American Standard FD145ALUPGRDA Owner's manual

Whole House Air Cleaner Upgrade Kit
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
Installation
Operation
Maintenance
Upflow Furnace
Models
*FD145ALUPGRDA
*FD175ALUPGRDA
*FD210ALUPGRDA
*FD245ALUPGRDA
18-HE56D1-3
▲WARNING
!
This information is for use by individuals having adequate
backgrounds of electrical and mechanical experience. Any
attempt to repair a central air conditioning product may
result in personal injury and/or property damage. The
manufacturer or seller cannot be responsible for the
interpretation of this information, nor can it assume any
liability in connection with its use.
Contents
Installation 2
Location
2
TFE Models Only
3
Enclosure Upgrade
4-7
Electrical Connections 8
Wiring Diagrams
8
Air Cleaner Operation 9
Set-Up Mode 9
PRE-FILTER Setting
9
Collection Cell Setting
10
Power Level Setting
10
Maintenance 10
Cleaning
10
Fuse Replacement
11
Troubleshooting 12
Outline drawings 13-15
Downflow Furnace
Models
*FD14DALUPGRDA
*FD17DALUPGRDA
*FD21DALUPGRDA
*FD24DALUPGRDA
Air Handler
Models
*FD215ALUPGRDA
*FD235ALUPGRDA
*FD260ALUPGRDA
*May be "A" or "T"
▲WARNING
!
RISK OF ELECTRIC SHOCK: These servicing
instructions are for use by qualified personnel only. To
reduce the risk of electric shock, do not perform any
servicing other than that contained in these operating
instructions unless you are qualified to do so.

© 2005 American Standard Inc. All Rights Reserved Pub. No. 18-HE56D1-3
Field Upgrade Guide
2
Air Flow Air Flow
Figure 2. Mounting Location of Air Cleaner
Side Mounting (Furnace Only)
Choose Right or Left Bottom Return All
Air Flow
Figure 3.
Downflow
INSTALLATION, LOCATION & LIMITATIONS
NOTE: Do not install the air filter in the discharge air
stream of either the heating or cooling unit.
This air cleaner cabinet must be mounted in the return air duct of
a central forced-air furnace/air handler.
Select a location that meets the following:
1. The face of the cell must be at a right angle to the air stream.
2. Allow a minimum of 28 inches clearance in front of the air
cleaner to permit removal of cells and pre-filter.
3. Flow-through Bypass Humidifiers
Excessive bypass air may cause water blow-off, which will
adversely affect system operation andAir Cleaner perfor-
mance. To verify bypass airflow, follow the Bypass Humidi-
fier Pre-Installation Checkout and Set-Up Procedures
available through your local distributor. Ask for publication
number 18-CH37D1-1.
4. Steam and Flow-through Fan Power Duct-mounted Hu-
midifiers
Follow the humidifier installation instructions. These
should only be installed on the supply air side of the
system.
UnpacktheAirCleaner andcheck tomake sureall compo-
nents are included. They consist of:
1) PRE-FILTER - traps large particles such as hair and lint
before they can enter the COLLECTION CELL section.
2) FIELD CHARGER - Charges the contaminants
3) COLLECTION CELL (2) - removes and collects small
impurities from the air.
4) Filter Mount Rail (2) - mounts into existing cabinet and is
used to hold the components in place. Rail is also used
to activate the safety power switch.
5) Power Door -the solid state power supply components
that convert the 24 Volt AC to the high-voltage, direct
current required to power the FIELD CHARGER and
COLLECTION CELLS. Allows access to the fluted
COLLECTION CELLS, FIELD CHARGER and PRE-
FILTER.
6) Transformer - supplies 24 Volts to the indoor unit and air
cleaner
7) 24 Volt Power / Control Cable
8) Gasket, Literature and Hardware Packet
9) Template, Screws and Drill Bit Kit - used to mount rails
10) Insulator Film
Check carefully for any shipping damage. This must
be reported to and claims made against the trans-
portation company immediately. Check to be sure
all major components are in the unit. Any missing
parts should be reported to your supplier at once,
and replaced with authorized parts only.
Figure 1. COMPONENTS OF THE
AIR CLEANER UPGRADE KIT
11
11
1
22
22
2
44
44
4
99
99
9
55
55
5
77
77
7
66
66
6
88
88
8
33
33
3
11
11
122
22
233
33
3
00
00
0
33
33
3

Pub. No. 18-HE56D1-3 3
Field Upgrade Guide
NOTE: Do NOT use a silicon base sealant. This causes a
coating on the FIELD CHARGER pins that will decrease the
efficiency of the air cleaner.
Note: Dual Circuited Air Handlers matched with heat pumps
will require an accessory Wall Mounted Transformer KIT #
BAYTRANS12024A to power the air cleaner. Do not replace
air handler transformer with the transformer supplied with
the air cleaner.
TFE Models only - Remove Existing Electrical
Hardware:
Identify the existing air cleaner located in the
return air duct of a central forced-air furnace/air
handler. The air cleaner is typically installed as
shown in Figures 2 or 3 on the previous page.
Furnace and Air Handler – (120VAC models) If the
existing air cleaner is an electronic type Perfect Fit
filter (EAC), switch the POWER button to the
“OFF” position. All furnace applications, and some
air handler applications use 120VAC 3 prong power
cord. This should be unplugged from the electrical
outlet.
Air Handler – (240 VAC models) If the EAC is
internally wired into the air handler, the power cord
and polarized connector adapter will need to be
removed from the air handler system.
1. Disconnect the strain relief connector (see
Figure 4 to the right).
2. Remove the six pin polarized connector on
the adapter located between the female
polarized connector on the heater and the
male polarized connector from the air handler
control box. See Figure 4 to the right.
3. Reconnect the female polarized connector on
the heater and the male polarized connector
from the air handler control box.
4. Disconnect the green ground wire on the plug
adapter from the heater barrier.
5. Seal the knockout used by the previous
power wires.
Strain relief
Disconnect green ground
lead from adapter from the
air handler cabinet ground.
Disconnect plug from heater. If no
accessory heater was installed,
disconnect this plug from the polorized
connector mounted on the electrical
junction box.
Figure 4. TFE wiring
For Non-TFE models, skip the section below and go to the
next page.
CAUTION
!
Do not install air cleaner where the filter can be exposed to
UV light. UV light can cause the plastic material to deterio-
rate, which may lead to filter damage.
5. Other Duct Mounted Humidifiers
Not recommended for installation with the air cleaner.
DO NOT operate the air cleaner during construction of a home.
The air cleaner is designed for use in normal living conditions
to capture small particles. The volume of dust and condensate
in the presence of chlorides and fluorides from paint, varnish,
stains, adhesives, cleaning compounds, and cement creates a
corrosive condition which may cause rapid deterioration of the
cabinet and internal components of the air cleaner and the
heater/furnace.
▲WARNING
!
Disconnect ALL power to the indoor air handler, fur-
nace, and air cleaner. NOTE: There may be more than
one electrical disconnect switch. Electric shock can
cause personal injury or death.

© 2005 American Standard Inc. All Rights Reserved Pub. No. 18-HE56D1-3
Field Upgrade Guide
4
ENCLOSURE UPGRADE
Figure 5 shows the template for drilling the rail
positioning holes. Figure 6 shows a close up of
the label on the installation template. The same
template will be used on both sides of the air
cleaner enclosure.
INSTALLATION OF THE FILTER MOUNT
RAILS
Remove all existing filters and PRE-FILTERs from the
air cleaner enclosure and discard.
DUCT
ALIGNMENT
PIN
FURNACE/AIR HANDLER
TEMPLATE
AIRFLOW
Installation template must be fully seated against front edge, and also against the 1" pre-filter rail for proper installation.
TEMPLATE
Figure 5
Figure 6
Figure 7
Figure 8
1. Identify the back insulator film. Remove the
backing material to expose the adhesive.
2. Center the insulator on the back wall against the
cabinet flange closest to the indoor unit as shown in
Figure 8. Press the insulator film against the back wall
to secure.
NOTE: Clean the back of the existing cabinet to
insure that it is dust free before adhering the new
insulator film.

Pub. No. 18-HE56D1-3 5
Field Upgrade Guide
4. Leaving the template in place to prevent the drill bit
from “walking”, use the provided drill bit to drill two holes
in the air cleaner enclosure. Do not try to mark and then
drill the holes, because the drill bit will have the
tendency to “walk” on the flat sheet metal case. This will
cause the metal rail to be installed incorrectly.
5. Use the provided screws to fasten the rail into place.
The metal tabs on the rails should be facing the front of
the air cleaner enclosure. After installed, one of the tabs
will be flush with the front of the enclosure and the other
will extend past the front edge of the enclosure.
6. With the rail now firmly affixed to the air cleaner
case with two screws, it may be desirable to add an
optional third screw on the rail for extra support. A third
hole is provided for this purpose, as well as a screw.
Use the existing hole located in the center of the rail as
a guide much like the installation template was used
earlier to prevent the drill bit from walking.
Figure 9
Figure 10
Figure 11
3. Identify the installation template from the upgrade kit
packaging. Install the template onto the air cleaner
enclosure as shown in Figure 9.
NOTE: THE TEMPLATE MUST BE PUSHED
TOWARDS THE BACK OF THE AIR CLEANER
ENCLOSURE UNTIL THE FRONT FLANGE OF THE
INSTALLATION TEMPLATE IS FULLY SEATED
AGAINST THE LEADING EDGE ON THE ENCLOSURE.
THE TEMPLATE MUST ALSO BE PUSHED TOWARDS
THE ONE INCH U CHANNEL FILTER RAIL AS SHOWN
IN FIGURE 8. IF THE TEMPLATE IS IMPROPERLY
USED, THE FILTER COMPONENTS WILL NOT FIT
INTO THE AIR CLEANER ENCLOSURE CORRECTLY.
PUSH
PUSH
PUSH
Figure 12

© 2005 American Standard Inc. All Rights Reserved Pub. No. 18-HE56D1-3
Field Upgrade Guide
6
NOTE: The filter mount rails are not installed in
the same orientation. If they are installed the
same way, the screw heads will be in the way of
the filter installation.
9. Secure the second rail into place using the
provided screws. The metal tabs should be facing
the front of the air cleaner enclosure. One of the
tabs should be flush with the front of the enclosure
and the other will extend past the front of the
enclosure.
10. With the rail now firmly affixed to the air
cleaner enclosure with two screws, it may be
desirable to add an optional third screw on this rail
for extra support. A third hole is provided for this
purpose, as well as a screw. Use the existing hole
located in the center of the rail as a guide much
like the installation template was used earlier to
prevent the drill bit from walking.
Figure 13
Figure 14
Figure 15
Figure 16
11. Install the FIELD CHARGER and lock into place by
bending one locking tab on the cabinet. See Fig. 16.
12. Install the PRE-FILTER and COLLECTION CELLS.
13. Each COLLECTION CELL must be oriented with the
handles toward the front.
14. The door can be installed in either direction. Deter-
mine which direction will best allow access to the latches
and 24 volt power cord. Insert the 2 tabs on the door
behind the front cabinet flange and rotate the door into the
closed position. Rotate the two quarter-turn latches on the
Power Door inward.
NOTE: The door has a safety switch to ensure power is
interrupted when the door is removed. This switch is open
when the door is removed from the cabinet. When the door
is properly installed, an actuator tab located in the cabinet
will close the switch, allowing power to the electronics.
Field Charger
Locking Tab
Actuator Tab for
Interlock Switch
7. Move the installation template to the other side
of the air cleaner enclosure. Place the template
onto the enclosure as indicated in Figure 13. The
template must be pushed towards the back of the
air cleaner enclosure until the front flange of the
installation template is fully seated against the
leading edge on the case. The template must also
be pushed towards the one inch U channel filter
rail as shown in Figure 13.
8. Drill two holes, using the template to guide the
drill bit as done previously.

Pub. No. 18-HE56D1-3 7
Field Upgrade Guide
16. Remove Model number / Serial number label from the kit and
place on the bracket as shown in Figures 18 and 19.
Note: Pictured enclosure is not installed on a furnace.
17. Measure and cut the provided gasket to length. Place gasket
material into the two channels located at each side of the
opening as shown in Figure 20. BEFORE INSTALLATION
AFTER INSTALLATION
Place circular foam
disc pads over screw tips
protruding from case.
Repeat on other side
Third screw and foam
sticker - Optional
15. After installing the middle filter mount rails into the existing air
cleaner enclosure with the provided blunt tip screws, it is
necessary to cover the exposed screw tips on the outside of
the cabinet.
Locate the six 1-1/4" foam disc pads from the hardware
packet and apply them over the screw tips on the outside of
the cabinet. This will protect the homeowner from any contact
with these screw tips.
Figure 18
Figure 19
Figure 20
Figure 17

8Pub. No. 18-HE56D1-3
Field Upgrade Guide
Fig. 12
Fig. 13
Plug the air cleaner power/control cable into the air cleaner
door and route the cable into the indoor unit low voltage
wiring location.
NOTE : Provide adequate strain relief for the low voltage
cable at the indoor unit.
NOTE: Wiring penetration must be sealed.
Connect the power/control wiring per Fig. 12.
For non-Trane/ American Standard systems an optional
120 AC to 24 VAC transformer, kit # BAYTRANS12024A
can be used to provide 24 volt power only to the air
cleaner.
Connect the power/control wiring per Fig. 13.
ELECTRICAL CONNECTIONS
The air cleaner requires 24 Volt AC power and indoor fan
signal to operate. A transformer adequately sized to power
both the system and air cleaner is provided with the air
cleaner. Remove the transformer in the indoor unit and
replace with the transformer provided.
NOTE: A 50 VA transformer is required for Trane/
American Standard Furnace applications and 75 VA
required for Trane/ American Standard Air Handler
applications. If the indoor air handler already has a
properly sized transformer, no replacement is required.
WARNING: DO NOT attach the power/ control cable to a
110 Volt EAC tap. The air cleaner uses 24 Volt power.
NOTE: A 50 VA
transformer is required
for Trane/ American
Standard Furnace
applications and 75 VA
required for Trane/
American Standard Air
Handler applications. If
the indoor air handler
already has a properly
sized transformer, no
replacement is required.
BAYTRANS12024A Transformer
INTERNAL TRANSFORMER WIRING DIAGRAM
•Transformer must have a
grounded 120VAC power source.
Do not defeat ground plug on the
transformer.
•Mount transformer to building
structure with the four provided
wood screws.
NOTE: The Black wire
must be connected to
chassisground to ensure
proper operation.
Air handler may not have a Low Voltage Terminal board.
Connect Electronic Air Cleaner wires to the Air Handler
Low Voltage Color coded wired.
Install Transformer, one is supplied with the Electronic Air
Cleaner, in the furnace or Air Handler.

Pub. No. 18-HE56D1-3 9
Field Upgrade Guide
DISPLAY FEATURES (Fig. 14)
The air cleaner display can be used for several functions:
• Provide the homeowner the operating status of the air
cleaner, including an indication the PRE-FILTER or
COLLECTION CELLS need cleaning.
• The installer accesses the Set-Up Mode to change the
time to clean settings for the PRE-FILTER and
COLLECTION CELLS as well as change the power level
setting.
• The unit will display fault codes for the homeowner
indicating there is a problem with the air cleaner and
various fault codes for the service technician to assist in
troubleshooting the problem.
AIR CLEANER OPERATION
Turn the air cleaner on by pushing the POWER button. The
backlit POWER and Filter RESET buttons will illuminate
along with the first green LED (G1) indicating 24 volt power
is present to the air cleaner.
When the indoor fan is operating the first LED (G1) will
slowly flash. This indicates the FIELD CHARGER and
COLLECTION CELLS have power and the unit is operating
normally. There is a slight time delay between the indoor fan
starting and LED (G1) flashing.
In normal operation, the air cleaner makes a slight sound as
the air passes through it and is cleaned. In some
applications, you may notice this sound coming from the
return air vent(s). If desired, this sound level can be
reduced with minimal impact on air cleaning efficiency by
reducing the power setting of the FIELD CHARGER in the
Set-Up Mode, see page 8.
NOTE: There is a 10 minute delay after the indoor fan
operates, before the air cleaner starts to operate, each
time the power to the air cleaner is turned off/on. This can
be bypassed by going into and then out of the Set-Up
mode
SET-UP MODE
A combination of RED, YELLOW, and GREEN LED's are
used to indicate the following settings.
• The three GREEN LED's are used to indicate PRE-FILTER
cleaning interval. This is measured in actual run time of the
indoor fan. The default setting is 2 months.
• The four YELLOW LED's indicate the collection cell
cleaning interval. This is measured in actual run time of the
indoor fan. The default setting is 6 months.
• The three RED LED's indicate the power level setting. The
default is maximum.
SET-UP MODE OF OPERATION
To enter the Set-Up Mode press and hold both the POWER
and RESET buttons for a minimum of 5 seconds. The current
settings are then displayed. See Fig. 15 If this is the desired
setting or at any time you want to exit the Set-Up mode,
press and hold BOTH the POWER and RESET buttons for a
minimum of 5 seconds to exit.
Fig. 15. Factory settings
G1
G2
G3
Y1
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
To change any of the settings, press the POWER button
once.
PRE-FILTER SETTING (Fig. 16)
One or more of the GREEN LED’s will come on indicating
the PRE-FILTER cleaning time setting. Repeatedly press the
RESET button to cycle through the time options for the PRE-
FILTER cleaning cycle until the desired setting is displayed.
Press the POWER button once to accept that setting and
move to the cell cleaning settings.
FIG. 16 GREEN LED PRE-FILTER SETTINGS
1 Month 2 Months* 3 Months
G1
G2
G3
Y1
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
G1
G2
G3
Y1
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
G1
G2
G3
Y1
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
* Factory Setting
Figure 14. LED Display

10 Pub. No. 18-HE56D1-3
Field Upgrade Guide
CELL CLEANING SETTING (Fig. 17)
One or more of the YELLOW LED’s will come on indicating
the COLLECTION CELL cleaning time setting. Repeatedly
press the RESET button to cycle through the time options for
the COLLECTION CELLS cleaning cycle until the desired
setting is displayed. Press the POWER button once to accept
that setting and move to the power settings.
Fig. 17 YELLOW LED COLLECTION CELL SETTING
2 Month 4 Months 6 Months* 9 Months
G1
G2
G3
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
G1
G2
G3
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
Y1
G1
G2
G3
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
Y1 Y1
G1
G2
G3
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
Y1
*Factory Setting
FIELD CHARGER POWER LEVEL
The RED LED lights are used to set the power level of the
FIELD CHARGER for maximum, medium, or minimum. The
number of illuminated RED LED lights indicates the current
setting. The factory setting is for maximum.
Lower settings will reduce the slight sound emitted by the
unit with minimal loss of air cleaning efficiency, if desired.
Lower settings will also further reduce the very low ozone
produced by the air cleaner. The U.S. Food and Drug
Administration recommends indoor ozone concentrations
should not exceed 50 parts per billion. Your air cleaner will
contribute only 5 parts per billion at the factory setting and
can be reduced to 3 parts per billion at the minimum setting.
FIELD CHARGER POWER LEVEL SETTINGS
One or more of the RED LED lights will illuminate. To
change the power level setting, press the RESET button
until the desired setting is indicated.
To save your new settings and exit the Set-Up mode, press
and hold BOTH the POWER and filter RESET buttons for a
minimum of 5 seconds.
Fig. 18 RED LED POWER LEVEL SETTINGS
Minimum Medium Maximum*
G1
G2
G3
Y1
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
G1
G2
G3
Y1
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
G1
G2
G3
Y1
Y3
Y4
R1
R2
R3
Y2
CLEAN
DIRTY
*Factory Setting
MAINTENANCE
For maximum efficiency the COLLECTION CELLS and PRE-
FILTER should be inspected and cleaned on a regular basis.
The FIELD CHARGER should only be removed and cleaned
annually by an authorized service professional.
CAUTION
!
High Voltage is present within the air cleaner for operation.
Beforeremovingthedoor,turnthepoweroffandwaitatleast
15 seconds to allow voltage to discharge.
NOTE: Before cleaning the coil or ducts in the air handler
or furnace, remove the COLLECTION CELLS, FIELD
CHARGER, and PRE-FILTER from the air cleaner.
Chemicals used during the cleaning of the air handler,
furnace, or ductwork can damage the air cleaner
components and degrade the performance of the air
cleaner.
CLEANING
1. Turn the air conditioning system off at the thermostat.
2. Turn off power to the air cleaner by pushing and holding the
POWERbuttonforthreeseconds. TheLED'swillremainon
until the voltage has discharged and it is safe to remove the
door. This requires approximately 15 seconds. Do not
remove the door until all lights are off.
3. Disconnect the power/control cable if required to place the
door in a secure location.
PRE-FILTER CLEANING
The PRE-FILTER can be vacuumed or washed to clean. The
PRE-FILTER should be completely dry before re-installing.
NOTE: Do not replace the plastic PRE-FILTER with a metal
type PRE-FILTER. A metal PRE-FILTER will cause
reduction in efficiency and potential failure of the
electronics in the air cleaner
COLLECTION CELL CLEANING
The COLLECTION CELLS can be cleaned either by
vacuuming (recommended method) or by washing.
VACUUM CLEANING
Vacuum both sides of the COLLECTION CELLS to clean.
WASHING
Use low-pressure water spray, such as a sink sprayer or
garden hose to clean the cells. Some residue may require
warm water to be removed.
• DO NOT USE SOAP OR DETERGENT IN CLEANING THE
COLLECTION CELLS.
• DO NOT IMMERSE THE CELLS COMPLETELY IN WATER.
• DO NOT PLACE THE CELLS INTO A DISHWASHER TO
CLEAN
.
Slightly tap the COLLECTION CELLS to remove water
retained in the filter. Allow the COLLECTION CELLS to dry
before re-installing.

Pub. No. 18-HE56D1-3 11
Field Upgrade Guide
Re-install the PRE-FILTER and COLLECTION CELLS. Be
sure to fold the collection cell handles flat. Install the door
and plug in the power/control cable if removed. Turn on
power to the air cleaner.
NOTE: The first green LED will be on but will not flash for
the first 10 minutes the indoor fan is operating. This is a
drying cycle for the PRE-FILTER and COLLECTION CELLS
RESET TIMERS
To reset the PRE-FILTER timer, press and hold the RESET
button until the PRE-FILTER LED turns off. (1 to 2 seconds)
To reset the collection cell timer, press and hold the RESET
button until the collection cell LED’s turn off. (4 to 5 seconds)
FAULT CODES
The air cleaner LED’s will display a fault indication, three
yellow or three red LED’s, when a fault has been detected. A
log of the last three faults is recorded and can be accessed
by going into the Set-Up mode. The unit will repetitively
check the system to determine if the fault persists. The fault
indication will be displayed as long as the fault condition
remains.
If the fault is no longer present, the system will return to
normal operation and no longer display the fault indication.
Even if the fault has been cleared, a log of the last 3 faults is
recorded.
REPETITIVE ARC FAULT INDICATION
If the unit detects 10 consecutive run cycles where an arc
occurs during the cycle, it will go into a lock out period for
one hour. This is indicated by three FLASHING YELLOW
LED’s. The PRE-FILTER and COLLECTION CELLS should
be cleaned to ensure no large material is trapped in the
filters and causing the fault. Check the FIELD CHARGER for
material that can cause the fault.
If the unit detects any other type of fault, this will be indicated
by three FLASHING RED LED’s. See the Service Facts for
fault code information.
FUSE REPLACEMENT
A fuse, located inside the Power Door, protects the power
supply components against damaging electrical currents.
This fuse has a rating of 3 amps and is a Purple color
automobile style fuse.
TO CHECK OR REPLACE THE FUSE
Disconnect the power cord from the front of the power pack
door. On the inside of the door remove the screws along the
outer edge to separate the metal door from the plastic cover.
The Purple Colored 3 amp fuse is located on the main printed
circuit board. Replace the fuse if blown and reassemble the
Power Door.
NOTE: When reassembling the inner panel to thePower
Door, ensure that the wiring is positioned to avoid interfer-
ence.
Re-install the door on the cabinet, plug in the power/control
cable and check for proper operation of the electronic air
cleaner.
The other electrical components inside the Power Door are
not field replaceable, the Power Door is available as a
complete assembly from your distributor.
FUSE
Fig. 19

12 Pub. No. 18-HE56D1-3
Field Upgrade Guide
Fig. 20
TROUBLESHOOTING
Service Indications Service Checks
Indoor Blower ON/ 1. Check that the Power Door is installed correctly
and the latche is closed. The actuator tab must
en
g
a
g
ed the door safet
y
switch.
2. Check the air cleaner power/control cable.
3. Push the power button once. Button back light should be on
4. Check for 24 Volts AC at the Air Cleaner Power
plug. A Yellow LED on the door by the air cleaner
plug should turn on for one second then turn off
immediately after 24VAC power is applied to the unit.
5. Check the Fuse inside the Power Door.
Indoor Blower ON/
Air Cleaner First
Green LED ON, Not Flashing 1. Air Cleaner is in the 10 minute DRY CYCLE.
2. No call for Air Cleaner operation due to no 24 volts
AC call going to G or W from the Furnace or Air
Handler
3. There is no High Voltage being provided to the
FIELD CHARGER or the COLLECTION CELLS.
Inspect the FIELD CHARGER assembly and
COLLECTION CELLS for any foreign material that
may be lodged in them. Clean as needed,
reassemble and test.
4. If the Air Cleaner still does nto work, remove Power
Door from the Air Cleaner Housing.
CAUTION HIGH VOLTAGE WILL BE
PRESENT FOR THE REMAINDER OF
THIS TEST.
5. With the indoor blower running and the power cord
plu
gg
ed into the Air Cleaner, use a tool to activate the
Power Door interlock switch. Push the power button
once. The first green LED should come on and after
the time delay it should start to flash.
If the first Green LED does not start to flash the fault
is with the Power Door.
Indoor Blower ON/ Four Yellow 1. Remove the Power Door, FIELD CHARGER &
LEDs Flashing COLLECTION CELLS. Inspect for foreign
material, clean if needed.
Indoor Blower ON 1. This indicates service is needed.
three Red LEDs Flashing See Service Facts for fault code information.
Air Cleaner First Green
LED OFF

Pub. No. 18-HE56D1-3 13
Field Upgrade Guide
UPFLOW FURNACE MODEL NUMBERS
ifD Air Cleaner A B
*FD145ALFR000A
*FD145ALUPGRDA 14.5 12.38
*FD175ALFR000A
*FD175ALUPGRDA 17.5 15.38
*FD210ALFR000A
*FD210ALUPGRDA 21.0 18.88
*FD245ALFR000A
*FD245ALUPGRDA 24.5 22.38
* May be "A" or "T"
OUTLINE DRAWING FOR UPFLOW FURNACES
2.8”
27” DEPTH CABINET
ADD DOOR DEPTH FOR TOTAL
Dimensions
7-7/16
1/8
1/8
A
B
27
24-13/16
Front
of
Cabinet
Side View

14 Pub. No. 18-HE56D1-3
Field Upgrade Guide
DOWNFLOW FURNACE MODEL NUMBERS
ifD Air Cleaner A B
*FD14DALFR000A
*FD14DALUPGRDA 14.5 12.38
*FD17DALFR000A
*FD17DALUPGRDA 17.5 15.38
*FD21DALFR000A
*FD21DALUPGRDA 21.0 18.88
*FD24DALFR000A
*FD24DALUPGRDA 24.5 22.38
* May be "A" or "T"
OUTLINE DRAWING FOR DOWNFLOW FURNACES
2.8”
21” CABINET DEPTH
ADD DOOR DEPTH FOR TOTAL
Dimensions
7-7/16
1/8
1/8
A
B
21
18-13/16
Front
of
Cabinet
Side View

Pub. No. 18-HE56D1-3 15
Field Upgrade Guide
OUTLINE DRAWING FOR AIR HANDLERS
2.8”
AIR HANDLER MODEL NUMBERS
ifD Air Cleaner A B
*FD215ALAH000A
*FD215ALUPGRDA 21.5 19.38
*FD235ALAH000A
*FD235ALUPGRDA 23.5 21.38
*FD260ALAH000A
*FD260ALUPGRDA 26.0 23.88
* May be "A" or "T"
21.0
18.88
21” DEPTH CABINET
ADD DOOR DEPTH FOR TOTAL
Front
of
Cabinet
Side View

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right
to change design and specifications without notice.
AmericanStandardInc.
6200TroupHighway
Tyler,TX75707
Formore information contact
your local dealer (distributor)
Field Retrofit Guide
Notes
400 CFM 600 CFM 800 CFM 1000 CFM 1200 CFM 1400 CFM 1600 CFM 1800 CFM 2000 CFM
*FD145ALFR000A
*FD145ALUPGRDA 0.04 0.09 0.14 0.20 0.27
*FD175ALFR000A
*FD175ALUPGRDA 0.03 0.06 0.10 0.14 0.19 0.24 0.30
*FD210ALFR000A
*FD210ALUPGRDA 0.02 0.04 0.07 0.10 0.13 0.17 0.21 0.26 0.31
*FD245ALFR000A
*FD245ALUPGRDA 0.01 0.03 0.05 0.07 0.10 0.13 0.16 0.19 0.23
*FD14DALFR000A
*FD14DALUPGRDA 0.07 0.14 0.22 0.32 0.44
*FD17DALFR000A
*FD17DALUPGRDA 0.05 0.09 0.15 0.22 0.30 0.39 0.49
*FD21DALFR000A
*FD21DALUPGRDA 0.03 0.07 0.11 0.15 0.21 0.27 0.34 0.42 0.50
*FD24DALFR000A
*FD24DALUPGRDA 0.02 0.05 0.08 0.12 0.16 0.20 0.25 0.31 0.37
*FD215ALAH000A
*FD215ALUPGRDA 0.03 0.06 0.10 0.15 0.20
*FD235ALAH000A
*FD235ALUPGRDA 0.02 0.05 0.09 0.12 0.17 0.22 0.27
*FD260ALAH000A
*FD260ALUPGRDA 0.02 0.04 0.07 0.10 0.14 0.18 0.23 0.28 0.33
PRESSURE DROP AT SPECIFIC AIRFLOW PER MODEL
* May be "A" or "T"
This manual suits for next models
10
Table of contents
Other American Standard Air Cleaner manuals
Popular Air Cleaner manuals by other brands

asecos
asecos HF.EA.8678 operating instructions

VIRUSKILLER
VIRUSKILLER VK-blue User's guide & instructions

TEINNOVA
TEINNOVA covix onair user manual

air & water solutions
air & water solutions CAP2500 owner's manual

Honeywell
Honeywell HPA250 Series Important safety instructions

Trion
Trion Air Boss T5200 Installation, operation & service