Apollo 51000-600 User manual

51000-600 / 51000-601
Wireless Combination Smoke, Heat and
Carbon Monoxide Detector
Installation Guide
ATTENTION: This manual should be read prior to use and retained for further
information.
1. GENERAL INFORMATION
The Wireless Combination Smoke, Heat and Carbon Monoxide Detector is a
2xCR123A battery powered wireless detector intended for use with a compatible
wireless alarm system. The detector consists of a photoelectric smoke sensor,
thermistor heat sensor and electrochemical carbon monoxide sensor coupled to a
wireless transmitter, which communicates with the control panel. When fire or
carbon monoxide is detected, the detector sounds a loud local alarm and the built-
in transmitter sends a signal to the control panel. The Wireless Combination
Smoke, Heat and Carbon Monoxide Detector contains an integrated fixed 41°F
(5°C) temperature freeze sensor that will send a warning signal based on
temperature detected. This detector is designed to provide protection with 70-foot
spacing capability. The detector can send alarm, tamper and battery condition
messages to the system’s receiver. Refer to the wireless system’s instruction for the
maximum number of transmitters that can be supported.
The detector has an operational life of 10 years. After 10 years of operation the
detector will provide audio visual trouble indication and must be replaced.
WARNING: This product is intended for use in ordinary indoor residential areas. It
is not designed to measure compliance with Occupational Safety & Health
Administration (OSHA) commercial and industrial standards.

2. DETECTOR OVERVIEW
2.1 DETECTOR FRONT
Figure 1 - Detector Front
2.2 DETECTOR BACK
Figure 2 - Detector Back
CO Test Button
Indicator LEDs
Fire Test
Button
CO Sensor
Gas Entry Port
Anti-Tamper Lock
Release
Sounder
Tamper Switch
Mechanism
Anti-Tamper Lock
Mechanism
Battery
Compartment

2.3 DETECTOR MOUNTING BASE
Figure 3 - Mounting Base
3. CONTENTS OF BOX
•Wireless Combination Smoke, Heat and Carbon Monoxide Alarm with
mounting base
•Installation guide (APD0812)
•Pack of screws and anchors
•Labels or decals as appropriate
•2 CR123A Panasonic batteries or 2 EL123AP Energizer batteries
4. OPERATION
The Wireless Combination Smoke, Heat and Carbon Monoxide Detector contains a
sounder which generates ANSI S3.41 Temporal-3 pattern when fire is detected or
ANSI S3.42 Temporal-4 pattern when Carbon Monoxide is detected. In alarm, a
message is also sent to the control panel and the detector’s ID is displayed. During
an alarm condition, pressing either of the FIRE or CO test/hush buttons will silence
the sounder for a short period (see LED and sounder operating modes table).
A multi-color LED indicator provides visual indication for the detector operating
modes and states. In general, RED is used to indicate ALARM conditions, YELLOW
is used to indicate FAULT conditions and GREEN is used for normal operation (see
Detector Status LED & Sounder operating modes table).
4.1 DETECTOR STATUS LED & SOUNDER OPERATING MODES
Status
Description
LEDs
Sounder
Smoke Alarm
Smoke has been
detected
3 RED flashes
in time with
sounder
Temporal-3
BEEP-BEEP-BEEP-pause
(press either button to
hush for 7 minutes)
Heat Alarm
Heat has been
detected
3 RED flashes
in time with
sounder
Temporal-3
BEEP-BEEP-BEEP-pause
CO Alarm
Carbon Monoxide
has been detected
4 RED flashes
in time with
sounder
Temporal-4
PIP-PIP-PIP-PIP-long
pause
(press either button to
hush for 5 minutes)
CO GO/NO-
GO Test
Test mode for
checking Carbon
Monoxide
functionality with
test gas
1 GREEN flash
followed by
1 BLUE flash
every 12
seconds
None
Freeze
Warning
Temperature is
below 41°F (5°C)
3 YELLOW
flashes
every 4
seconds
None
Anti-Tamper
Locking Tab
Tamper Switch
Mechanism
Screw Mounting Holes

General Fault
A sensor has failed or
some other fault has
occurred
1 YELLOW
flash
every 4
seconds
Chirp every 48 seconds
CO Fault
The CO cell has
reached the end of its
useable life or a fault
has occurred with
the CO detection
portion of the
detector
2 YELLOW
flashes
every 8
seconds
Chirp every 48 seconds
End Of Life
The detector has
been operational for
10 years and must be
replaced
5 YELLOW
flashes
every 12
seconds
Chirp every 48 seconds
Sensitivity
Drift/Dirty
Fault
The detector may no
longer alarm within
the smoke sensitivity
limits on the back of
the device and must
be cleaned
1 YELLOW
flash
every 8
seconds
Chirp every 48 seconds
Low Battery
The batteries are low
and must be replaced
1 YELLOW
flash
every 12
seconds
Chirp every 48 seconds
(press either button to
silence for 12 hours)
Fire Test
Fire test button
pressed and held to
initiate test
3 RED flashes
in time with
sounder
Temporal-3
BEEP-BEEP-BEEP-pause
CO Test
CO test button
pressed and held to
initiate test
4 RED flashes
in time with
sounder
Temporal-4
PIP-PIP-PIP-PIP-long
pause
Tamper
The detector has
been removed from
the base
1 YELLOW
flash followed
by
1 GREEN flash
every 12
seconds
None
Power Up
The detector has had
batteries installed
and is powered up
1 RED flash
followed by
1 YELLOW
flash followed
by
1 GREEN flash
A single chirp
Normal
Operation
The detector is
operating normally
with no fault or
alarm conditions
1 GREEN flash
every 12
seconds
None
Table 1 - Detector Status LED & Sounder Operating Modes
4.2 DETECTOR DIRTY FEATURE
When the detector has been contaminated and may no longer be within the
marked sensitivity limits the detector will chirp every 48 seconds and flash the
YELLOW LED once every 8 seconds. Refer to Section 10.1 for cleaning your
detector.
4.3 DETECTOR END OF LIFE
When the detector has reached the end of its 10 year operating life it will chirp
every 48 seconds and flash the YELLOW LED 5 times every 12 seconds. The
detector must be replaced.
4.4 LOW BATTERY DETECTION
The detector regularly checks the battery condition. If a low battery is detected the
detector will chirp every 48 seconds and flash the YELLOW LED once every 8
seconds. The chirp may be silenced for 12 hours by pressing either button (See
Section 2.1 Figure 1). The batteries must be replaced using 2 Panasonic CR123A
batteries or 2 Energizer EL123AP batteries.

5. BATTERY INSTALLATION AND REPLACEMENT
5.1 FIRST DETECTOR USE
The detector ships with batteries installed and a pull tab to prevent electrical
contact while in transit. Remove the pull tab before installing the detector.
Figure 4 - Pull Tab
5.2 BATTERY REPLACEMENT
To replace the batteries, remove the detector from the mounting base. Remove the
batteries from the detector, a flat bladed screwdriver may be used to help remove
the batteries, but care must be taken to ensure the batteries are not damaged. Wait
a minimum 20 seconds for the detector to power down completely. Install 2 new
Panasonic CR123A or Energizer EL123AP batteries, taking care to follow the
battery polarity indication on the detector next to the battery compartment. The
detector should flash RED, YELLOW, GREEN and chirp 8 seconds after the batteries
are installed. Return the detector to the mounting base, the detector should flash
GREEN every 12 seconds to indicate normal operation. Test the detector as
described in Section 9 FIELD SERVICE TESTS of this installation guide.
WARNING: CONSTANT EXPOSURES TO HIGH OR LOW TEMPERATURES OR HIGH
HUMIDITY MAY REDUCE BATTERY LIFE
6. PROGRAMMING TO CONTROL PANEL
Refer to the appropriate compatible control panel programming guide for the
proper procedure required to enroll the Wireless Combination Smoke, Heat and
Carbon Monoxide Detector into the system.
7. MOUNTING THE DETECTOR
7.1 RECOMMENDED LOCATIONS FOR SMOKE HEAT DETECTORS
According to National Fire Protection Association (NFPA) the major threat from
fire in a dwelling unit occurs at night when everyone is asleep. The principal threat
to persons in sleeping areas comes from fires in the remainder of the unit;
therefore, a smoke detector(s) is best located between the bedroom areas and the
rest of the unit. In units with only one bedroom area on one floor, the smoke
detector(s) should be located as shown in Figure 5. In dwelling units with more
than one bedroom area or with bedrooms on more than one floor, more than one
smoke detector is required, as shown in Figure 6.
Figure 5 - Location of the detectors in units with only one bedroom area on one floor
Remove pull tab
before installing
detector

Figure 6 - Location of the detectors in dwelling units with more than one bedroom area or with
bedrooms on more than one floor
In addition to smoke detectors outside of the sleeping areas, the device should be
installed on each additional story of the dwelling unit, including the basement.
These installations are shown in Figure 7. The living area smoke detector should be
installed in the living room or near the stairway to the upper level, or in both
locations. The basement smoke detector should be installed in close proximity to
the stairway leading to the floor above. Where installed on an open-joisted ceiling,
the detector should be placed on the bottom of the joists. The detector should be
positioned relative to the stairway so as to intercept smoke coming from a fire in
the basement before the smoke enters the stairway.
Smoke detectors are optional where a door is not provided between living room
and recreation room (Figure 8). The smoke from a fire generally rises to the ceiling,
spreads out across the ceiling surface, and begins to bank down from the ceiling.
The corner where the ceiling and wall meet is an air space into which the smoke
could have difficulty penetrating. In most fires, this dead air space measures about
0.1m (4in.) along the ceiling from the corner and about 0.1m (4in.) down the wall.
Detectors should not be placed in this dead air space, see Figure 9, Figure 10 and
Figure 11.
Where NOT to install the alarm:
•Directly above a sink, cooker, stove or oven
•Do not locate detector within 5 feet (1.5 m) of any cooking appliance
•Next to a door or window that would be affected by drafts i.e. extractor fan or
air vent
•Outside
•Do not install in any environment that does not comply with the detector’s
environmental specifications
•In or below a cupboard
•Where air flow would be obstructed by curtains or furniture
•Where dirt or dust could collect and block the sensor
•Where it could be knocked, damaged, or inadvertently removed
This detector shall not be installed in location where the normal ambient
temperature is below 40°F (4.4°C) or where it exceeds 100°F (37.8°C).
THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72:
NATIONAL FIRE ALARM AND SIGNALING CODE.
Figure 7 - Detector located on each story

Figure 8 - Split level arrangement
Figure 9 - Example of proper mounting for detectors
Figure 10 - Example of proper mounting for detectors with sloped ceilings
Figure 11 - Example of proper mounting for detectors with peaked ceilings

7.2 RECOMMENDED LOCATIONS FOR CARBON MONOXIDE DETECTORS
Ceiling Mounted - position at least 12" from any wall.
Wall Mounted - position at least 6" from ceiling, but not lower than a light switch.
Where to install, ideally:
•Within 10 feet (3m) of a sleeping area
•Inside the bedroom if it contains a fuel burning appliance
•On every floor of the building
•Ideally, install in any room that contains a fuel burning appliance
•If the appliance or the room is not normally used, such as the boiler room, the
detector should be placed just outside the room so the alarm can be heard
more easily
Figure 12 - CO Detector location diagram
Where NOT to install, ideally:
•Directly above a sink, cooker, stove or oven
•Do not locate detector within 5 feet (1.5m) of any cooking appliance
•Next to a door or window that would be affected by drafts i.e. extractor fan or
air vent
•Outside
•Do not install in any environment that does not comply with the detector’s
environmental specifications
•In or below a cupboard
•Where air flow would be obstructed by curtains or furniture
•Where dirt or dust could collect and block the sensor
•Where it could be knocked, damaged, or inadvertently removed
7.3 MOUNTING PROCEDURE
NOTE: The Wireless Combination Smoke, Heat and Carbon Monoxide Detector
should only be installed by a competent technician or installer.
NOTE: The Wireless Combination Smoke, Heat and Carbon Monoxide Detector
must not be used with a guard.
NOTE: DO NOT attach the detector to removable ceiling panels.
NOTE: Two warning labels are provided with the detector. One should be mounted
near the CO detector and the other near a source of fresh air where members of the
household will gather if the alarm signal sounds.
CAUTION: Airborne dust particles can enter the detector, remove the detector
before beginning construction work or other dust producing activity. Immediately
replace detector when dust producing activity has ceased.
WARNING: DO NOT PAINT Detector
Once a suitable location has been identified install the mounting base on the ceiling
or wall (if local ordinances permit) using the two screws and anchors provided
(Figure 13). Remove the battery pull tab (Section 5.1) and ensure the detector
powers up (Section 5.2). Fit the detector on the mounting base (Figure 14) and
turn clockwise until the detector clicks into place and the alignment notches are
aligned (Figure 15). Test the detector as described in Section 9 FIELD SERVICE
TESTS of this installation guide.

Figure 13 - Installing the base
Figure 14 - Detector aligned to base prior to completing installation
Figure 15 - Detector fully aligned and installed on mounting base
8. TAMPER PROTECTION
The Wireless Combination Smoke, Heat and Carbon Monoxide Detector has a built-
in tamper switch which will cause a tamper signal to be transmitted to the control
panel if the detector is removed from the mounting base. The detector also
includes an anti-tamper feature which prevents the detector being removed from
the mounting base. To enable the anti-tamper feature cut the anti-tamper tab on
the mounting base (Figure 16 and Figure 17) and install the detector on the
mounting base. When the anti-tamper feature has been enabled, to remove the
detector from the mounting base, a small screwdriver must be inserted in the anti-
tamper release hole (Figure 18) to press on the release lever whilst turning the
detector counterclockwise.
Alignment
marks
Alignment
marks

Figure 16 - Anti-Tamper locking tab
Figure 17 - Anti-Tamper locking tab removed
Figure 18 - Anti-Tamper release hole location
9. FIELD SERVICE TESTS
NOTE: Before testing, notify the central station that the detector system is
undergoing maintenance in order to prevent unwanted alarms. Testing the
detector will activate an alarm and send a signal to the panel. The test functions
cannot be used if the detector has a trouble or end-of-life condition. Detectors must
be tested after installation and following periodic maintenance.
The detector has two test buttons, one for smoke testing and one for CO testing
(See Section 2.1 Figure 1).
9.1 SENSITIVITY CHECK
Examine the detector and observe the LED, if the LED is blinking GREEN once every
12 seconds the detector is operating normally and sensitivity is within the marked
sensitivity range on the back of the detector. If the LED is blinking YELLOW every 8
seconds and beeping every 48 seconds it may no longer be within the marked
sensitivity range and should be cleaned. Refer to Section 10.1 for cleaning your
detector.
9.2 SMOKE ALARM TEST
Press and hold the fire test button (See Section 2.1 Figure 1) for 2 seconds, the
detector will sound Temporal-3 and the LED will blink RED along with the sounder.
Continue to press and hold the fire test button for up to 12 seconds to ensure the
smoke alarm signal is sent to the control panel. Verify the signal was received at
the control panel.
9.3 SMOKE ALARM FUNCTIONAL TEST
Using SDi SOLO A10, SDi Smoke Centurion or SDi Smoke Sabre canned smoke
products, according to the labeled instructions, spray canned smoke at the
detector. The detector will sound Temporal-3, the LED will blink RED along with
the sounder and the smoke alarm signal will be sent to the control panel. Verify the
signal was received at the control panel.
9.4 HEAT ALARM FUNCTIONAL TEST
Using a hair dryer of 1000-1500 Watts at a distance of approximately 12 inches
from the detector, direct hot air at the detector. The detector will sound Temporal-
3, the LED will blink RED along with the sounder and the heat alarm signal will be
sent to the control panel.
9.5 CO ALARM TEST
Press and hold the CO test button (See Section 2.1 Figure 1) for 2 seconds, the
detector will sound Temporal-4 and the LED will blink RED along with the sounder.
Continue to press and hold the CO test button for up to 12 seconds to ensure the CO
alarm signal will be sent to the control panel. Verify the signal was received at the
control panel.
Anti-Tamper
Locking Tab
Removed
Anti-Tamper
Locking Tab
Anti-Tamper
Release Hole

9.6 CO ALARM FUNCTIONAL TEST
After pressing and holding the CO test button for 12 seconds as in the previous
step, the detector will enter a CO GO/NO-GO test mode and the LED will blink
GREEN and BLUE for 2 minutes. While the detector is in the CO GO/NO-GO test
mode, using SDi SOLO C6 CO test gas, spray a small amount of CO test gas directly
into the gas entry port (See Section 2.1 Figure 1). The detector will sound
Temporal-4, the LED will blink RED along with the sounder and the CO alarm signal
will be sent to the control panel. Verify the signal was received at the control panel.
The CO test will automatically clear after testing, or after 2 minutes if no CO test gas
was used.
9.7 POST TESTING
If the detector fails to activate in any of the tests it should be cleaned, as outlined in
Section 10.1 of this manual, and the test should be repeated. If the detector still
fails to activate, return for servicing.
Once testing is complete, ensure the detector returns to normal operation mode
with the LED blinking GREEN every 12 seconds. If the detector is not in normal
operation, refer to Section 4.1 Table 1 - Detector Status LED & Sounder Operating
Modes to determine the detector state.
10. MAINTENANCE
TEST ONCE A WEEK
WARNING: USE ONLY BATTERIES SPECIFIED. USE OF DIFFERENT BATTERIES
MAY HAVE A DETRIMENTAL EFFECT ON THE DETECTOR.
YOUR DETECTOR SHOULD BE CLEANED AT LEAST ONCE A YEAR.
10.1 CLEANING
Remove the detector from the mounting base. Use a vacuum cleaner to vacuum
through the openings around the perimeter of the detector, or alternatively, use
compressed air to blow through the openings around the perimeter of the detector.
Wipe the detector clean with a damp cloth. Return the detector to the mounting
base.
11. FIRE DETECTION
WARNING: PLEASE READ CAREFULLY AND THOROUGHLY
•NFPA 72 states: Fire-warning equipment for residential occupancies are
capable of protecting about half of the occupants in potentially fatal fires.
Victims are often intimate with the fire, too old or too young, or physically or
mentally impaired such that they cannot escape even when warned early
enough that escape should be possible. For these people, other strategies such
as protection-in-place or assisted escape or rescue would be necessary.
•A battery powered alarm must have a battery of the specified type, in good
condition and installed properly.
•Smoke alarms must be tested regularly to make sure the batteries and the
alarm circuits are in good operating condition.
•Smoke alarms cannot provide an alarm if smoke does not reach the detector.
Therefore, smoke alarms may not sense fires starting in chimneys, walls, on
roofs, on the other side of a closed door or on a different floor.
•If the alarm is located outside the sleeping room or on a different floor, it may
not wake up a sound sleeper.
•Studies have shown that smoke and heat alarms may not awaken all sleeping
individuals, and that it is the responsibility of individuals in the household that
are capable of assisting others to provide assistance to those who may not be
awakened by the alarm sound or those who may be incapable of safely
evacuating the area unassisted.
•The use of alcohol or drugs may also impair one’s ability to hear the smoke
alarm. For maximum protection, a smoke alarm should be installed in each
sleeping area on every level of a home.
•Although smoke alarms can help save lives by providing an early warning of a
fire, they are not a substitute for an insurance policy. Homeowners and renters
should have adequate insurance to protect their properties.
FAMILY ESCAPE PLAN
According to National Fire Protection Association (NFPA) there often is very little
time between the detection of a fire and the time it becomes deadly. This interval
can be as little as 1 or 2 minutes. Planning and practicing for fire conditions with a
focus on rapid exit from the residence are important. Drills should be held so that
all family members know the action to be taken.
SAFETY TIPS

•Make a home escape plan. Draw a map of your home showing all doors and
windows. Discuss the plan with everyone in your home.
•Know at least two ways out of every room, if possible. Make sure all doors and
windows leading outside open easily.
•Have an outside meeting place (like a tree, light pole or mailbox) a safe distance
from the home where everyone should meet.
•Practice your home fire drill at night and during the day with everyone in your
home, twice a year.
•Practice using different ways out.
•Teach children how to escape on their own in case you can’t help them.
•Close doors behind you as you leave.
IF THE ALARM SOUNDS
•If the smoke alarm sounds, get out and stay out. Never go back inside for
people or pets.
•If you have to escape through smoke, get low and go under the smoke to your
way out.
•Call the fire department from outside your home. FOR MORE SAFETY
INFORMATION SEE THE WEBSITE: www.nfpa.org/education.
12. CARBON MONOXIDE GAS AND ITS DETECTION
CAUTION: This carbon monoxide detector is designed for indoor use only. Do not
expose to rain or moisture. Do not knock or drop the detector. Do not open or
tamper with the detector as this could cause malfunction. The detector will not
protect against the risk of carbon monoxide poisoning if not properly installed.
CAUTION: This device will only indicate the presence of carbon monoxide gas at
the sensor. Carbon monoxide gas may be present in other areas. This carbon
monoxide alarming device is designed to detect carbon monoxide gas from ANY
source of combustion. It is NOT designed to detect smoke, fire or other gases unless
the product has been investigated and determined to comply with applicable
requirements.
This device should not be installed as a substitute for proper installation, use, and
maintenance of fuel burning appliances, including appropriate ventilation and
exhaust systems. Carbon monoxide gas is a highly poisonous gas which is released
when fuels are burned. It is invisible, has no smell and is therefore impossible to
detect with the human senses. Under normal conditions in a room where fuel
burning appliances are well maintained and correctly ventilated, the amount of
carbon monoxide released into the room by appliances should not be dangerous.
Conditions that can result in transient CO situations:
1. Excessive spillage or reverse venting of fuel-burning appliances caused by
•outdoor ambient conditions, such as wind direction and/or velocity, including
high gusts of wind, and insufficient draft in the vent pipes,
•negative pressure differential resulting from the use of exhaust fans,
•simultaneous operation of several fuel-burning appliances competing for
limited internal air,
•loose vent pipe connections from fuel-fired appliances,
•obstructions, or unconventional vent pipe designs that can amplify the above
situations,
•poorly designed or maintained chimneys and/or vents,
2. Extended operation of unvented fuel-burning devices (range, oven, fireplace,
etc.),
3. Temperature inversions that can trap exhaust gases near the ground,
4. Car idling in an open or closed attached garage, or near a home.
The following symptoms are related to CARBON MONOXIDE POISONING and are to
be discussed with All members of the household:
1. Mild Exposure: Slight headache, nausea, vomiting, fatigue (often described as
"Flulike" symptoms).
2. Medium Exposure: Severe throbbing headache, drowsiness, confusion, fast
heart rate.
3. Extreme Exposure: Unconsciousness, convulsions, cardiorespiratory failure,
death.
4. Many cases of reported CARBON MONOXIDE POISONING indicate that while
victims are aware they are not well, they become so disoriented they are unable
to save themselves by either exiting the building or calling for assistance. Young
children and household pets are typically the first affected.

WARNING: IMPORTANT INFORMATION FOR THE USER
Individuals with medical problems may consider using warning devices which
provide audible and visual signals for carbon monoxide concentrations under 30
ppm.
WARNING
Actuation of your CO alarm indicates the presence of carbon monoxide (CO)
which can KILL YOU.
If alarm signal sounds:
1. Operate reset/silence button.
2. Call your emergency services (fire department or 911).
3. Immediately move to fresh air - outdoors or by an open door/window. Do a
head count to check that all persons are accounted for. Do not reenter the
premises nor move away from the open door/window until the emergency
services responders have arrived, the premises have been aired out, and
your alarm remains in its normal condition.
4. After following steps 1 - 3, if your alarm reactivates within a 24 hour
period, repeat steps 1 - 3 and call a qualified appliance technician (Telephone
Number) to investigate for sources of CO from fuel burning equipment and
appliances, and inspect for proper operation of this equipment. If problems
are identified during this inspection have the equipment serviced
immediately. Note any combustion equipment not inspected by the
technician and consult the manufacturers' instructions, or contact the
manufacturers directly, for more information about CO safety and this
equipment. Make sure that motor vehicles are not, and have not been,
operating in an attached garage or adjacent to the residence.
The premises should be well ventilated when household cleaning supplies or
similar contaminants are used.
DETECTOR REPLACEMENT
This detector is manufactured with a long-life carbon monoxide sensor. Over time
the sensor may lose sensitivity and may need to be replaced with a new carbon
monoxide detector. The detector’s lifespan is 10 years from the date of
manufacture.
NOTE: When the detector is removed from its base, a tamper message is sent to the
central station.
The detector will also cause a trouble condition once it has reached the end of its
useful life. If this occurs, it is time to replace the detector.
NOTE: Before replacing the detector, notify the proper authorities that
maintenance is being performed and the system will be temporarily out of service.
Disable the zone or system undergoing maintenance to prevent any unwanted
alarms. Dispose of the detector in accordance with any local regulations.
NOTE: The replacement date that appears on the device is the date beyond which
the device may no longer detect carbon monoxide accurately and should be
immediately replaced.
CAUTION
It should be noted the installation, operation, testing and maintenance of a carbon
monoxide detector is different to smoke detectors. Per NFPA 720 section 5.3.7.2 a
CO detector shall not be connected to a zone that signals a fire condition (i.e. smoke
detectors zones). Therefore, the carbon monoxide alarm signal must be
programmed as a non-fire zone. See the control’s installation instructions for the
appropriate carbon monoxide zone type to be programmed.
13. SPECIFICATIONS
•Transmitter Frequency: 345.000 MHz (crystal controlled)
•Dimensions: Ø 5’’ x 2.75’’ high (Ø 125mm x 70mm high)
•Weight (including battery): 10.5 oz (300 g)
•Color: White
•Audible Signal (ANSI Temporal 3/Temporal 4): 85dBA min. in alarm (at 10ft /
3m)
•Sensitivity: 2.00 –3.34%/foot obscuration
•Operating Temperature: 40°F to 100°F (4.4°C to 37.8°C)
•Operating Humidity: 15%-90% RH Non-Condensing
•Supplementary heat rating: 135°F
•Supplementary heat spacing rating: 70ft

•Battery (included): Two (2) Panasonic CR123A or Two (2) Energizer EL123AP
Lithium Batteries
•Regulatory Listing: Intertek ETL listed to UL 268 with supplementary heat
detection, UL 2075, ULC S529 with supplementary heat detection and ULCS588
standards
•Warranty: Two (2) years
•Included Accessories: Mounting Hardware Package
14. COMPATIBLE RF EQUIPMENT
14.1 MODEL 51000-600
Control Unit: Vivint CP04 (VS-SH2000-000) Doc 77-600022-001 –Rev A.2
Max Separation Range: 100 ft
14.2 MODEL 51000-601
Control Unit: Honeywell Lyric LCP500-L Doc 800-18078H 11/15 Rev. H
Max Separation Range: 100 ft
In typical single level and multilevel dwelling units and apartment buildings having
similar smoke alarm systems there is a possibility that signals sent by wireless
sensors may be blocked or reflected by metal before they reach the alarm Control
Panel, even if the signal path has been recently checked during a weekly test.
Blockage can occur if a metal object has been moved into the sensor’s signal path.
15. REGULATORY INFORMATION NOTICE
Unauthorized changes or modifications could void the user’s authority to operate
the equipment.
This device complies with Part 15 of the FCC Rules and Industry Canada license-
exempt RSS standard(s). Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesired
operation of the device. This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to Part 15 of FCC Rules. These limits
are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to
try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and the receiver
• Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
• Consult the dealer or an experienced radio/television technician for help
“For your information, The National Fire Alarm Code, NFPA 72, reads as follows:
“11.5.1 Required Detection.”
“Where required by applicable laws, codes, or standards for a specific type of
occupancy, approved single- and multiple-station smoke alarms shall be installed
as follows:
1. In a sleeping rooms and guest rooms
2. Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of any
door to a sleeping room, the distance measured along
a path of travel
3. On every level of a dwelling unit, including basements
4. On every level of a residential board and care occupancy (small facility),
including basements and excluding crawl spaces and unfinished attics
5. In the living area(s) of a guest suite
6. In the living area(s) of a residential board and care occupancy.
(Reprinted with permission from NFPA 72®, National Fire Alarm Code
Copyright © 2007 National Fire Protection Association, Quincy, MA 02269.
This reprinted material is not the complete and official position of the National Fire
Protection Association, on the referenced subject which is represented only by the
standard in its entirety.)
(National Fire Alarm Code® and NFPA 72® are registered trademarks of the
National Fire Protection Association, Inc., Quincy, MA 02269.)
APD0812 R1.6B
Other manuals for 51000-600
1
This manual suits for next models
1
Table of contents
Other Apollo Smoke Alarm manuals

Apollo
Apollo XPERT 8 User manual

Apollo
Apollo 51000-355 User manual

Apollo
Apollo XPA-CB-11170-APO User manual

Apollo
Apollo REACH WIRELESS RW1000-600APO User manual

Apollo
Apollo 65A Series User manual

Apollo
Apollo AlarmSense User manual

Apollo
Apollo Orbis A1R User manual

Apollo
Apollo REACH RW1000-660APO User manual

Apollo
Apollo Smoke Detector XP95 User manual

Apollo
Apollo Smoke Detector XP95 User manual