manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Alemlube
  6. •
  7. Measuring Instrument
  8. •
  9. Alemlube 51008 User manual

Alemlube 51008 User manual

Suitable for Measuring the transfer of diesel, petrol and kerosene
Flow rate 15L M to 120L M
Maximum ressure 3 bar (50 SI)
Weight 2.0kg Accuracy-+1.0%
Inlet/Outlet connections 1” BS (F)
Ope ating Inst uctions
1 Configure the meter in an orientation that suits your application i.e.: by
undoing screws at the base of the meter and reorientate the meter so that
the inlet and outlet of the meter suit your application.
2 Connect the meter inlet to the hose or fixed fitting that the product is being
delivered through.
3 Once threads connected and completely sealed with thread tape, open the
tanks on/off valve or start up the pump.
4 Diesel fuel, petrol or kerosene will now start to flow through to the
mechanical flow meter turning over the batch recording digits and totaliser
recording digits
Impo tant To Note:
The 51008 and 51008F fuel meters are pre-calibrated in factory to be used with
diesel fuel. As specific operating conditions (such as real flow rate, the viscosity
and temperature of the measured fluid) may affect the meter accuracy, a
recalibration should be carried out after the installation has been completed. A
new calibration is necessary each time the meter is disassembled for
maintenance operations or when it is used to measure fluids that differ from
diesel fuel.
Calib ation P ocedu e
1 Unscrew the plug ( art No. 51008-4)
2 urge the system (pump, pipelines, meter) of air by dispensing until the flow
of diesel fuel is full and steady.
3 Stop the flow by shutting off the nozzle, but keep the pump running.
4 Reset the batch register by means of the reset know
( art No. 51008-2).
5 Dispense at the flow rate which the best accuracy is required at, by using a
calibration container having a capacity not less than 20 litres. Do not reduce
the flow in order to reach the graduated zone of the calibration container.
The right way to do this is to start and stop the flow rate repeatedly until the
required filling is obtained.
6 Compare the indication of the calibration with the one of the meter. If the
indicated value is higher than the real value, loosen the screw
( art No.51008-13) if the indicated value is lower than the real value,
tighten the screw ( art No. 51008-13).
Desc iption
The 51008 mechanical fuel meter has an aluminium body incorporating an inlet and outlet flange and can meter fuel accurately
between 15 and 120L M. Featuring an oscillating plate, the meter incorporates bypasses which enable the meter to be used on
different petroleum based liquids of varying viscosity’s. The meter features rotational inlet/outlet for vertical or horizontal applications.
The meter includes a set of resetable digits that need to be reset to zero before the meter is to be used to record its next batch
reading. The meter can be supplied with a 1”BS (f) filter, an optional extra ( art No. 51008F) or without the filter ( art No. 51008.)
Specifications
7 Repeat the operations 4 to 6 until accuracy is satisfactory.
8 Tighten the plug ( art No. 51008-14) again. The O’Ring ( art No. 51008-11) which the calibration screw is
provided with has the function to avoid accidental loosening of the adjustment screw but does not facilitate
any sealing function.
Visit our website at www.alemlube.com.au Email - inf[email protected]u
Mechanical Fuel Meter 51008
NSW
TEL: (02) 9939 0711
FAX: (02) 9939 0411
QLD/PNG
TEL: (07) 3889 8480
FAX: (07) 3889 8490
VIC/TAS
TEL: (03) 8787 8288
FAX: (03) 8787 8266
WA
TEL: (08) 9209 3066
FAX: (08) 9209 3933
SA/NT
TEL: (08) 8241 7111
FAX: (08) 8241 7011
NZ
TEL: (09) 447 1007
FAX: (09) 447 1008
OWNER’S TECHNICAL MANUAL
51008_51008 20/04/11 2:47 M age 1
PART NO DESCRIPTION ITEM NO PART NO DESCRIPTION
2151008-21BevelPinionshaft
22 51008-22 Cover Sealing Kit
2351008-23BevelPinion
PREM
ITEM NO PART NO DESCRIPTION ITEM NO PART NO DESCRIPTION
gniRO11-8001511etalpemaN1-800151
gniRO21-8001521bonkteseR2-800152
tsujdassapyB31-8001531revoclanretxE3-800153 ing screw
gulpssapyB41-8001541gulP4-800154
rebmahcgnirusaeM51-8001551wercS5-800155
gniRO61-8001561ylbmessareteM6-800156
gnirpSrednilyC71-8001571wercS7-800157
wercS81-8001581revocydoB8-800158
reveLgnivirD91-8001591ydobreteM9-800159
etalPraeG02-8001502gniRO01-8001501
2151008-21BevelPinionshaft
22 51008-22 Cover Sealing Kit
2351008-23BevelPinion
PREM
PART NO DESCRIPTION ITEM NO PART NO DESCRIPTION
2151008-21BevelPinionshaft
22 51008-22 Cover Sealing Kit
2351008-23BevelPinion
PROBLEM REMEDY
Leak from the shaft gasket due to damaged gasket. Remove the gear assembly and replace the O Ring (Part No. 51008-22) and the bush.
Insufficient accuracy due to wrong calibration. Repeat calibration following the instructions on Page 1.
Insufficient accuracy due to soiled or blocked measuring chamber. Clean the measuring chamber with an appropriate cleaning agent.
acoL.diulfehtniriaoteudycaruccatneiciffusnI te and eliminate leaks in the inlet lines.
Reduced flow rate due to a clogged or blocked measuring chamber. Clean the measuring chamber with an appropriate cleaning agent.
Pa ts And D awing B eakdown Fo The 51008
O de ing Spa e Pa ts
arts List – art No. 51008/51008F
T ouble Shooting
2
Visit our website at www.alemlube.com.au Email - inf[email protected]u
NSW
TEL: (02) 9939 0711
FAX: (02) 9939 0411
QLD/PNG
TEL: (07) 3889 8480
FAX: (07) 3889 8490
VIC/TAS
TEL: (03) 8787 8288
FAX: (03) 8787 8266
WA
TEL: (08) 9209 3066
FAX: (08) 9209 3933
SA/NT
TEL: (08) 8241 7111
FAX: (08) 8241 7011
NZ
TEL: (09) 447 1007
FAX: (09) 447 1008
51008_51008 20/04/11 2:47 M age 2

Other Alemlube Measuring Instrument manuals

Alemlube 51008 User manual

Alemlube

Alemlube 51008 User manual

Alemlube 51008P User manual

Alemlube

Alemlube 51008P User manual

Popular Measuring Instrument manuals by other brands

Konica Minolta CM3600D brochure

Konica Minolta

Konica Minolta CM3600D brochure

IFM SM2 00 Series operating instructions

IFM

IFM SM2 00 Series operating instructions

LI-COR LI-600N quick start guide

LI-COR

LI-COR LI-600N quick start guide

Kobold SMV operating instructions

Kobold

Kobold SMV operating instructions

Bahco BDACM1000 user manual

Bahco

Bahco BDACM1000 user manual

Juniper 4VETJ user manual

Juniper

Juniper 4VETJ user manual

Autometers Systems HORIZON HT-35 manual

Autometers Systems

Autometers Systems HORIZON HT-35 manual

HVTest HTHL-200A manual

HVTest

HVTest HTHL-200A manual

Giga-tronics 8650B Series Operation manual

Giga-tronics

Giga-tronics 8650B Series Operation manual

Cybertek OP6031 manual

Cybertek

Cybertek OP6031 manual

dynasonics TFXD Series Operation & maintenance manual

dynasonics

dynasonics TFXD Series Operation & maintenance manual

Cincinnati CL-900 Series manual

Cincinnati

Cincinnati CL-900 Series manual

Circutor CEM-C12c instruction manual

Circutor

Circutor CEM-C12c instruction manual

Klein Tools DTL304 instruction manual

Klein Tools

Klein Tools DTL304 instruction manual

Ashcroft N5500 Installation and maintenance instructions

Ashcroft

Ashcroft N5500 Installation and maintenance instructions

Hanna HI 9835 instruction manual

Hanna

Hanna HI 9835 instruction manual

Agrosta NEMESIS quick start guide

Agrosta

Agrosta NEMESIS quick start guide

Topcon GTS-230 Series instruction manual

Topcon

Topcon GTS-230 Series instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.