Antari SFX-1000 User manual

- - 0 - -

- 1 -
SFX-1000 & SFX-1500
Security Smoke Generator User Manual
Thank you for choosing Antari security smoke generator. Please read this instruction carefully prior to
operation.
Warning!
* Hot nozzle! Keep at least 50 cm distance.
* The heater of the generator is extremely hot. Please be careful when the front cover is opened.
* No user serviceable parts inside. Please contact with an authorized dealer when maintenance is
required.
* Please disconnect power before change fuse.
* Please operate only with adult supervision.
* Only Antari smoke fluid should be used. Other fluid may damage the equipment or cause dangers
to human physical safety.
* Do not use without smoke fluid.
* For indoor use only. Please keep dry.
* Please clear smoke away from room after an ejectment. Otherwise, residue might be caused.
Package
Before starting installation Antari security smoke generator, please make sure that you have all the
following equipments:
● 1 × Antari security smoke generator
● 1 × Smoke fluid bladder
● 1 × Mounting set
● 1 x User Manual
Controlling of Smoke
The three sets of terminal blocks on the PCB of Antari smoke generators, Alarm, Trigger, and Hold-off
are the keys to generate smoke. In order for generator to produce smoke in the critical moment, the
three sets of connections must be closed circuit at the same time, which can avoid wrong action of
making smoke. For instance, both Alarm and Trigger can be set up as switches on the security system
control panel. On the other hand, Hold-off usually can be connected to a PIR (motion detector) or a
window/door sensor. However, please note in order to stop making smoke, either Trigger or Alarm has
to be released (open circuit). Only releasing Hold-off cannot stop smoking.

- 2 -
PCB Connection
All relay outputs are offered as volt-free contacts.
The “Alarm” and “Trigger” inputs are also required to be volt-free.
Tamper: When the Tamper connection or its front jumper or the machine front cover or fluid bag
chamber cover, any one of above four parts is open circuit, the LED red light will flash
every 2 seconds and the buzzer will produce a long beep sound every minute to warn.
12V/100mA This terminal block can offer DC 12V 100mA power output.
Hold off This terminal can work with Alarm and Trigger together to activate the smoke generator.
When all Hold, Alarm, and Trigger, three terminal blocks are closed circuit, the machine
will start to produce smoke. Usually, this terminal can be connected to a PIR (motion
detector) or a door/window sensor. Once the PIR is activated, this connection will be
closed circuit. However, only removing Hold-off (Making it open circuit) cannot stop
smoking.
Verification There are three connection points in this terminal block. They are COM, NO (Normally
Open), and NC (Normally Closed) respectively. When COM and NO are wired to a
security control center, the relay will give a signal of closed circuit if the machine is
activated. This signal can notice the security control center that the unit is producing
smoke. Or this connection can be wired to another security smoke machine. When the
unit starts to produce smoke, this terminal will send the closed circuit signal to trigger the
other smoke machine.
If COM and NC are wired, the reverse signal (open circuit) will be sent out.
UPS There are three connection points in this terminal block. They are COM, NO (Normally
Open), and NC (Normally Closed) respectively. When COM and NO are wired to a
security control center, the relay will give a signal of closed circuit if the UPS is in use.
This signal can notice the security control center that the UPS is working.
If COM and NC are wired, the reverse signal (open circuit) will be sent out.
Low There are three connection points in this terminal block. They are COM, NO (Normally
Open), and NC (Normally Closed) respectively. When COM and NO are wired to a
security control center, the relay will give a signal of closed circuit if the smoke fluid is low.
This signal can notice the security control center that the smoke fluid is low.
If COM and NC are wired, the reverse signal (open circuit) will be sent out.
Ready There are three connection points in this terminal block. They are COM, NO (Normally
Open), and NC (Normally Closed) respectively. When COM and NO are wired to a

- 3 -
security control center, the relay will give a signal of closed circuit if the smoke machine
completes the heating process. This signal can notice the security control center that the
smoke machine is ready.
If COM and NC are wired, the reverse signal (open circuit) will be sent out.
Trigger This terminal can work with Alarm and Hold together to activate the smoke generator.
When all Hold, Alarm, and Trigger, three terminal blocks are closed circuit, the machine
will start to produce smoke.
Generally, this terminal can be set as a switch. Releasing the switch (Making it open
circuit) can stop smoking.
Alarm This terminal can work with Trigger and Hold together to activate the smoke generator.
When all Hold, Alarm, and Trigger, three terminal blocks are closed circuit, the machine
will start to produce smoke. Generally, this terminal can be set as a switch. Releasing the
switch (Making it open circuit) can stop smoking.
◎Example for PCB connection
}
}
RIR ( Motion detector)
12V/100mA DCinput
(Please notice positive and negative)
Activated signal
Change of status displayed by LED
FU LR
ON/OFF
Activated signal
Change of status
signal output
Switch
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
TAMPER
12VDC/100mA
Hold
Verification
FOG
UPS
LOW
Ready
Trigger
Alarm
Notice:
When Trigger, Alarm, and Hold are activated at the same time (All are closed circuit),
the generator will start to produce smoke.
In order to stop making smoke, either Trigger or Alarm has to be removed (Open circuit).
Only removing Hold cannot stop smoking.

- 4 -
◎Example of application
Security Buzzer Security Smoke Generator Security Strobe
SecuritySystemControlCenter PIR(MotionDetector)
Setting the DIP Switches
Open the front cover and locate the DIP switches (There is a block of two).
DIP1 When switch to “ON”, the activation of producing smoke is reverse.
(It means that Alarm, Trigger, Hold-off PIR Alarm have to be open circuit in order to make
smoke)
DIP2 In order to change UPS state (Switch UPS ON/OFF) on the security smoke machine, first please
switch DIP Switch 2 to ON. At this moment, the red and green LED flicker.
And then please press PB2 button for 10 seconds. When setting is completed successfully, the
buzzer beeps. After setting, please switch the DIP Switch 2 to OFF. Then the whole process is
totally finished.
Set Up Duration of Smoke Output
Switch DIP switch No. 2 to “ON”. Press PB1 for 5 seconds. After twice short beep, every press of PB1
can add 15 seconds. The duration of smoke can be set between 15 and 360 seconds. When setting is
completed, switch DIP 2 to “OFF”.
Replacement of Smoke Fluid Bladder
Open the front cover, smoke fluid bladder can be changed easily in a few seconds. When processing
exchange of smoke fluid bladder please turn on the power of the generator and make sure that micro
switch is activated properly ( you can hear the click sound) so that timer can be reset and record the
working time of smoke fluid bladder correctly. Loose knob and clamp and take old fluid bladder out first.
Insert fluid pipe connector into new fluid bladder cap (out mark). Finally, put the new bladder back to the
generator and screw the knob and clamp tightly. Meanwhile please confirm if the LED light is on green

- 5 -
light normally. Please always replace a full fluid bladder. Otherwise, it might damage the pump of
generator.
LED & Buzzer Status Table
Machine Status Buzzer LED
Machine Overheating 1 short beep every 5 sec. Red flash twice every 2 sec.
Front Cover or Fluid Bag
Chamber Cover is Opened
1 long beep every 1 min. Red flash once every 2 sec.
UPS Power Cut 3 short beeps every 30 sec. Red flash twice every 5 sec.
AC Power Cut 2 short beeps every 30 sec. Red flash once every 5 sec.
Heater Fault 1 long beep every 10 sec. Red flash
Fluid Level Empty 1 long and 1 short beep every 5 min. Orange flash
Fluid Level Low 1 short beep every 5 min. Permanent orange
Heating Process incomplete Long beep for 30 sec. and then 3 short
beeps every 5 min.
Permanent red
DIP 2 switch to ON No buzzer Red and green flash together
Normal No buzzer Permanent green
Armed No buzzer Green light flashes slowly
Test the security smoke generator
Once Antari security smoke generators reach ready status (Green LED On), you can carry out a simple
test at generators to check the smoke production.
Open the front cover, and press and hold down the “PB1“test button. The machine will produce smoke.
Smoke production ceases once the “PB1”test button is released.
Thank you very much again for your patience and reading this manual. If you have any further question
about our products, please do not hesitate to contact your local distributor orAntari directly.
Antari contact information
No. 8, Lane 231, Nankan Rd., Sec.1, Lujhu, Taoyuan county, Taiwan

- 6 -
SFX-1000 & SFX-1500 保全煙霧機操作說明書
ຏᔁଋᏴϡ!Antari ܲБᙳ፟Ăֹϡ݈ኛͿዦώᄲځĄ!
警告!
* ᙳᆡĂኛҌᄃܲ 50 ۞ᗓĄ
* ᙳ፟ሤგޘޝĂ༊χฟ᜕ᄏኛ፺๋Ċ
* ፟ጡొֹϡ۰ΞҋҖՀೱ۞ІĄтᅮჯ࣒ܲዳኛᓑඛᝋགྷዚથĄ
* Հೱܲᐍක݈ኛᙯౕĄ
* ኛдѣјˠႾ༛۞ଐڶ˭ֹϡĄ
* ኛֹϡ Antari ϡᙳڵĂᙳڵΞົౄјᙳ፟۞ຫᗼٕˠវઉ۞๋Ą
* ᙳڵኛֹϡĄ
* ่ዋϡٺވĂ֭ኛܲᒌĄ
* ᆡޢኛވ۩ঈĂӎΞౄјണۏĄ
ᇾΒ྅
щ྅݈ኛቁᄮଋѣͽ˭ٙѣІ:
● 1 × Antari ܲБᙳ፟
● 1 × ᙳڵఠ
● 1 × У (ᒒࢬ܅ڕУ)
● 1 × ֹϡᄲځ
ᙳ۞ଠט
Antari ᙳ፟۞ྮڕ˯۞ˬბତᕇ Alarm,Trigger Hold-off ߏᄦౄᙳ۞ᙯᔣĄࠎ˞ֹᙳ፟д
ࢦࢋגϒቁજү,ͽ˯ˬତᕇυืТజౕྮጱ఼,ΞͽᔖҺ፟ጡ۞ᄱજүĄּ т ,AlarmTrigger
ӮΞజనؠࠎܲБଠט۞ୁજฟᙯ,҃Ω˘ࢬ,Hold-off ఼૱ΞͽజాତҌ˘࣎ PIR(જүઍീጡ)
ٕܝઍീጡĄ҃,ኛڦຍ!тࢋઃᆡજү,υืྋฟ Alarm ٕTrigger Ї˘ฟᙯ(ֹјࠎฟྮ,ጱ
఼۞ېၗ),ֹ่ Hold-off ฟྮߏڱֹ፟ઃજү۞Ą
ྮڕ۞Α
ٙѣយ۞ᏮӮࠎᑅ
Alarm Trigger ۞Ꮾˢ˵ืࠎᑅ

- 7 -
Tamper ༊Tamper ତᕇٕ݈۞ྭତጡ(Jumper)ٕ፟ጡ˯ᄏٕڵఠވᄏЇң˘ࠎฟྮې
ၗ,LED ົՏࡋࡓ፶˘Ѩ,ཻᆀጡົՏᛗ൴˘ܜဤᓏֽᛋϯ
12V/100mA ѩତᕇΞͽ೩ֻۡ߹ 12V 100 щૈ۞Ꮾ
Hold off ѩତᕇ Alarm,Trigger Ξͽ˘үֽᛈ൴ᙳ፟ᆡĄ༊ Hold-off, Alarm Trigger ˬ
ᕇТజጱ఼ࠎౕྮ۞ېၗ˭,ᙳ፟ܮົฟؕᄦౄĄ఼૱ΞͽజాତҌ˘࣎ PIR(જү
ઍീጡ)ٕܝઍീጡ,˘ό PIR ٕܝઍീጡజᛈ൴,ѩତᕇܮົјࠎౕྮېၗ,Ъజฟୁ
۞Alarm Trigger ܮΞͽֹ፟જү,҃,ֹ่ Hold-off ฟྮߏڱֹ፟ઃજү۞Ą
Verification ѩბ˯ѣˬତᕇ,Ҿࠎ COM,NO(૱ฟ)NC(૱ౕ)Ą༊ COM NO జତቢזܲБଠ
ט,тᙳ፟జᛈ൴ฟؕજү,យົ็˘ౕ࣎ྮ۞ගଠט,ѩΞ
ͽ఼ۢܲБଠט፟ጡགྷฟؕᆡ˞Ąٕ۰,ΞӀϡѩତᕇΝాତΩ˘ܲБᙳ፟,
༊፟ጡฟؕજү,ѩତᕇົ˘ౕ࣎ྮ۞ཱིΝୁજΩ˘ᙳ፟Ą
тڍߏ COM NC జాତ,ᙳ፟జᛈ൴,࠹۞ཱི(ฟྮ)ົజĄ
UPS ѩბ˯ѣˬତᕇ,Ҿࠎ COM,NO(૱ฟ)NC(૱ౕ)Ą༊ COM NO జତቢזܲБଠ
ט,тUPS Αజֹϡ,យົ็˘࣎ගଠט,ѩΞͽ఼ۢܲБଠ
ט UPS ΑགྷฟؕજүĄ
тڍߏ COM NC జాତ,UPS જү,࠹۞ཱི(ฟྮ)ົజĄ
Low ѩბ˯ѣˬତᕇ,Ҿࠎ COM,NO(૱ฟ)NC(૱ౕ)Ą༊ COM NO జତቢזܲБଠ
ט,тᙳڵҲڵณ,យົ็˘࣎ගଠט,ѩΞͽ఼ۢܲБଠט
ᙳڵགྷҲڵณېၗĄ
Ready тڍߏ COM NC జాତ,UPS જү,࠹۞ཱི(ฟྮ)ົజĄ
ѩბ˯ѣˬତᕇ,Ҿࠎ COM,NO(૱ฟ)NC(૱ౕ)Ą༊ COM NO జତቢזܲБଠ
ט,༊፟ጡΐሤԆј,យົ็˘࣎ගଠט,ѩΞͽ఼ۢܲБଠט
፟གྷԆјΐሤ,ٺ౯р۞ېၗĄ
тڍߏ COM NC జాତ,UPS જү,࠹۞ཱི(ฟྮ)ົజĄ
Trigger ѩତᕇ Alarm, Hold-off Ξͽ˘үֽᛈ൴ᙳ፟ᆡĄ༊ Trigger, Alarm Hold-off
ˬᕇТజጱ఼ࠎౕྮ۞ېၗ˭,ᙳ፟ܮົฟؕᄦౄᙳĄ˘҃֏,ѩତᕇΞͽజనࠎ
ୁજฟᙯ,ྋฟѩฟᙯ(ֹјࠎฟྮ۞ېၗ)Ξͽֹ፟ጡઃજүĄ
Alarm ѩତᕇ Trigger, Hold-off Ξͽ˘үֽᛈ൴ᙳ፟ᆡĄ༊ Alarm, Trigger Hold-off
ˬᕇТజጱ఼ࠎౕྮ۞ېၗ˭,ᙳ፟ܮົฟؕᄦౄᙳĄ˘҃֏,ѩତᕇΞͽజనࠎ
ୁજฟᙯ,ྋฟѩฟᙯ(ֹјࠎฟྮ۞ېၗ)Ξͽֹ፟ጡઃજүĄ

- 8 -
◎ ྮڕాତቑּ
}
}
RIR ( )動作偵測器
12V / 100mA ( )電壓輸入 請注意正負極
觸發訊號
LED燈號顯示機器狀態的改變
FULR
ON/OFF
觸發訊號
機器狀態改變訊號
啟動開關
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
TAMPER
12VDC/100mA
Hold
Verification
FOG
UPS
LOW
Ready
Trigger
Alarm
ڦຍ: Alarm, Trigger Hold-off ˬତᕇТజౕྮጱ఼,፟ጡົฟؕᆡજү
тࢋઃᆡજү,υืྋฟ Alarm ٕTrigger Ї˘ฟᙯ(ֹјࠎฟྮ,ጱ఼۞ېၗ),ֹ่ Hold-off
ฟྮߏڱֹ፟ઃજү۞Ą
◎ ܲБ፟ᑕϡቑּ
ܲБཻᆀጡ ܲБᙳ፟ ܲБЍ፶
ܲБրଠט PIR જүઍീጡ
ᇥฟᙯ۞నؠ
χฟᙳ፟۞݈ᄏĂѣ˘࣎Ξᇥ۞ᇥฟᙯΞͽనؠĄ

- 9 -
DIP1 ˘ཱིᇥฟᙯᇥҌ”ON”Ăୁજᙳ۞જү࠹Ą
(ຍ Alarm, Trigger, Hold-off PIR Alarm υืజฟྮ,јࠎጱ఼۞ېၗ,፟ጡົฟؕயϠ
ᙳ)
DIP2 ࢋฟᙯ UPS ืАᇥฟᙯ 2ᇥШ ON Ă LED ϯ፶ົࡓăქϹᘖĂҝ PB2 ต10 ࡋĂ
༊నؠјΑཻᆀጡົ൴ဤဤᓏĂనؠрޢГᇥฟᙯ 2ᇥШ OFF ĂܮԆјೱ UPS ۞ᙯౕᄃฟୁĄ
ᜈᆡม۞నؠ
2ཱིᇥฟᙯᇥҌ”ON”Ąᑅҝ PB1 ᔣ5ࡋĄᓏൺဤޢĂՏ˘Ѩ PB1 Ξͽᆧΐ 15 ࡋ۞ᆡมĂ
มΞͽనؠд 15 Ҍ360 ࡋมĄనؠԆјޢĂ 2ཱིᇥฟᙯᇥҌ”OFF”Ą
ڵఠ۞Հೱ
χฟᙳ݈፟ᄏĂΞͽдޝൺ۞มᅅٽ۞ՀೱڵఠĄ༊ซҖڵఠ۞ՀೱĂኛᙳ፟χ
ฟĂ֭ቁؠજฟᙯజᛈ൴(ಁඍᓏ)ឰࢍጡࢦາࢍĂтѩࢍጡϒቁгᐂڵఠ۞үมĄ
ࢵАĂᗫฟؠڵఠ۞ตΙĂפᖞڵఠĂତĂڵგᐝ೧ˢາڵఠ۞ఠᄏ۞ OUT ĂޢĂ
າڵఠٸаᙳ֭፟ΙตᖼღĂТᑭߤ፶ཱིߏӎޭೇϒ૱ĄՀೱڵఠኛೱ˯Бາ·
႕ڵ۞ڵఠĂӎĂΞົౄјᑒ۞ຫᗼĄ
LED ཻᆀጡᄲځ
፟ጡېၗ ཻᆀጡᓏᜩېၗ LED ϯېၗ
፟ጡ࿅ሤ Տ5ࡋᛗ 1ൺဤ ࡓ፶Տ 2ࡋᘖ 2Ѩ
፟ጡ˯ᄏٕڵఠވᄏజχฟ Տ1ᛗ 1ܜဤ ࡓ፶Տ 2ࡋᘖ 1Ѩ
UPS జᕝ Տ30 ࡋᛗ 3ൺဤ ࡓ፶Տ 5ࡋᘖ 2Ѩ
AC జᕝ Տ30 ࡋᛗ 2ൺဤ ࡓ፶Տ 5ࡋᘖ 1Ѩ
ΐሤ྅ཉѣયᗟ Տ10 ࡋᛗ 1ܜဤ ࡓ፶ᘖ
۩ڵณ Տ5ᛗ 1ܜ1ൺဤ ፗ፶ᘖ
Ҳڵณ Տ5ᛗ 1ൺဤ ፗ፶ޮܪ
ΐሤϏԆј ܜဤ 30 ࡋĂՏ 5ᛗ 3ൺဤ ࡓ፶ޮܪ
2ཱིᇥฟᙯᇥז ON ࡓҒქҒϹᘖ
ϒ૱ ქ፶ޮܪ
ᛋԦ ქ፶ቤၙᘖ

- 10 -
ീྏܲБᙳ፟
˘ό Antari ܲБᙳ፟ٺ౯р۞ېၗ(ქLED ፶ܪ)ĂଋΞͽ၆ᙳ፟ᆡߏӎϒ૱જүઇ˘࣎ᖎಏ
۞ീྏĄχฟᙳ፟۞݈ᄏĂ”PB1”ീྏᔣĂᙳ፟ಶົயϠᙳĂ༊ٸฟീྏᔣĂᙳ፟ಶົ
ઃᆡĄ
ГѨຏᔁଋዦώᄲځĂтଋ၆ Antari யݡѣЇң࠹ᙯႷયĂኛϲӈᄃ༊г
གྷዚથٕۡତᄃԧࣇᓑඛĄᔁᔁĊ
Antari ᓑඛ
Email: sales@antari.com ྖ: +886-3-322-5829 ็ৌ:+886-3-322-0433
έ៉Ꭹᛀѻฏݑྮ˘߱ 231 ޒ8ཱི

- 11 -
C08SFX102
This manual suits for next models
1
Table of contents
Other Antari Fog Machine manuals

Antari
Antari F-5 Fazer User manual

Antari
Antari B-100 User manual

Antari
Antari Z-3000II User manual

Antari
Antari HZ-500 User manual

Antari
Antari Z-300II Fazer User manual

Antari
Antari M-5 User manual

Antari
Antari HZ-100 User manual

Antari
Antari Z-390 Series User manual

Antari
Antari MOBILE MB-1 User manual

Antari
Antari Z-380 User manual

Antari
Antari F-2 Fazer User manual

Antari
Antari Z-1520 RGB User manual

Antari
Antari B-100 User manual

Antari
Antari Z-1500 III User manual

Antari
Antari F-4 Fazer User manual

Antari
Antari FT-50 User manual

Antari
Antari DNG-250 User manual

Antari
Antari SW-250 User manual

Antari
Antari S-120 User manual

Antari
Antari DNG-200 User manual