
TROUBLESHOOTING
DISPLAY IS BLANK
If Power LED is not illuminated at the equipment
control module check the following:
• Check circuit breaker and reset if necessary.
• Make sure power switch at heating & cooling
system is on.
• Make sure furnace door is closed securely.
HEATING SYSTEM DOES NOT RESPOND
(“HEATING” APPEARS ON SCREEN)
• Check for 24VAC at the equipment on the secondary
side of the transformer between power and
common. If voltage is not present, check the heating
equipment to find the cause of the problem.
• Check for 24VAC between the heat terminal (W)
and the transformer common. If 24VAC is present,
the thermostat is functional. Check the heating
equipment to find the cause of the problem.
• Check for loose or broken wires between the
thermostat and the heating equipment.
COOLING SYSTEM DOES NOT RESPOND
(“COOLING” APPEARS ON SCREEN)
• Check for 24VAC at the equipment on the secondary
side of the transformer between power and
common. If voltage is not present, check the cooling
equipment to find the cause of the problem
• Check for 24VAC between the cooling terminal (Y)
and the transformer common. If 24VAC is present,
the thermostat is functional. Check the cooling
system to find the cause of the problem.
• Check for loose or broken wires between the
thermostat and the cooling equipment.
FAN DOES NOT TURN ON IN A CALL FOR HEAT
• Check Installer Setting Fan Control In Heating /
Heat Pump Auxiliary Type, to make sure the fan
control is properly set to match the type of system.
HEAT PUMP ISSUES COOL AIR IN HEAT MODE,
OR WARM AIR IN COOL MODE
• Check wiring at the terminal block to confirm the
reversing valve is connected to the proper terminal.
O is active in cooling and B is active in heating.
HEAT/COOL BOTH ON AT SAME TIME
• Check Installer Setting Equipment Type, to make
sure it is set to match the installed heating/cooling
equipment.
• Check to make sure heating and cooling wires are
not shorted together.
HEATING EQUIPMENT IS RUNNING IN
COOL MODE
• Check Installer Setting Equipment Type, to make
sure it is set to match the installed heating/cooling
equipment.
“HEATING” IS NOT DISPLAYED
• Check Installer Setting Control Setup is set
correctly.
• Change the System Mode to Heat, and set
the temperature level above the current room
temperature.
“COOLING” IS NOT DISPLAYED
• Check Installer Setting Control Setup is set
correctly.
• Change the System Mode to Cool, and set
the temperature level below the current room
temperature.
INSTALLER MENU
USB SETTINGS
FILE IMPORT, ETC
THERMOSTAT &
HVAC SYSTEM
CONFIGURATION
HUMIDIFIER
CONFIGURATION
DEHUMIDIFIER
CONFIGURATION
EQUIPMENT
OUTPUT TESTS
IMPORT/EXPORT
USB INSTALLER
SETTINGS FILES,
FACTORY RESET
VENTILATION
CONFIGURATION
AIR CLEANER
CONFIGURATION
QUICK REFERENCE TO CONTROLS & DISPLAY
POWER/STATUS – On solid during normal operation. Flashes
when connection to the thermostat is lost and at power-up while
the thermostat connection is being established.
HEATING – On when heating outputs are active.
COOLING – On when cooling outputs are active.
FAN – On when fan output is active.
HUMIDIFIER – On when humidifier output is active.
DEHUMIDIFIER – On when dehumidifier output is active.
VENTILATION – On when ventilation output is active.
AIR CLEANING – On when air cleaner output is active.
EQUIPMENT CONTROL MODULE LEDs
THERMOSTAT FEATURES
• Remote access and control over Wi-Fi.
• Indoor air quality control.
– Humidification automatic or manual control.
– Dehumidification.
– Event-Based™air cleaning.
– Ventilation with temperature and humidity limits.
• Temperature control.
• Heat Blast®raises the room temperature 3°F to 5°F.
• One touch Away.
• Support for optional wireless outdoor temperature
sensor.
• Large touch screen with adjustable backlight.
• 7 day programmability.
• Displays room temperature, room humidity,
temperature setting, and optional outdoor temperature.
• Air filter, humidifier, dehumidifier, and HVAC service
reminders.
• Programmable fan control with fan circulation mode.
• Easy to use temperature control can override program
schedule at any time.
• Progressive recovery ensures proper temperature at
the start of a program event.
• Built in compressor protection prevents damage to
your equipment.
• System test mode.
English 1918 English