Alpha ESS Storion-SMILE T10 User manual

V01.25062019
Alpha ESS Co., Ltd.
+86 513 806 068 91
www.alpha-ess.com
JiuHua Road 888, Nantong High-Tech Industrial
Development Zone, Nantong City, 226300
Alpha ESS Suzhou Co., Ltd.
+86 512 6828 7609
www.alpha-ess.com
Level 15,SIPC 158 Wangdun Road SIP Suzhou,
215028
Alpha ESS Europe GmbH
+49 610 3459 1601
www.alpha-ess.de
Paul-Ehrlich-Straße 1a, 63225 Langen, Hessen
Alpha ESS Australia Pty. Ltd.
+61 402 500 520 (Sales)
+61 1300 968 933 (Technical Support)
www.alpha-ess.com.au
Suite 1, Level 1, 530 Botany Road, Alexandria,
NSW, 2015
Alpha ESS Italy S.r.l.
+39 599 239 50
www.alpha-ess.it
Via Loda,17-41013 Castelfranco Emilia(MO)
Alpha ESS Korea Co., Ltd
+82 64 721 2004
2F, 19-4, Nohyeong 11-gil, Jeju-si, Jeju-do,
Republic of Korea
Alpha ESS UK Co., Ltd
Drake House, Long Street, Dursley, gl11 4hh
INSTALLATIONMANUAL
ENERGYSTORAGESYSTEM(ESS)
STORION-SMILE-T10(INDOOR)
INSTALLATION MANUAL
ENERGY STORAGE SYSTEM (ESS)
STORION-SMILE-T10 (OUTDOOR)

CONTENTS
INTRODUCTION
01
INSTALLATION
02
01
03
04
06
06
07
08
09
10
10
11
12
17
24
24
28
29
31
31
32
33
36
37
39
39
40
40
01
10
31
32
38
SYSTEM OPERATION
03
42
EMS INTRODUCTION AND SET UP
04
SYSTEM REGISTRATION
05
ON-LINE MONITORING
06
ANNEX
07
1.1 SYSTEM INTRODUCTION
1.2 GENERAL PRECAUTIONS
1.3 PARTS LIST
1.4 SYSTEM APPEARANCE
1.4.1 Battery
1.4.2 HV50056
1.4.3 Inverter Cable Box
1.5 LIABILITY LIMITATION
2.1 INSTALLATION SITE AND ENVIRONMENT
2.1.1 General
2.1.2 Restricted Locations
2.2 INSTALLATION
2.3 WIRING
2.4 POWER METER
2.4.1 Meter ADL-3000 (If Applicable)
2.4.2 ACR10R Meter (If Applicable)
2.4.3 Meter setting
3.1 SWITCH ON
3.2 SWITCH OFF
4.1 FUNCTION DESCRIPTION
4.2 SETTING
4.3 EMS COMMUNICATION CHECKING
4.4 ASSEMBLING OF THE FRONT PANELS
5.1 SYSTEM SETUP IN MONITORING
5.1.1 BASIC INFORMATION
5.1.2 OTHER INFORMATION
6.1 ACCOUNT REGISTRATION
7.1 DATASHEET – ALPHAESS STORION-SMILE-T10
V01 25062019
New
This manual is under the copyright of Alpha ESS Co., Ltd, with all rights reserved. Please keep
the manual properly and operate in strict accordance with all safety and operating instruc-
tions in this manual. Please do not operate the system before reading through the manual.
Copyright Statement
Version Information
Version Date Content

1.1 System Introduction
INTRODUCTION01
INTRODUCTION INTRODUCTION
AlphaESS Storion-SMILE-T10 (incl. M4856-S, HV50056 and SMILE-T10-INV) can be
applied in DC-coupled systems (mostly new installation), AC-coupled systems (mostly
retrofit) and Hybrid-coupled systems (mostly retrofit, and PV capacity-increase), as the
following scheme:
Figure 1 DC-coupled Storage System – Scheme
Monitoring
Device
PV
PV
Alpha
Cloud
LAN
Normal Loads
GridGrid Meter
Critical Loads
Storion-SMILE-T10
Figure 2 AC-coupled Storage System – Scheme Figure 4 AC-coupled Storage System – Scheme, Germany >10 kWp
Monitoring
Device
Alpha
Cloud
LAN
Normal Loads
GridGrid Meter
Critical Loads
Storion-SMILE-T10
Grid MeterPV Inverter
PV Inverter
PV
Monitoring
Device
Alpha
Cloud
LAN
Normal Loads
GridGrid Meter
Critical Loads
Storion-SMILE-T10
Z1 of Grid
Company
Grid Meter
Z2 of Grid
Company
PV
PV
Figure 3 Hybrid-coupled Storage System – Scheme
Monitoring
Device
Alpha
Cloud
LAN
Normal Loads
GridGrid Meter
Critical Loads
Storion-SMILE-T10
Grid Meter
PV Inverter
CAUTION:
For the AC-/ Hybrid-coupled system, unlike DC, two power meters are to be mounted.
In Germany some federal states require that only AC solutions be used if more than 10 kWp
capacity of PV is installed, the meters of grid company must be also installed in the system as
the following figure shows
01 0201 02

1.2 General Precautions
1.3 Parts List
Check the following parts list to ensure it is complete.
AlphaESS delivers a total system separately on site to client, this consists of:
INTRODUCTION INTRODUCTION
DANGER
CAUTION:
SMILE-T10_INV
Danger to life due to high voltages of the PV array, battery and electric shock.
When exposed to sunlight, the PV array generates dangerous DC voltage which will be
present in the DC conductors and the live components of the inverter. Touching the DC
conductors or the live components can lead to lethal electric shocks. If you disconnect the DC
connectors from the system under load, an electric arc may occur leading to electric shock
and burns.
Do not touch uninsulated cable ends.
Do not touch the DC conductors.
Do not open the inverter and battery.
Do not wipe the system with damp cloth.
Have the system installed and commissioned by qualified people with the appropriate skills
only.
Prior to performing any work on the inverter or the battery pack, disconnect the inverter
from all voltage sources as described in this document.
Risk of injury through lifting or dropping the system.
The inverter and battery are heavy. There is risk of injury if the inverter or battery is lifted
incorrectly or dropped during transport or when attaching to or removing from the wall.
Lifting and transporting of the inverter and battery must be carried out by more than 1
person.
WARNING
Risk of chemical burns from electrolyte or toxic gases.
During standard operation, no electrolyte shall leak from the battery pack and no toxic gases
shall form. Despite careful construction, if the Battery Pack is damaged or a fault occurs, it is
possible that electrolyte may be leaked or toxic gases formed.
Do not install the system in any environment of temperature below -10°C or over 50°C and
in which humidity is over 85%.
Do not touch the system with wet hands.
Do not put any heavy objects on top of the system.
Do not damage the system with sharp objects.
Do not install or operate the system in potentially explosive atmospheres or areas of high
humidity.
Do not mount the inverter and the battery pack in areas containing highly flammable
materials or gases.
If moisture has penetrated the system (e.g. due to a damaged enclosure), do not install or
operate the system.
Do not move the system when it is already connected with battery modules.
Secure the system to prevent tipping with restraining straps in your vehicle.
The transportation of AlphaESS Storion-SMILE-T10 must be made by the manufacturer or
an instructed personal. These instructions shall be recorded and repeated.
A certified ABC fire extinguisher with minimum capacity of 2kg must be carried along when
transporting.
It is totally prohibited to smoke in or close to the vehicle when loading and unloading.
For the exchange of a battery module, please request for new hazardous goods packaging
if needed, pack it and let it be picked up by the suppliers.
In case of contact with electrolyte, rinse the affected areas immediately with water and
consult a doctor without delay.
T10-INV box (X1)
Communication
cable (X1)
BAT-BAT
Communication
cable (X1)
Screw package:
Expansion tube (X8)
Expansion screw (X8)
Battery connector:
Positive-Negative
power line (X1)
AC terminal (X12) Cable tie (X30)
Cable bond (X1) Hexagon nuts
with flange (X2)
DC connectors:
Positive X3,
nega-tive X3
Bracket A (X1)
Bracket B (X1) AC auxiliary
power cable (X1)
3-phasig Meter (X1):
ADL3000 or ACR10R
Installation
Manual (X1)
03 04
SMILE-T10_INV

1.4 System Appearance
1.4.1 Battery
1.4.1.1 Specifications
Figure 5 Storion-SMILE-T10 Delivery Scope
Figure 6 M4856 Inteface Definition
1
2
3
4
5
M4856-S
HV50056
INTRODUCTION
1
2
3 4
5
Battery pack (X1)
Bracket (X2)
PE Protective
bag (X1) Screw M5*10(X4)
Screw package:
Expansion tube (X4)
Expansion screw (X4)
Gasket (X4)
Battery connector:
Black power line (X1)
Battery
communication
line (X1)
Hexagon nuts
with flange (X4) Cable tie (X6)
HV50056 box (X1)
Terminal
resistance (X1)
RJ45 Connectors
(X12)
Screw package:
Expansion tube (X5)
Expansion screw (X5)
Battery power cables:
Positive power cable (X1)
Negative power cable (X1)
Communication
cable (X1)
BAT-HV
Cable bond (X1)
Hexagon nuts
with flange (X4)
User Manual (X1):
M4856-S & HV50056
Quick Installation
Manual (X1):
M4856-S & HV50056
Object Description
1
2
3
4
5
6
Hybrid Inverter with Cable Box
HV50056 (High-voltage Control Box)
M4856-S (BAT1)
M4856-S (BAT2)
M4856-S (BAT3)
M4856-S (BAT4)
Object Description
1
2
3
4
5
Positive Pole
Negative Pole
2 x COM Port (CAN)
Dip Switch
LED
INTRODUCTION 05 06
HV50056
M4856-S

1.4.1.2 LED Display
1.4.2 HV50056
1.4.2.1 Specifications
Figure 9 High-voltage Control Box – Front View, Inside
Figure 10 High-voltage Control Box – Top View
In normal condition, LED display three status:
INTRODUCTION
Figure 7 High-voltage Control Box – Left & Right View
Figure 8 High-voltage Control Box – Front View
1
3
2
12
10
9
14 15
18
19
20
11
13
16
4
5
6
7
8
17
Status Normal Protection Fault
LED Display Green light
blinks for 1 sec
Red light
blinks for 1 sec
Red and green
lights blink for
1 sec
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
No. Description DescriptionNo.
External LCD Wiring Port
SD Card
Dip Switch
Dry Contact
LMU COM Port (CAN)
BMU COM Port (CAN)
COM Port Reserved
LAN COM Port
INV + / INV -
Earthing Point X 2 (Required to connect
with grounding copper)
AC Auxiliary Input
Bat+
Bat-
Molded Case Circuit Breaker (MCCB)
AC Switch (For AC Auxiliary Input)
LCD Screen
LED Indicator
External Dispatch COM Port
EMS Meter Communication Port
INV COM Port
INTRODUCTION 07 08

Figure 11 Inverter (DE)
Figure 8 Inverter (AU)
INSTALLATION
1.4.3 Inverter Cable Box
1 2 3 4 5
6
7
1 2 3 4 5
6
7
8
Item Description (DE)
1
2
3
4
5
6
7
8
DC Switch
PV2
PV1
Battery +/-
EMS COM port
On-Grid Wiring Ports
Back Up Wiring Ports
Earthing Point X 2 (Required To Connect With Grounding Copper)
Object Description (AU)
1
2
3
4
5
6
7
8
PV1
PV2
PV3
Battery +/-
EMS COM port
On-Grid Wiring Ports
Back Up Wiring Ports
Earthing Point X 2 (Required To Connect With Grounding Copper)
1.5 Liability Limitation
2.1 Installation Site and Environment
2.1.1 General
Any product damage or property loss caused by the following conditions AlphaESS
does not assume any direct or indirect liability.
This Manual introduces the basic steps on how to install and set up Alpha ESS
Storion-SMILE-T10
M4856-S is a sealed component with no access to battery terminals or cell components
within module.
• Product modified, design changed or parts replaced without AlphaESS authoriza-
tion;
• Changes, or attempted repairs and erasing of series number or seals by non
AlphaESS technician;
• System design and installation are not in compliance with standards and regula-
tions;
• Failure to comply with the local safety regulations (VDE for DE, SAA for AU);
• Transport damage (including painting scratch caused by rubbing inside packaging
during shipping). A claim should be made directly to shipping or insurance company
in this case as soon as the container/packaging is unloaded and such damage is
identified;
• Failure to follow any/all of the user manual, the installation guide and the mainte-
nance regulations;
• Improper use or misuse of the device;
• Insufficient ventilation of the device;
• The maintenance procedures relating to the product have not been followed to an
acceptable standard;
• Force majeure (violent or stormy weather, lightning, overvoltage, fire etc.);
• Damages caused by any external factors.
INSTALLATION02
he M4856-S has two versions, one is indoor, and another is outdoor. The SMILE-T10
energy storage system (indoor version) can only be installed in an indoor location. The
SMILE-T10 energy storage system (outdoor version) can be installed in an outdoor or an
indoor location.
The SMILE-T10 systems should be installed in a room, where access to SMILE-T10 is not
obstructed by the structure of the building, fixtures and fittings within the room.
The SMILE-T10 adopts to natural ventilation. The location should be clean, dry and
adequately ventilated. The room’s entry doors and panels shall open in the direction of
egress and allow unobstructed access to the SMILE-T10 for installation and maintenance
purposes.
NOTE: please pay attention to unpacking the battery, the worst case is that some
components could be damaged.
INTRODUCTION 09 10

2.1.2 Restricted Locations
2.2 Installation
Figure 13 Unpacking the Battery
Figure 12 Removing Front Panel
Figure 12 Distancelimit of Installation to Neighboring Objects
Where the SMILE-T10 is located on or within 300mm of the wall or structure separat-
ing it from the habitable room, the barrier shall extend —
Please refer to Figure 9
(i) 1000 mm beyond the vertical sides of the SMILE-T10;
(ii) 300 mm above the SMILE-T10; and
(iii) To the extent of the bottom of the SMILE-T10.
The following location are not allowed for installation:
• habitable rooms;
• in ceiling spaces;
• wall cavities;
• on roofs not specifically deemed suitable;
• areas of access/egress;
• under stairways;
• under access walkways;
• sites where the freezing point is reached, like garages, carports or other places;
• sites with humidity and condensation over 85%;
• sites which are salty and where humid air can penetrate;
• earthquake areas –additional security measures are required here;
• sites that are higher than 3000 meters above the sea level;
• sites with explosive atmosphere;
• sites with direct sunlight;
• sites with extreme change of ambient temperature;
• wet rooms;
• sites with highly flammable materials or gases; or
• sites with a potentially explosive atmosphere;
Step 1 Take out the battery from the packaging box.
Step 2 Pull the buckle from the bottom right in the middle and pull the top two guide rods
to remove the front panel.
INSTALLATION INSTALLATION
NOTE: the packaging box must be placed in accordance with the marked direction, the
upward carton, unpacking in the other direction is wrong.
Where the top of the SMILE-T10 is within 300 mm of the ceiling or structure above the
SMILE-T10, the ceiling or structure surface shall be suitably non-combustible for an
area of 600 mm past the extremities of the SMILE-T10.
Where more than 4 batteries are installed, some batteries shall be installed beside,
distance between two rows batteries shall be not less than 100 mm
SMILE-T10 shall be mounted with the highest point no greater than 2.2 m above the
floor or platform.
11 12

Figure 15 Assembling Battery Brackets
Figure 17 Mounting Battery
Figure 18 Unpacking the High-voltage Control Box
Figure 16 Placing Battery
Step 3 Use a screwdriver to assemble the battery mounting bracket onto the outside of the
battery, as Figure 12 shows.
Step 5 Insert the expansion tube into the drilled hole. Pass the expansion screw through the
gasket and lock with a screwdriver, as Figure 14 shows.
M4856-S is stackable with maximum of 4 batteries in each row. To install another battery repeat
Steps 1~5
Step 6 Take the HV50056 out of the packaging box. Pull out the top two guide rods and remove
the front panel. Remove the rear bracket from the HV50056, as shown in Figure 17.
Step 4 Confirm the installation place at first.
Push the battery against the wall and confirm the location of the battery with a horizontal ruler.
Place the PE bag on the battery to block out the dust before drilling.
Please drill four holes (two on each side) directly on the wall at the marking positions of the
brackets with an impact drill (bit φ 8.0mm, length 20cm), and the depth of each hole should be
about 7 cm.
INSTALLATION INSTALLATION
13 14

Figure 19 Fixing the Rear Bracket of HV50056
Figure 21 Installation of the Bracket A of the Inverter
Figure 22 Installation of the HV50056 and the Inverter
Figure 20 Fixing of the Rear Bracket of HV50056
Step 7 Fix the HV50056 rear bracket as shown in Figure 16.
1 Find the positioning point and mark it.
2 Use the impact drill (drill φ10.0mm, length 20cm) to directly drill the hole in the marking position
of HV50056 rear bracket, the depth of the drilled hole should be 7cm.
3After the drilling is completed, insert the expansion tube into the drilled hole, and fix the rear
bracket with a 10mm self-tapping screw by using 10MM sleeve (SW10).
4Fix the HV50056 box rear bracket with the flange nut and use a 7MM sleeve on the two L-shaped
brackets of the battery (SW7).
Step 9 Fix the inverter B bracket as shown in Figure 19.
1 Find the positioning point and mark it.
2 Use the impact drill (drill φ10.0mm, length 20cm) to directly drill the hole in the marking position,
the depth of the hole is about 7cm.
3After the drilling is completed, insert the expansion tube into the drilled hole, and fix the bracket
B with a 10mm self-tapping screw by using 10MM sleeve (SW10).
4Fix bracket B with the flange nut and use a 7MM sleeve on the two L-shaped brackets of the
battery (SW7).
Step 8 Fix the bracket A of the inverter on the rear bracket of HV50056 with the flange nuts, as
shown in Figure 18.
The bottom of the bracket A shall be placed at the same horizontal line with the rear bracket of
HV50056.
INSTALLATION INSTRUCTIONS
INSTALLATION
NOTE: Place the PE bag on the battery to block out the dust before drilling.
15 16
Hanging Position for the Inverter
Hanging positions for the HV50056

2.3 Wiring
Figure 23 Connection of Power Cables on Battery Side
Figure 24 Battery Power Cable
Figure 27 Communication Cables
Figure 25 Power Cable Plug Connectors
Figure 26 Connection of Communication Cables on Battery Side
Step 10 Please hang the HV50056 on the rear bracket of HV50056 and hang the SMILE-T10-INV
on the bracket B of the inverter. Fix them with screws.
Step 1 Before wiring please remove the front maintenance baffle of the batteries with a
cross screwdriver.
Step 2 Please connect the power cables as referred in Figure 21 Step 3 Please connect the communication cables as referred in Figure 24
Battery power cable connection sequence:
Through the waterproof cap→through the sealing ring→through the joint, fixed to the
copper bar with M5 nut inside of the battery.
Battery communication cable connection sequence: the RJ45 connector of the
communication cables shall go through the waterproof cap → through the sealing ring
→through the joint and inserted in to the COM port inside of the battery.
HV50056 & Battery communication cable connection sequence: the RJ45 connec-
tor on one side shall go through the waterproof connector inserted into the COM port
inside the battery which is nearest to HV900112. The RJ45 connector on the other side
shall go through the waterproof cover inserted into the LMU port inside the HV50056.
HV50056 & Battery power cable connection sequence: one side terminal shall go
through the waterproof cap→through the sealing ring→through the joint of the battery, fixed to
the copper bar with M5 nut inside of the battery; The plug connector on the other side shall be
connected to the plug port of the HV50056 with the corresponding color. When a snap sound is
heard, the connection is correct.
Terminal Resistance
INSTALLATION INSTALLATION
17 18

Figure 28 ConnectionofthePowerCablesandACAuxiliaryCable
Figure 29 Connection of the Communication Cables on the Inverter Side
Figure 30 Connection of PV cables
Terminal Resistance: Insert the terminal resistance into the last COM port of the last battery.
Step 4 Please connect one DC power cable from INV+ port on HV50056 to BAT+ port
on SMILE-T10-INV, and another DC power cable from INV- port on HV50056 to BAT-
port on SMILE-T10-INV. One side of the AC auxiliary power cables should be connect-
ed to the AC auxiliary port on HV50056 and another side should be connected to the
distribution box, as shown in Figure 26.
Step 5 Connect the communication cable between HV50056 and the inverter, take
the inverter's own net cable out. First remove the cover, then pass the net cable
through the waterproof cap, sealing ring and connector, connect to the corresponding
port, and then the cover should be fixed back and the waterproof cap should be
tightened, as shown in Figure 27.
INSTALLATION INSTALLATION
NOTE:
1. To remove the waterproof connector, it
shall be rotated counterclockwise according
to the installation procedure.
2. Use a screwdriver to remove the mainte-
nance baffle before wiring.
3. The battery has no circuit breaker for
protection. Please be careful, do not short the
positive and negative terminals during
installation.
4. The waterproof sealing ring needs to be
confirmed that it shall be inserted into the
plastic claw ring during installation.
NOTE: The communication cable can go directly through waterproof sealing ring, there
is no need to make net cable on the spot.
19 20

Figure 31 Connection of AC cables
Figure 32 Earthing Point
Step 6 Connect the PV MC4 connector to the PV ports of the inverter.
Step 7 Remove the AC cable terminal strip cover, crimp the AC cable and connect it to the
corresponding terminal block position, and then fix back the cover, as shown in Figure 30.
Step 8 As shown in Figure 30, the grounding position of the HV50056 and the inverter.
Step 9 DIP switch defines the ID address of each battery in one cluster. Set the DIP switch of the
nearest battery from the HV50056 to the farthest battery in sequence of 1 to N. N is the number of
the batteries, which is min. 4 and max. 8.
Figure 33 DIP Switch Definition
AU
DE
Figure 34 Turning on the Switch
On-Grid (L1/L2/L3/N/PE)
Back-Up (L1/L2/L3/N)
On-Grid (L1/L2/L3/N/PE)
Back-Up (L1/L2/L3/N/PE)
Grounding position of inverter Grounding position of HV50056
INSTALLATION INSTALLATION
NOTE: There should be no same ID number in one cluster.
21 22

2.4 Power Meter
2.4.1 Meter ADL-3000 (If Applicable)
2.4.1.1ADL-3000 (without CT, without meter plug), if applicable:
The power meter should be installed and connected in the distribution box. There are
two kinds of power meters, ADL-3000 and ACR10R, which users can choose from.
ADL-3000: three-phase meter (with or without CT)
ACR10R: three-phase meter with CT
Step 10 After wiring, please open the front cover of HV50056 and turn on the molded case circuit
breaker.
Figure 35 Installation of the front panels
Figure 37 ADL-3000 Connection (without CT, without Meter Plug)
INSTALLATION INSTALLATION
Note: Meter 7, 8 connect the RJ45 3, 6, then RJ45 connect the Meter port on the
control box.
A PV meter will be applied in an
AC/hybrid system.
23 24

2.4.1.2 ADL-3000 (without CT, with meter plug), if applicable:
Figure 38 ADL-3000 Connection (without CT, with Meter Plug)
2.4.1.3 ADL-3000 (with CT, without meter plug), if applicable:
Figure 39 ADL-3000 Connection (with CT, without Meter Plug)
INSTALLATION INSTALLATION
A PV meter will be applied in an
AC/hybrid system.
Note: When connecting CTs, pay attention to the current direction. P1 should be
nearest to the grid or the PV-inverter.
A PV meter will be ap-plied in an
AC/hybrid system.
25 26

2.4.1.4 ADL-3000 (with CT, with meter plug), if applicable:
Figure 40 ADL-3000 Connection (with CT, with Meter Plug)
2.4.2 ACR10R Meter (If Applicable)
Figure 41 ACR10R with CT Connection (without Meter Plug)
INSTALLATION INSTALLATION
Note: When connecting CTs, pay attention to the current direction. P1 should be
nearest to the grid or the PV-inverter.
A PV meter will be applied in an
AC/hybrid system.
Note: When connecting CTs, pay attention to CT arrow directions, please refer to
Figure 41.
A PV meter will be applied in an
AC/hybrid system.
27 28

2.4.3 Meter Setting
2.4.3.1 ADL3000
2.4.3.2 ACR10R
Step 1 The initial interface of the meter
(normal working interface) is as shown
below:
Step 2 Click the “SET” button to enter the
password interface:
Step 1 This is the initial interface of the
meter, click the "Set" button;
Step 2 Click the "SETUP" button;
Step 3 Click the "Enter" button to enter
the following interface and press the up
and down arrow keys to enter the
password 0001;
Step 4 Click the "Enter" button and the
password input is completed.
Step 5 Click the “Enter” button again to
enter the address interface:
Step 6 Click the “Enter” button to enter
the following interface, press the up and
down arrow keys to set the meter address,
the Grid meter (DC, AC and Hybrid system)
address is set to 001, and the PV meter (AC
and Hybrid system) address is set to 002.
Step 7 Click the "Enter" button and the
address setting is completed.
Step 8 Click the “SET” button to enter the
following interface:
Step 9 Click the “SET” button again to
enter the save interface:
Step 10 Click the “Enter” button to enter
the following interface, press the up and
down arrow keys, and set “no” to “YES” to
save the configuration.
Step 11 Click the "Enter" button and the
setting ends.
Step 3 On the password input interface,
the code is "0001", confirm to enter the
setting interface;
Step 4 In the setting interface, select
"Comm" option, enter the communication
setting interface;
INSTALLATION INSTALLATION
29 30

System shall be turned on in the correct sequence to avoid any damage.
System shall be turned off in the correct sequence to avoid any damage.
Figure 42 SMILE-T10 EMS Interface
3.1 Switch On
3.2 Switch Off
4.1 Function Description
Step 1 Turn on the MCCB and the AC switch of HV50056 shows.
Step 2 Turn on the external On-grid AC breaker
Step 3 Turn on the PV switch (DE: PV switch on inverter; AU: external PV switch)
Step 4 If backup load is applied, turn on the external Backup AC breaker
Step 5 Set the communication address and communication baud rate in the commu-
nication setting interface. When the meter is used as the Grid meter (DC, AC/Hybrid
system), the address is set to “005”. When it is used as the PV meter (AC/Hybrid
system), the address is set to “006”. The baud rate is set to 9600;
Step 1 Remove the front panel of the inverter and HV50056
Step 2 If backup load is applied, turn off the Backup AC breaker.
Step 3 Turn off the MCCB of HV50056 and the ac switch on HV50056
Step 4 Turn off the PV switch (DE: PV switch on inverter; AU: external PV switch)
Step 5 Turn off the On-grid AC breaker.
EMS INTRODUCTION AND SET UP04
SYSTEM OPERATION03
ON: Fault
OFF: No Fault
ON: Battery communication is OK
OFF: Battery communication is lost
ON: System works normally
OFF: System is abnormal or warning
ON: System is communicating with server
OFF: System is not communicating with server
A
B
C
D
Fault
Battery
Normal
Internet
Return Button: Escape from current interface or function
Up button: Move cursor to upside or increase value.
Down Button: Move cursor to downside or decrease value.
ENT Button: Confirm the selection.
Display the information of the inverter in this LCD screen.
E
F
G
H
I
Button
Function
LCD Screen
SYSTEM OPERATION
Item Name Status Description
Object Name Description
EMS INTRODUCTION AND SET UP
I
31 32

Figure 43 Password Interface
Figure 45 Function Interface Figure 46 Solar Setting Interface
Figure 44 Setting Menu
Figure 47 Battery Model Interface Figure 48 SOC Calibration Interface
4.2 Setting
Step 1 Click setting and enter the
password.
The installation's password is four-digit
password: 1111, after the password is
correctly entered, you shall be at the main
Setting interface (administrator
permissions).
Step 3 Click Solar to set the Solar relevant
information.
Step 4 Set PV capacity, the total capacity
of PV capacity of T10-INV and PV inverter
(if it is installed).
Step 2 Click Function to enter function
setting.
Step 5 Click the Battery Function and
check battery type M4856-S.
Step 6 Check SOC Calibration function set
No.
Figure 49 CT Meter Option Interface Figure 50 Grid Setting InterfaceInterface
Step 7 Choose CT Meter. If you use CT,
please enter the relevant CT ratio. If you
don’t use CT, please enter the ratio as 1.
Step 8 Click the Grid Function to set up
relevant parameters about the grid.
Figure 51 Max. Feed in rate Setting
InterfaceInterface
Figure 52 System Mode Setting
Interfaceterface
Step 9 Set the Max. Feed in rate value. Step 10 Click Function-System Mode to
set system mode: DC, AC, Hybrid.
Figure 53 Work Mode Setting
Interface
Figure 54 Force Charge Setting Interface
Step 11 Click the mode then set up work
mode.(self-use or force time charge)
Step 12 If you want to use force charge,
set Enable here.
EMS INTRODUCTION AND SET UP EMS INTRODUCTION AND SET UP
33 34

After wiring and EMS setting, check that the status indicators are normal. Then enter
MENU->Status->Communication to check that the communication status of all the
devices are normal.
AC\HYBRID system:
DC system:
Figure 55 Force Charge Start Time
Setting Figure 56 Force Charge End Time Setting
Step 13 Set the charge start time
Step 15 Set the charging cut-off SOC.
Step 14 Set the charging start time
Figure 57 Charging cut SOC Setting Figure 58 Discharging cut SOC Setting
Step 16 Set the discharging cut-off SOC.
Step 17 Click Safety in the setting
menu. Set safety standard.
ARN4105 for Germany, CEI0_21 for Italy,
G83_2 for Great Britain, AS4777 for
Australia
Figure 59 Safety Setting Interface Figure 60 Date&Time Setting Interface
Figure 61 Ethernet interface
Figure 62 Date&Time Setting Interface Figure 63 Date&Time Setting Interface
Step 21 Make sure all the following
number is correct.
Step 20 Click Language to set language
Figure 64 BMS
Figure 66 BMS Figure 67 Ethernet and Meter
Figure 65 Ethernet and Meter
Step 18 Click System in the setting
menu. Click Date &Time and set up the
date and time.
Step 19 Click Ethernet to set the IP
address. DHCP mode means that setup IP
address is set up automatically.
If you want to set up the IP address
manually, please choose manual mode.
4.3 EMS Communication Checking
EMS INTRODUCTION AND SET UP EMS INTRODUCTION AND SET UP
Note: It is needed to set the following 3 parameters for manual mode:
IP Address: IP address;
Subnet Mask: Subnet mask;
Default Gateway: Default gateway;
Automatic display one parameter:
MAC Address: display MAC Address.
35 36
This manual suits for next models
3
Table of contents
Other Alpha ESS Batteries Pack manuals
Popular Batteries Pack manuals by other brands

iTechworld
iTechworld iTECH400X PRO user guide

PowerWalker
PowerWalker LiFe Battery System 102-37 user manual

MasterPower
MasterPower GreenE 3.68K Installation, operation & maintenance manual

CYCMOTOR
CYCMOTOR B Series user manual

GOAL ZERO
GOAL ZERO Guide 10 Plus user guide

CYCMOTOR
CYCMOTOR B Series user manual