4 Technical specifications
This manual highlights unsafe practices and other important information.
Warnings are emphasised by means of special signs. All warnings in the manual are summarised on this page.
Pay special attention to the instructions below in order to avoid severe personal injury or damage to the top unit.
Solenoid valves
0 to 2 solenoid valves in each unit possible.
Type 3/2 port
Air supply 0.15 - 0.7 MPa (1.5-7 bar)
Filtered air, max. particles or dirt 5 µ 5-5 mg/m3
Max. flow 180 l/min
Max. oil content 1mg/m
3
Max. water content 0.88 g/m3-20 oC compressed air
Throughput ø2.5 mm
Air restriction (throttle function) No
Manual hold override Yes
External air tube connection ø6 mm or 1/4". (specify when ordering)
Silencer/filter Connection possible via ø6 mm
(Filter recommended in tropical regions)
Nominal voltage 12 VDC
Nominal power 0.52 W
Allowable voltage fluctuation ±10% of rated voltage
Certificate of conformity KEMA 08 ATEX 0093 X
Inductive sensor
Switching element function NAMUR NC
Nominal voltage: Uo 8 V
Measuring plate not detected 3 mA
Measuring plate detected 1 mA
Indication of switching state: LED, yellow
EMC in accordance with IEC / EN 60947-5-2:2004; NE 21
Standards DIN EN 60947-5-6 (NAMUR)
Certificate of conformity PTB 00 ATEX 2032 X
Materials
Plastic parts Nylon PA6, reinforced, stainless steel fibres
Metal parts Stainless steel and bras
Seals Nitrile (NBR)
Gore vent. membrane PBT plastic
Micro environment demand specifications
Temperature
Working: -10°C to +45°C EN 50020
Storage: -40°C to +85°C IEC 68-2-1/2
Temperature change: -25°C to +70°C IEC 68-2-14
Vibration 10-55 Hz, 0.7 mm IEC 68-2-6
55-500 Hz, 10g
3 x 30 min, 1 octave/min
Drop test IEC 68-2-32
Humidity
Constant humidity: +40°C, 21 days, 93% R.H. IEC 60068-2-78
Cyclic humidity: +15°C/+45°C EN 60068-2-30
12 cycles
(working) 93% R.H.
Protection class IP66 and IP67 EN 60529
Surface resistance <1GΩ(ohm) EN 60079-0
Type of ex protection Ex II 2G/D EEx ia IIC T6 ATEX directive 94/9/EC
7