfactorily. Replace the limit switch box
cover. On the Temec style and GFA style of limit box ensure the limit cams are tightened and
locked.
The Crash-Function
(For doors with breakaway and impact detection only)
if the door has been impacted and the bottom beam has been knocked out of the side-frame, the
door stops immediately and the red illuminated push button is lit.

Part # 6410T0008 Rev.F
-17-
Once the door has been impacted, to restore full function of the door, press the ▲ up arrow button.
The door then will go to full open and reset itself close.
Runtime Monitoring
The controller has an internal timer to measure the door run time when opening or closing. The
timer expires after the door runs continuously for 20 seconds (some doors have a 40 second
EPROM). If this occurs, the door will immediately stop and the red button on the panel will be lit
solid. To reset this condition, disconnect main power (off). Verify that the door is not binding or you
have a motor/gearbox problem. After this check, then reapply power.
Safety Circuit Limit Box (GFA Drives
Only)
The terminals 21 to 28 on the limit
switch figure 18 are reserved for the
safety circuit. An interruption of the
safety circuit causes the control voltage
to be interrupted. Electrical operation is
no longer possible when this occurs.
Photocell Cut-off (GFA Drives Only)
The limit switch (S6) must be adjusted
to bypass the photocells when the door
is approximately 8 inches off the
ground. This allows the bottom loop on
the bottom beam assembly to clear the
photocell and not cause the door to
reverse. Not used with Light Curtains.
Inertia Brake Wiring (if Equipped)
(Re-Coil-Away Doors ONLY with chain drive and without counter balance springs)
The inertia brake needs to wired in order for the door to operate. Refer to electrical drawings for
wiring points. If the red indicator is extended from the housing the electrical contact will be in an
open position and thus preventing the door from operating.
Figure 18
S5 AUX
S6 Photocell Cutoff

Part # 6410T0008 Rev.F
-18-
Pressure Switch Adjustment (if Equipped)
Bump the rubber safety edge with your hand observe LED
6 (see Figure 9 for location), it should flash on briefly. If the
LED does not flash, adjust the switch. The pressure switch
is located on the bottom beam see Figure 19. Remove the
cover of the pressure switch enclosure. Rotate the white
plastic screw on the pressure switch clockwise with a small
screwdriver until the LED 6 turns on. Then rotate the screw
counter-clockwise until LED 6 turns off, and then rotate an
additional ¼ turn. Test the safety edge and observe LED 6
(it should turn on momentarily whenever pressure is applied
to safety edge). (Note: LED 26 turns off if edge fails pulse
test when in pneumatic mode = not used.)
Figure 19

Part # 6410T0008 Rev.F
-19-
TROUBLESHOOTING
TABLE 5- Controller Faults
Red Lamp
+ LED 20
(ON PANEL STOP
BUTTON)
Alarm
(OUTPUT
TERMS 82-84)
Error Description Indication
Flash ON Power on test First 3 seconds after Power on
Flash ON Manual lever,
Handcrank, activated LED 9 = OFF
ON ON Safety edge error LED 6 = ON
ON ON Photocell error LED 25 = ON
OFF OFF Photocell blocked LED 7 = OFF (Photocell 1)
LED 15 = OFF (Photocell 2)
ON ON Thermal contact activated LED 8 = OFF; Door controller is
locked
ON ON Safety edge was triggered:
SW1-3 = ON LED 26 = ON
ON ON EPROM Check sum error Door controller is locked; No
“power on test” indication
ON ON RAM Error Door controller is locked; No
“power on test” indication
If LED’s 7, 8, 9, or 15 is not on when the system is powered up it will go into a locked condition. Reset
power and see which light is not lit and then check that item to get that light to be on.
If you have all the proper LED except for LED’s 2 & 4 you need to check the wiring and or jumpers at
terminals 1& 2 or 1A & 2A.
No lights on the CPU CARD
Terminal 33 and 34 should have 24VDC availible if not
check fuses.
Also check terminal 63 and 64 for 24VAC

Part # 6410T0008 Rev.F
-20-
ULTRA ACS-50 FUSING SIZE CHART-(GFA MOTOR)
VOLTAGE
MOTOR TYPE
MOTOR HP
MOTOR FLA
PANEL FLA
PANEL MAIN FUSE
208V
1-SPEED
2.0
7.5
9.9
208V 3
-
Phase
3.0
10.6
13.0
208V 3
-
Phase
2-SPEED
2.0
7.5
9.9
208V 3
-
Phase
3.0
10.6
13.0
208V 3
-
Phase
230V
1-SPEED
2.0
6.3
7.8
230V 3
-
Phase
3.0
9.6
10.7
230V 3
-
Phase
2-SPEED
2.0
6.3
7.8
230V 3
-
Phase
3.0
9.6
10.7
230V 3
-
Phase
460V
1-SPEED
2.0
3.4
3.9
460V 3
-
Phase
3.0
4.8
5.47
460V 3
-
Phase
2-SPEED
2.0
3.4
3.9
460V 3
-
Phase
3.0
4.8
5.47
460V 3
-
Phase
575V
1-SPEED
2.0
9.6
10.7
575V 3
-
Phase
3.0
3.9
4.3
575V 3
-
Phase
2-SPEED
2.0
9.6
10.7
575V 3
-
Phase
3.0
3.9
4.3
575V 3
-
Phase
Table of contents
Popular Control Panel manuals by other brands

Honeywell
Honeywell PL-1000 Installation and user manual

St. Croix
St. Croix DHC3000 instructions

UPS Aviation Technologies
UPS Aviation Technologies 10 user guide

Pro-tec
Pro-tec Algo-Tec 6400 manual

Bosch
Bosch Solution Ultima 880 Quick reference guide

Gamewell
Gamewell ZNS Installation & operation manual

Swegon
Swegon CASA Genius quick start guide

CAME AMERICA AUTOMATION
CAME AMERICA AUTOMATION Z Series installation manual

Nederman
Nederman HV Series user manual

bolid
bolid SIGNAL-20M Operation manual

See Water
See Water Oil Smart OSD3P-30 Series Installation and operation manual

RESEARCH CONCEPTS
RESEARCH CONCEPTS RC4600 Operator's manual