Ansal Blue Star 12 User manual

Manual de Instalación
Thank you very much for purchasing our air conditioner,
Before using your air conditioner , please read this manual carefully and keep it for future reference.
Conjunto Split Baja Silueta de Alta Presión Estática

Install according to this installation instructions strictly.
If installation is defective, it will cause water leakage,
electrical shock fire.
When installing the unit in a small room, take measures
against to keep refrigerant concentration from exceeding
allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information.
Excessive refrigerant in a closed ambient can lead to oxygen
deficiency.
Use the attached accessories parts and specified parts
for installation.
otherwise, it will cause the set to fall, water leakage,
electrical shock fire.
Install at a strong and firm location which is able to
withstand the set' s weight.
If the strength is not enough or installation is not properly
done, the set will drop to cause injury.
The appliance must be installed 2.5m above floor.
The appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits
must be disconnected.
The appliance must be positioned so that the plug is
accessible.
The enclosure of the appliance shall be marked by word,
or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring
standard, regulation and this installation instructions. An
independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in
electrical work, it will cause electrical shock fire.
Use the specified cable and connect tightly and clamp
the cable so that no external force will be acted on the
terminal.
If connection or fixing is not perfect, it will cause heat-up or
fire at the connection.
Wiring routing must be properly arranged so that control
board cover is fixed properly.
If control board cover is not fixed perfectly, it will cause
heat-up at connection point of terminal, fire or electrical
shock.
If the supply cord is damaged, it must be replaced by the
manufacture or its service agent or similarly qualifued
person in order to avoid a hazard.
An all-pole disconnection device which has at least 3mm
separation distance in all pole and a residual current
device(RCD)with the rating of above 10mA shall be
incorporated in the fixed wiring according to the national
rule.
When carrying out piping connection, take care not to let
air substances go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high
pressure in the refrigeration cycle, explosion and injury.
Do not modify the length of the power supply cord or use
of extension cord, and do not share the single outlet with
other electrical appliances.
Otherwise, it will cause fire or electrical shock.
Carry out the specified installation work after taking into
account strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling
and causing accidents.
Be sure to be in conformity with the local, national and
international laws and regulations.
Read "PRECAUTIONS" carefully before installation.
The following precautions include important safty items.
Observe them and never forget.
Keep this manual with the owner's manual in a handy place
for future reference.
1. PRECAUTIONS
WARNING
WARNING
The safty precautions listed here are divided into two categories. In
either case, important safty information is listed which must be read
carefully.
After completing the installation, make sure that the unit operates
properly during the start-up operation. Please instruct the customer
on how to operate the unit and keep it maintained.Also, inform
customers that they should store this installation manual along with
the owner's manual for future reference.
Be sure only trained and qualified service personnel to
install, repair or service the equipment.
Improper installation, repair, and maintenance may result in
electric shocks, short-circuit, leaks, fire or other damage to
the equipment.
Failure to observe a warning may result in death.
CAUTION
Failure to observe a caution may result in injury or damage
to the equipment.
CONTENTS PAGE
PRECAUTIONS....................................................................................... 1
INSTALLATION INFORMATION................................................................ 2
ACCESSORIES....................................................................................... 3
INSPECTING AND HANDLING THE UNIT.................................................. 4
INDOOR UNIT INSTALLATION................................................................. 4
OUTDOOR UNIT INSTALLATION.............................................................13
INSTALL THE CONNECTING PIPE...........................................................17
CONNECT THE DRAIN PIPE....................................................................19
CONNECTIVE DIAGRAM........................................................................20
WIRING.................................................................................................20
TEST OPERATION..................................................................................21

To install properly, please read this "installation manual" at
first.
The air conditioner must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow
this manual as strictly as possible.
If the air conditioner is installed on a metal part of the
building, it must be electrically insulated according to the
relevant standards to electrical appliances.
When all the installation work is finished, please turn on
the power only after a thorough check.
Regret for no further announcement if there is any change
of this manual caused by product improvement.
2. INSTALLATION INFORMATION
INSTALLATION ORDER
Select the location;
Install the indoor unit;
Install the outdoor unit;
Install the connecting pipe ;
Connect the drain pipe;
Wiring;
Test operation.
CAUTION
Ground the air conditioner.
Do not connect the ground wire to gas or water pipes,
lightning rod or a telephone ground wire.Incomplete
grounding may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in
electric shocks.
Connect the outdoor unit wires , then connect the indoor
unit wires.
You are not allow to connect the air conditioner with the
power source until wiring and piping the air conditioner is
done.
While following the instructions in this installation
manual, install drain piping in order to ensure proper
drainage and insulate piping in order to prevent
condensation.
Improper drain piping may result in water leakage and
property damage.
Install the indoor and outdoor units, power supply wiring
and connecting wires at least 1 meter away from
televisions or radios in order to prevent image
interference or noise.
Depending on the radio waves, a distance of 1 meter may not
be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children
or infirm persons without supervision.
Don't install the air conditioner in the following locations:
There is petrolatum existing.
There is salty air surrounding (near the coast).
There is caustic gas (the sulfide, for example) existing in
the air (near a hot spring).
The Volt vibrates violently (in the factories).
In buses or cabinets.
In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
Other special conditions.
If the refrigerant leaks during installation, ventilate the
area immediately.
Toxic gas may be produced if the refrigerant comes into the
place contacting with fire.
The temperature of refrigerant circuit will be high, please
keep the interconnection cable away from the copper
tube.
After completing the installation work, check that the
refrigerant does not leak.
Toxic gas may be produced if the refrigerant leaks into the
room and comes into contact with a source of fire, such as a
fan heater, stove or cooker.

3. ACCESSORIES
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.
Table 3-1
QUANTITY
SHAPE
NAME
1. Soundproof / insulation sheath
10. Remote controller manual
6. Remote controller
(on some models)
7. Frame(on some models)
9.Alkaline dry batteries (AM4)
2
1
11. Wire controller 1
1
1
1
2
1
2
Tubing & Fittings
Remote controller & Its Frame
(Match with
remote controller )
Wire controller & Its Frame
(Match with wire controller )
Others
8.Mounting screw(ST2.9×10-C-H)
13. Installation manual
1
12. Owner‘s manual
4. Drain joint
5. Seal ring
Drainpipe Fittings
(for cooling & heating)
2. Binding tape 1
2

Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and
noise in those electrical appliances. (Noise may be
generated depending on the conditions under which the
electric wave is generated, even if 1 meter is kept.)
5.2 Install the main body
CAUTION
Please refer to the following figures for the distance
measurement between the screw bolts.
Please install with Ø10 hanging screw bolts.
The handling to the ceiling varies from the constructions, consult
the construction personnels for the specific procedures.
The size of the ceiling to be handled------ Do keep the
ceiling flat. Consolidate the roof beam for possible vibration.
1 Installing Ø10 hanging screw bolts. (4 bolts)
The installation of hanging screw bolts.
Carry out the pipe and line operation in the ceiling after finishing
the installation of the mai body. While choosing where to start
the operation, determine the direction of the pipes to be drawn
out. Especially in case there is a ceiling, position the refrigerant
pipes, drain pipes,indoor & outdoor lines to the connection
places before hanging up the machine.
After the selection of installation location, position the
refrigerant pipes, drain pipes,indoor & outdoor wires to the
connection places before hanging up the machine.
Cut off the roof beam.
Strengthen the place that has been cut off, and
consolidatethe roof beam.
The installation of hanging screw bolts.
Fig.5-2
NOTE
Confirm the minimum drain tilt is 1/100 or more
Wooden construction
Put the square timber traversely over the roof beam, then install
the hanging screw bolts. (Refer to Fig.5-2)
5.2
Timber over the beam
Roof beam
Hanging screw bolts
Ceiling
5. INDOOR UNIT INSTALLATION
4. INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any damage should
be reported immediately to the carrier claims agent.
When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor
damage.
Choose on before hand the path along which the unit is to be
brought in.
Move this unit as originally package as possible.
When lifting the unit , always use protectors to prevent belt
damage and pay attention to the position of the unit’s centre of
gravity.
1
2
3
4
There is enough room for installation and maintenance.
The ceiling is horizontal, and its structure can endure the
weight of the indoor unit.
The outlet and the inlet are not impeded, and the
influence of external air is the least.
The air flow can reach throughout the room.
The connecting pipe and drainpipe could be extracted out
easily.
There is no direct radiation from heaters.
5.1 Installation place
The indoor unit should be installed in a location that meets
the following requirements:
Fig.5-1
Maint enance roomage
checking orifice
600mmX600mm
600mm or more
500mm or more

Thank you very much for purchasing our air conditioner,
Before using your air conditioner , please read this manual carefully and keep it for future reference.
Fig.5-3
Fig.5-4
Fig.5-5
Fig.5-6
New concrete bricks
Inlaying or embedding the screw bolts. (Refer to Fig. 5-3)
For Original concrete bricks
Use embedding screw bold, crock and stick harness. (Refer to
Fig.5-4)
Steel roof beam structure
Install and use directly the supporting angle steel. (Refer to Fig.5-5)
5.3
5.4
5.5
(Blade shape insertion)(Slide insertion)
Steel bar
Embedding screw bolt
(Pipe hanging and embedding screw bolt)
Hanging screw bolt
Hanging bolts
Supporting
angle steel
Overhanging the indoor unit
5.6
5.7
(1) Overhang the indoor unit onto the hanging screw bolts with
block.
(2) Position the indoor unit in a flat level by using the level
indicator, unless it may cause leakage.
Screw nut
Washer
Hanging
screw bolt
Overhang part
Installing the dust proof net and canvas air passage
1. Install the dust proof net according to the installation manual;
2. Install the canvas air passage underneath the dust proof net.
Diagrammatic sketch for Installingthe main body
Shockproof cushion
5.8 Duct Design
1. Air inlet and air outlet duct should be apart far enough to
prevent air outlet entering Air Inlet.
2. There is dust filter on the indoor unit.
Recommended duct connection
Canvas tie-in Canvas tie-in
Air outlet
Isolation booth
Isolation booth
checking orifice
Air inlet
Air dust filter
NOTE
Do not put the connecting duct weight on the indoor unit.
1.
When connecting duct, use inflammable canvas tie-in to prevent
vibrating.
2.
When connecting duct, install in place prone to takedown for
maintenance.
3.
Change the fan motor static pressure corresponding to external
duct static pressure.
4.
If installed in place like meeting room where noise is easy to be
perceived, design isolation booth and internal duct underlayer to
muffle the duct system and weaken the air encounter noise in the
duct.
5.
Fig.5-7

Fig.5-8
Fig.5-9
MODEL 24~36
MODEL 42~60
Unit: mm
Unit: mm
The positioning of ceiling hole and indoor unit and hanging screw bolts
routine method of installation: the size of installation for indoor unit following the Fig.5-8 and Fig.5-9
1073
64
31
82
339
82
AIR OUTLET
1200
1148
6-Φ5 HOLES FOR AIR
OUTLET DUCT CONNECTION
AIR OUTLET DUCT FLANGE
400
AIR INTAKE DUCT FLANGE
4-12*25 OBLONG SUSPENTION BOLT HOLES AIR INTAKE
4-Φ5 HOLES FOR AIR
OUTLET DUCT CONNECTION
400
65
15
37
638
600
17 253
638
14 136
69
90
15
50
800
1148
137
125
11
28
169
691
52
35
136
123 179 15
REFRIGERANT-PIPE FLARED
CONNECTION Φ12.7(1/2)
REFRIGERANT-PIPE FLARED
CONNECTION Φ19(3/4)
CONNECTING POINT OF DRAIN PIPE
ELECTRICAL
CONTROL
BOX
PLASTIC COVER
153
169
144
136
11
28
15
15
123 179
930
135 88
24
46
68
82
82
56
270
400
AIR OUTLET
AIR INTAKE
AIR INTAKE DUCT FLANGE
4-12*25 OBLONG SUSPENTION BOLT HOLES
6-Φ5HOLES FOR AIR
INTAKE DUCT CONNECTION
AIR OUTLET DUCT FLANGE
4-Φ5HOLES FOR AIR
INTAKE DUCT CONNECTION
PLASTIC COVER
CONNECTING POINT OF
DRAIN PIPE
ELECTRICAL CONTROL BOX
REFRIGERANT-PIPE FLANED
CONNECTION Φ16(5/8) FOR MODEL 24-30
(Φ19(3/4) FOR MODEL 36)
722
65
33931
82
82
128
170
179
123
11
691
52
38
15
15
15
28
144
135
170
128
28
11
15
15
179123
212 418
82
82
88
56
270
400
68 25
46
856
800
240
15
37
600
638
16 253
638
47 134
72
103
400
161
800
15
50
SAFETY DRAIN CONNECTING PIPE
SAFETY DRAIN CONNECTING PIPE
30
255
249 29
REFRIGERANT-PIPE FLANED
CONNECTION Φ9.52(3/8) FOR MODEL 24-30
(Φ12.7(1/2) FOR MODEL 36)

Fig.5-10
The method of installation: Adopt following method if the air-conditioning’s size of installationsite is limited and the indoor unit can’t put into the
installtionsite.
MODEL 24~36
Fig.5-11
For 24-36 Cooling & Heating
Air conditioner main body Electrical heater assembly
Installation screw

Fig.5-12
Water Tray
Position A
Position B
11-Screw
Safety Drain Tray
1. The whole unit status show as Fig.5-10.
2. Remove the all 11 bolts from fixed Safety Drain Tray, and then take off the tray as figure showed in Fig.5-11.
3. Take off the tray along the direction of the arrow show in Fig.5-11.
4. Clean the tray and evaporator.
5. Re-install the unit follow the reverse above orders.
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Don’t heavy pull the foam tray, when dismounting; otherwise the foam tray would break.
CAUTION
4 Screw
For fixing the reinforced panel
Fig.5-13
maintenance of motor:
FIiler
Motor Asseembly
Safety Drain Tray 11-Screw
For fixing the satety drain tray
Fortified panel
4 Bolts
For fixing the fan assembly

1. Refer to Fig.5-12, remove all 11 bolts from safety drain tray, and take off the safety drain tray.
2. Refer to Fig.5-12, remove all 4 bolts from reinforced panel, and take off the panel.
3. Refer to Fig.5-12, remove all 4 bolts from fan assembly, see Fig.5-13, according to which orders to take off the fan assembly.
4. Refer to Fig.5-13, horizontal pushing the fan assembly, until it cannot not move any further, and then lift up slightly and take down to remove it.
5. After motor maintenance, reinstall the fan assemblies as per the reverse above orders. And connect the motor with electric control box,
as motor with power cable of capacity.
CAUTION
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Before dismount the fan assembly, you must remove the motor and electric control box, as well as connective wires between
motor and capacity assembly.
3. Fan subassembly is very heavy, please be careful during maintaining, otherwise physical injury would be caused.
Fig.5-15
MODEL 42~60
Side view of fan assembly
installation state
Front view of fan assembly installation state
Fan assembly should
push horizontally to the
end (about 18mm), and
then take off it.
The state after fan assembly is taken off
Fig.5-14
Inside of structure
Move 18mm
Move
Scroll
Pothook

12 Screw
For fixing the safety drain tray
CAUTION
Fig.5-17
Water Tray
Position A
Position B
Safety Drain Tray
1. The whole unit status show as Fig.5-13.
2. Remove the all 11 bolts from fixed Safety Drain Tray, and then take off the tray as figure showed in Fig.5-14.
3. Take off the tray along the direction of the arrow show in Fig.5-14.
4. Clean the tray and evaporator.
5. Re-install the unit follow the reverse above orders.
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Don’t heavy pull the foam tray, when dismounting; otherwise the foam tray would break.
For 48-60 Cooling & Heating
Fig.5-16
Installation screw
Electrical heater assembly
Air conditioner main body
CAUTION
The installation of the electrical heater assembly please refer to the Fig 5-16.(for some models)

Move 18mm
Move
Scroll Pothook
Side view of fan assembly
installation state
Front view of fan assembly installation state
Fan assembly should
push horizontally to the
end (about 18mm), and
then take off it.
The state after fan assembly is taken off
12-Screw
For fixing the satety drain tray
4 Bolts
For fixing the fan assembly
Fig.5-19
Fig.5-18
maintenance of motor:
Inside of structure
Safety Drain Tray
Motor Assembly
Filter
CAUTION
1. Refer to Fig.5-16, remove all 11 bolts from safety drain tray, and take off the safety drain tray.
3. Refer to Fig.5-16, remove all 4 bolts from fan assembly, see Fig.5-17, according to which orders to take off the fan assembly.
3. Refer to Fig.5-17, horizontal pushing the fan assembly, until it cannot not move any further, and then lift up slightly and take down to remove it.
4. After motor maintenance, reinstall the fan assemblies as per the reverse above orders. And connect the motor with electric control box, as
well as motor with power cable of capacity.
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Before dismount the fan assembly, you must remove the motor and electric control box, as well as connective wires between motor and
capacity assembly.
3. Fan subassembly is very heavy, please be careful during maintaining, otherwise physical injury would be caused.

5.9 Fan performances
Static pressure curve
1500 1600 1700 1800
1200
24K
Low speed
Mid speed
External static pressure (Pa)
3
Air volume(m
/h)
11001000900
170
150
130
110
90
70
50
30
10
Slight speed
1300 1400
High speed
Pa
190
100
1800 2000 2200 2400
1200
30K
Low speed
Mid speed
External static pressure (Pa)
3
Air volume(m /h)
1000900700
170
150
130
110
90
70
50
30
10
Slight speed
1400 1600
High speed
Pa
190
100
Pa
High speed
2000
1800
1200
36K
Low speed
Mid speed
3
Air volume(m /h)
1000
Slight speed
1400 1600 2200 2400
190
10
30
50
70
90
External static pressure (Pa)
110
130
150
170

6.1 Installation Place
6. OUTDOOR UNIT INSTALLATION
There is enough room for installation and maintenance.
The air outlet and the air inlet are not impeded, and can
not be reached by strong wind.
It must be a dry and well ventilating place.
The support is flat and horizontal and can stand the
weight of the outdoor unit. And will no additional noise or
vibration.
Your neighborhood will not feel uncomfortable with the
noise or expelled air.
It is easy to install the connecting pipes or cables.
Determine the air outlet direction where the discharged air
is not blocked.
There is no danger of fire due to leakage of inflammable
gas.
The piping length between the outdoor unit and the indoor
unit may not exceed the allowable piping length.
In the case that the installation place is exposed to strong
wind such as a seaside, make sure the fan operating
properly by putting the unit lengthwise along the wall or
using a dust or shield.(Refer to Fig.6-1)
If possible, do not install the unit where it is exposed to
direct sunlight.
If necessary, install a blind that does not interfere with the
air flow.
During the heating mode, the water drained off the
outdoor unit ,The condensate should be well drained away
by the drain hole to an appropriate place, so as not to
interfere other people.
Select the position where it will not be subject to snow
drifts, accumulation of leaves or other seasonal debris. If
unavoidable, please cover it with a shelter.
Locate the outdoor unit as close to the indoor unit as
possible.
If possible, please remove the obstacles nearby to prevent
the performance from being impeded by too little of air
circulation.
The minimum distance between the outdoor unit and
obstacles described in the installation chart does not
mean that the same is applicable to the situation of an
airtight room. Leave open two of the three directions
(M,N,P) (Refer to Fig.6-5)
Fig.6-1
The outdoor unit should be installed in the location that
meets the following requiements:
NOTE
All the pictures in this manual are for explanation purpose
only. They may be slightly different from the air conditioner you
purchased(depend on model).The actual shape shall prevail.
X
O
Strong wind
170
150
130
110
90
70
50
30
10
190
3800
3600
30002800
Slight speed
2400
Air volume(m
/h)
3
Mid speed
Low speed
48K
2600 3200 3400
High speed
Pa
4000
2200
2000
160
2000 2200 4000
Pa
High speed
3400
3200
2600
60K
Low speed
Mid speed
3
Air volume(m
/h)
2400
Slight speed
2800 3000 3600 3800
190
10
30
50
70
90
110
130
150
170
160

mmmm
B
C
D
E
F
Fig.6-2
Fig.6-4
Fig.6-3
A
H
A
H
1. Split type outdoor unit
6.2 Figure of body size Table 6-1 unit:mm
Fig.6-5
Table 6-2 unit:mm
AB
C
Fig.6-6
2. Vertical discharge type outdoor unit
852 582 368 390 328 660340
762 530 290 315 270 593282
762 530 290 315 270 593282
MODEL A B C D E H REMARK
F
24
18
30
36
842
940
560
600
600
335
376
376
360
400
400
312
340
340
695
1245
1245
324
895 590 333 355 302 862313
990 624 366 396 340 966354
990 624 366 396 340 966354
990 624 366 396 340 966354
990 624 366 396 340 966354
360
940 600 376 400 340 1245360
990 624 366 396 340 966354
360940
600 376 400 340 1245360940
590 378 400 330 1167340900
42
48
60
12
Fig.6-2
Fig.6-2
Fig.6-2
Fig.6-2
Fig.6-2
895 590 333 355 302 862313
Fig.6-2
Fig.6-2
Fig.6-2
Fig.6-2
Fig.6-3
Fig.6-2
Fig.6-3
Fig.6-2
Fig.6-3
Fig.6-3
590 378 400 330 1167340900
Fig.6-3
Fig.6-3
BA C
636 554 554
636 554 554
840
852
554 554
740 740
MODEL
DIMENSIONS
48
36
24
18
Refore to
Fig.6-5
Fig.6-6
REMARK

Fig.6-12
Fig.6-11
≥400
≥300
≥300
a) In case that suspending in the ceiling
b)In case that installing on the floor
≥300
≥400
≥300
3. Centrifugal fan type outdoor unit
6.4 Available configuration
All the figures in this manual are for explanation
purpose only. They may be slightly different from the air
conditioner you purchased.The actual unit shall prevail.
NOTE
NOTE
Four different configuration are available for oudoor unit only
changing the panels and fan position.
Keep in mind that fan unit weight is aprox 30g ,the unit as
well as relevant equipment covered with the vinyl cover
during installation work.
To change air inlet is only necessary to interchange the
indicated panels position. Both panels use screws to be fixed
to unit chassis.
Air inlet modification
Change Panel
Fig6-13
Table 6-3
>30cm
>30cm
>200cm
>60cm
(Wall or obstacle)
Maintain channel
Air outlet
Air inlet
M
P
Air inlet
N
>30cm
>30cm
>30cm
>30cm
>120cm
Air Outlet
Air inlet
Air inlet
Air inlet
Air inlet
Fig.6-10
(Wall or obstacle)
(Wall or obstacle)
Fig.6-9
Fig.6-8
Fig.6-7
A
B
C
D
H
E
unit:mm
3. Centrifugal fan type outdoor unit
6.3 Space of installation and maintenance
1. Split type outdoor unit
2. Vertical discharge type outdoor unit
A
1381
1394
1174
B
1328
1338
1120
C
702
783
680
D
740
820
720
E
770
850
750
F
520
568
475
G
336
398
300
H
500
574
430
I
296
342
265
J
443
1381 1328 702 740 770 520 336 500 296 443
463
393
MODEL
30
36
48
24

Fig.6-15
>60cm
Fix with bolt
Since the gravity center of the unit is not at its physical
center, so please be careful when lifting it with a sling.
Never hold the inlet of the outdoor unit to prevent it from
deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation accoding to the sepecif-ications of
the outdoor units.(Refer to Fig.6-15)
Fasten the feet of this unit with bolts firmly to prevent it from
collapsing in case of earthquake or strong wind.(Refer to
Fig.6-15)
To change air outlet is necessary to interchange panels too.
Fan outlet panel is attached to fan structure, which must be
mounted as follow.
Fig.6-14
drain water
Concrete Foundation
Fig.6-16
≥100
100~300
BC
unit:mm
1. Suspend the unit as the drawing indicates.
2. Ensure that ceiling can resist the Outdoor unit weight indicated
in specification label plate.
Suspended unit
No Description
Outdoor Unit
Vibration-proof rubber
Anchor Bolt M10
Drainage (Wide 100×Depth 150)
Drainage
Mortar Hole (Φ100×Depth 150)
Sling Bolt
Suspension Bracket
Table 6-4
Table 6-5
Fig.6-17
MODEL B C
1120 720
1328 740
1328 740
1338 820
18~24
30
36
48~60
1
2
3
4
5
6

7. INSTALL THE CONNECTING PIPE
Check whether the height drop between the indoor unit and
outdoor unit, the length of refrigerant pipe, and the number of
the bends meet the following requirements:
CAUTION
All field piping must be provided by a licensed
refrigeration technician and must comply with the
relevant local and national codes.
Do not let air, dust, or other impurities fall in the pipe
system during the time of installation.
The connecting pipe should not be installed until the
indoor and outdoor units have been fixed already.
Keep the connecting pipe dry, and do not let moisture in
during installation.
Execute heat insulation work completely on both sides
of the gas piping and the liquid piping. Otherwise, this
can sometimes result in water leakage.
The Procedure of Connecting Pipes
7.1
(The number of bends less than 10)
Table 7-1
Model
12K
18K-24K
30K-42K
12K
18K-24K
30K-60K
48K-60K
12K
18K-24K
30K
48K-60K
36K
50Hz T1 condition/R22
Split type air conditioner
50Hz Vertical discharge air conditioner
/60Hz T1 condition/R22 Split type air
conditioner and Vertical discharge air
conditioner
The type of models
R410A inverter Split type air
conditioner and and Centrifugal
fan outdoor unit
50
50
30
15
50
30
15
30
30
25
10
25
R410A Split type air conditioner
and and Centrifugal fan outdoor
unit
50Hz/60Hz T3 condition
(outdoor unit down)
50Hz/60Hz T3 condition
(outdoor unit up)
the unit with quick joint
12K
48K-60K
18K-30K
36K
18K-24K
42K-60K
30K
36K
18K-24K
12K-18K
48K-60K
42K
30K
36K
50
25
15
30
50
30
25
30
25
50
30
30
50
15
35
55
25
20
30
25
15
8
20
25
15
10
20
20
25
12
5
15
25
10
8
20
10
8
20
refrigerant pipe
The length of
height drop
The max
Drill a hole in the wall (suitable just for the size of the wall
conduit), then set on the fittings such as the wall conduit and
its cover.
Bind the connecting pipe and the cables together tightly with
binding tapes.
Pass the bound connecting pipe through the wall conduct
from outside. Be careful of the pipe allocation to do on
1
2
Connect the pipes. Refer to "How to Connect the pipes" for
details.
Expel the air with a vacuum pump. Refer to "How to expel the
air with a vacuum pump" for details.
open the stop values of the outdoor unit to make the refrigerant
pipe connecting the indoor unit with the outdoor unit in fluent
flow.
Check the leakage. Check all the joints with the leak detector or
soap water.
Cover the joints of the connecting pipe with the soundproof /
insulating sheath (fittings), and bind it well with the tapes to
prevent leakage.
3
5
6
7
4
How to Connect the pipes
Flaring
1
Cut a pipe with a pipe cutter. (Refer to Fig.7-1)
Table 7-2
Insert a flare nut into a pipe and flare the pipe.
Refer to Table 7-2 for the dimension of flare nut spaces.
(mm)
6.4 8.3 8.7
9.5 12.0 12.4
12.7 15.4 15.8
15.9
19
18.6 19.0
22.9 23.3
R0.4~0.8
45°±2
90 °
±4
A
min max
Pipe gauge Tightening torque Flare dimensin A
97.2~118.6 N.m
(990~1210 kgf.cm)
(630~770 kgf.cm)
61.8~75.4 N.m
49.5~60.3 N.m
(504~616 kgf.cm)
32.7~39.9 N.m
(333~407 kgf.cm)
14.2~17.2 N.m
(144~176 kgf.cm)
Fig.7-1
Flare shape
Ø
Ø
Ø
Ø
Ø
90 Lean crude burr
Be sure to with insulating materials cover all the exposed parts
of the flare pipe joints and refrigerant pipe on the liquid-side
and the gas-side. Ensure that there is no gap between them.
Incomplete insulation may cause water condensation.
CAUTION
2
Bend the tubing in proper way. Do not harm to them.
Connect the indoor unit at first, then the outdoor
unit.
Bend the pipe with thumb
min-radius 100mm
Fig.7-2
The bending angle should not exceed 90.
Bending position is preferably in the middle of the
bendable pipe. The larger the bending radius the better it
is.
Do not bend the pipe more than three times.
When connecting the flare nut, coat the flare both inside
and outside with either oil or ester oil and initially tighten

-76 cmHg
Lo-lever Hi-lever
Charge hose Vacuum pump
Lo-lever
Manifold valve
Multi-meter Pressure meter
Outdoor
unit
Indoor
unit
Stop valve
Gas side
Liquid side
AC
D
B
Fig.7-6
Fig.7-7
service port
cap
maintenance nut
hexagon holeshaftseal
Fig.7-5
Loosen and remove the maintenance nuts of stop valves A
and B, and connect the charge hose of the manifold valve to
the service port of stop valve A. (Be sure that stop valves A
and B are both closed)
Connect the joint of the charge hose with the vacuum pump.
Open the Lo-lever of the manifold value completely.
Turn on the vacuum pump. At the beginning of pumping,
loosen the maintenance nut of stop valve B a little to check
whether the air comes in (the sound of the pump changes,
and the indicator of compound meter turns below zero). Then
fasten the maintenace nut.
When the pumping has finished, close the Lo-lever of the
manifold valve completely and turn off the vacuum
pump.Make pumping for 15 minutes or more and check that
the compound meter indicates -76cmHg(-1X10 Pa)
Loosen and remove the cap of stop valves A and B to open
stop valve A and B completely, then fasten the cap.
Disassemble the charge hose from the service port of stop
valve A, and fasten the nut.
1
2
4
3
5
7
6
Using the vacuum pump
5
Fig.7-3
Remove the cap and turn the valve clockwise with the
hexagon wrench.
Securely tighten the valve until the shaft contacts the
main bodyseal.
CAUTION
Always use a charge hose for service port connection.
After tightening the cap, check that no refrigerant leaks
arepresent.
Tightening torque N M (Turn clockwise to close)
Stop Shaft (valve body) Cap
(Valve lid)
Ø6.4
Hexagonal
wrench 4 mm
Ø9.5
Ø12.7
Ø15.9 Hexagonal
wrench 6 mm
Ø22.2 Hexagonal
wrench
10 mm
Ø25.4 36~44
23~27
18~22
13.5~16.55.4~6.6
8.1~9.9
13.5~16.5
27~33
11.5~13.9
Make sure to tighten the cap securely.
For the tightening torque,refer to the table below.
Too large torque will harm the bellmouthing and too
small will cause leakage. Please determine the torque
according to Table 7-3.
After the connecting work is finished, be sure to check
that there is no gas leak.
CAUTION
How to expel the air with a vacuum pump
Stop valve operation introduction
1.
2.
3.
Remove the cap and turn the valve
counterclock-wise with the hexagon wrench.
Turn it until the shaft stops.Do not apply excessive
force to the stop valve. Doing so may breakthe valve
body, as the valve is not a backseat type. Always use
the special tool.
Make sure to tighten the cap securely.
Fig.7-4
Maintenance nut
Be sure to use both a spanner and torque wrench
together when connecting or disconnecting pipes to
/from the unit.

8. CONNECT THE DRAIN PIPE
Install the drainpipe of the indoor unit
The outlet has PTI screw bread, Please use sealing materials
and pipe sheath(fitting) when connecting PVC pipes.
The drain pipe of indoor unit must be heat insulated, or it will
condense dew, as well as the connections of the indoor unit.
Hard PVC binder must be used for pipe connection, and make
sure there is no leakage.
With the connection part to the indoor unit, please be noted not
to impose pressure on the side of indoor unit pipes.
When the declivity of the drain pipe downwards is over 1/100,
there should not be any winding.
The total length of the drain pipe when pulled out traversely shall
not exceed 20m, when the pipe is over long, a prop stand must
be installed to prevent winding.
Refer to the under figures for the installation of the pipes.
CAUTION
8.1
1.5m~2m
Insulating
material Downward declivity
lower than 1/100
Bend
S shape
VP30
Downward declivity
lower than 1/100
Put as deep as possible
(about 10cm)
Fig.8-1
70 100
60
80
Fig.8-2
Check the Leakage
7.3
Check all the joints with the leak detector or soap water.
(See Fig.7-8 as a reference illustration)
NOTE
In the figure
A......Lo-stop valve
B......Hi-stop valve
C,D..Joints of the connecting pipe to the indoor unit.
B A
DC
Check-point of indoor unit
Check-point of outdoor unit
Fig.7-8
Additional Refrigerant Charge
7.2
CAUTION
Refrigerant cannot be charged until field wiring has been
completed.
Refrigerant may only be charged after performing the leak test
and the vacuum pumping.
When charging a system, care shall be taken that its maximum
permissible charge is never exceeded, in view of the danger of
liquid hammer.
Charging with an unsuitable substance may cause explosions
and accidents, so always ensure that the appropriate
refrigerant is charged.
Refrigerant containers shall be opened slowly.
Always use protective gloves and protect your eyes when
charging refrigerant.
The outdoor unit is factory charged with refrigerant.
Calculate the added refrigerant according to the diameter
and the length of the liquid side pipe of the outdoor
unit/indoor unit connection.
NOTE:The number of bends is up to the length of the max
height drop.Usually for each 10m need a bend.
Table 7-4
Brass tube(mm) R410A R22
Ø6.35
Ø9.53
Ø12.7
Ø15.9
Ø19.0
0.022kg/m×(L-5)
0.011kg/m×(L-5)
0.060kg/m×(L-5)
0.030kg/m×(L-5)
0.110kg/m×(L-5)
0.060kg/m×(L-5)
0.170kg/m×(L-5)
0.085kg/m×(L-5)
0.250kg/m×(L-5)
0.125kg/m×(L-5)
0.030kg/m×(L-5)
0.015kg/m×L
0.065kg/m×(L-5)
0.030kg/m×L
0.115kg/m×(L-5)
0.060kg/m×L
0.190kg/m×(L-5)
0.095kg/m×L
0.290kg/m×(L-5)
0.145kg/m×L
orifice in the indoorunit
orifice in the outdoorunit
orifice in the outdoorunit
orifice in the outdoorunit
orifice in the outdoorunit
orifice in the outdoorunit
orifice in the indoorunit
orifice in the indoorunit
orifice in the indoorunit
orifice in the indoorunit
NOTE:the table above refer to the liquid tube.
This manual suits for next models
7
Table of contents
Other Ansal Water Pump manuals
Popular Water Pump manuals by other brands

Ingersoll-Rand
Ingersoll-Rand 66243-X Operator's manual

DAYLIFF
DAYLIFF DDW 400S Installation & operating manual

FLORABEST
FLORABEST FTS 1100 B2 translation of original operation manual

Binks
Binks E2-60 Service manual

Nordson
Nordson VDK-MIDI TYPE 6 operating instructions

LIFAN Power USA
LIFAN Power USA LF1.5HWP Operating instructions and owner's manual

Pentair
Pentair NOCCHI FCD20 PVM 5-5 F manual

Wayne
Wayne WLS150 Operating instructions and parts manual

Hoppecke
Hoppecke Electrolyte Circulation System Installation and operating instructions

Intex
Intex QUICK FILL PLUS quick start guide

JABSCO
JABSCO 59510-Series manual

Siccom
Siccom mini FLOWATCH 1 EVO manual