- 2 - T2AGK78(D) Installation Guide
Overview:
Altronix T2AGK78 and T2AGK78D Trove AMAG kits are pre-assembled and consist of Trove2AG2 enclosure/backplane with factory installed
Altronix power supply/charger and sub-assemblies. These kits also accommodate up to two (2) AMAG M4000 modules for up to eight (8) doors
in a single enclosure.
Configuration Chart:
Altronix
Model
Number
115VAC
60Hz
Input
Current
(A)
Power
Supply
Board
Input
Fuse
Rating
Power
Supply
Board
Battery
Fuse
Rating
Maximum Supply
Current for Main
Output on
Power Supply board
and ACM8(CB)
Access Power
Controllers’
outputs
Nominal
DC
Output
Voltage
Range
(VDC)
Fail-
Safe/
Fail-
Secure
Outputs
Additional
Fused
Outputs
ACM8 and ACM8CB
Board Input Fuse Rating
ACM8 Board
Output Fuse Rating
ACM8CB Board
Output PTC Rating
PDS8 Board
Input Fuse Rating
PDS8 Board
Output Fuse Rating
PDS8CB Board
Input PTC Rating
PDS8CB Board
Output Fuse Rating
T2AGK78
4.2 5A/
250V
15A/
32V 24VDC @ 9.7A 20.17-
26.4 8 8 10A/
250V
2.5A/
250V –10A/
32V
3A/
32V – –
T2AGK78D 2.5A – – 9A 2.5A
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the
wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position
of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes
over the three upper screws. Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge.
Slide the tamper switch bracket onto the edge of the enclosure, approximately 2” from
the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel
input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Mount AMAG M4000 modules to TAG2 backplane, refer to page 3.
5. Refer to the ULXB Power Supply/Charger Installation Guide for
AL1024ULXB2 and corresponding Sub-Assembly Installation Guides for
the following models: ACM8(CB), PDS8(CB) and VR6 for further installation instructions.
Hardware:
Fig. 1
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Nylon Spacer | 5/16” Pan Head Screw | Lock Nut