OPERATION-/FAULT INDICATOR
LSE-D16-24-BS
MANUAL
Safety regulations Mounting page 2
Schematics page 3
Control elements Technical data page 4
Programming page 5
Functionality page 7
www.aps-systems.ch
2
Safety regulations
Before the installation of the LSE-D16 Operation-/Fault indicator read these
instructions carefully and completely. Improper handling can result in severe
personal injury, substantial property damage or even death.
Cleaning
Before cleaning first disconnect the equipment from the mains. Do not use any
liquid cleaner or corrosive agent but solely a dampened cloth.
Installation
Installation work must be carried out by certified technical staff only. Follow the
instructions in this handbook. Observe the locally applicable regulations for the
safe and riskless handling of electrical installations
Supplementary power
Power supplies for the LSE-D16 Operation-/Fault indicator must comply with
the stipulations for safety extra-low voltage (SELV) given in IEC 346-4-41. We
recommend our power supplies of the EcoPower Series as they fulfil these
stipulations completely
Please note:
If the unit is supplied with AC the system outputs LT/LQ/HQ are disabled.
Switching on the system
The LSE-D16 Operation-/Fault indicator has no master switch: the system is
alive as soon as the power supply has been switched on.
A switch must be provided in the building installation as a cut-off device. The
switch must be labelled appropriately, must be in the vicinity of the equipment
and must be easily accessible to the user.
Mounting
Firstly, the front cut-out of 138 x 68 mm must be made. Then slide the LSE-
D16 Operation-/Fault indicator trough the cut-out and fix the mounting clips.
Finally, tighten the screws of the mounting clips.
All electrical connections are effected by the plug-in screw terminals
3
Schematics
*
The outputs LT (Lamp test), LQ (Lamp ack.) and HQ (Horn ack.) are only
enabled using a DC power supply. The LQ and HQ functions can be
customised, see the Programming chapter. The outputs are designed as a
current sink and are not potential-free. If potential-free contacts are required, a
relay must be utilised.
Wiring example for the LT output with an external relay:
4
Control elements
The following buttons are integrated in the front of the unit:
Horn acknowl.
The built-in buzzer and the horn output are
deactivated.
Lamp acknowl
All queued alarms are acknowledged
Lamp acknowl.
All LEDs as well as the lamp test output are
activated for 3 seconds.
Technical data
Indicator process
New value or first-up indicator
Signalling
16 DUO LED / integrated buzzer
Indicator inputs
16 inputs each, NO/NC operation/fault
Time delay
5s/10s/60s for all fault inputs, global
Automatic alarm acknowledgement
5s/10s/60s for all fault inputs, global
NO/NC
All operation –fault inputs, separate
System inputs
Horn / lamp test / common alarm
System outputs (DC operation onl.)
Horn ack. / alarm ack. / lamp test
Control elements
Horn ack. / alarm ack. / lamp test
Supply voltage
8-30VDC / 12-28.5VAC, 40-80Hz
Signal voltage
24V AC/DC ± 20%
Voltage system inputs
Analogue Supply voltage
Voltage system outputs
Current sink max. 30VDC
System output load
Max. 50mA
Power consumption
Max. 3W
Weight
260g
Dimensions WxHxD
72x144x75mm
Front panel cut out
138 x 68mm
Terminals
Plug-in screw terminals 0.2 -. 2.5mm2
Mounting position
Any
Protection degree housing
IP40
Protection connector
IP20
Temperature range
0 to 65°C
5
Programming
General
Using the controls in programming mode:
Icon
Description
Designation
Function in programming mode
Horn
acknowledgement
HQ
Navigation up
Alarm acknowledge
LQ
Switch
Lamp test
LT
Navigation down
The programming mode is started as follows: Power up the unit and push the
HQ and LT keys at the same time within 10 seconds. If no other keys are
pressed within 5 seconds, LSE-D16 will switch back to operating mode. If
additional keys are pressed, the programming mode remains active for 30
seconds. If no other key is pressed for 30 seconds, LSE-D16 will return to
operating mode and will take over the programming. The programming mode
can be ended by pushing the HQ and LT keys. The settings are saved.
Programming levels
LSE-D16 Operation-/Fault indicator has 3 programming levels:
1. Fault indicator inputs (red): Opening contact/closing contact
switchover
2. Operating inputs (green): Opening contact/closing contact
switchover
3. Virtual DIP switch: time delays and output modes
When the programming mode is activated, LSE-D16 Operation-/Fault indicator
starts at the level that was last used. The levels can be changed in active
programming mode using the HQ and LT navigation keys. If for example Level
2 is active on operating input 1, pushing the HQ keys switches the LSE-D16 -
/Fault indicator to level 1.
6
Level 1
Level 1 is used to set if the fault indicator inputs are a NO closing contact or a
NC opening contact. The green flashing LED signals the selected fault
indicator input. The LQ key is used to switch the function:
Red LED off = NO closing contact
Red LED on = NC opening contact
Level 2
Level 2 is used to set if the operating inputs are a NO closing contact or a NC
opening contact.The red flashing LED signals the selected operating input.
The LQ key is used to switch the function:
Green LED off = NO closing contact
Green LED on = NC opening contact
7
Level 3
Level 3 is used to set the following additional parameters:
Green LED = DIP-Switch off
Red LED = DIP-Switch on
LED
Status
Function
1
Off
All fault indicator inputs without switch-on delay
2
Off
1
On
All fault indicator inputs with 5s switch-on delay
2
Off
1
Off
All fault indicator inputs with 10s switch-on delay
2
On
1
On
All fault indicator inputs with 60s switch-on delay
2
On
3
Off
Inner buzzer on
3
On
Inner buzzer off
4
Off
Horn output as the image of the HQ key (active for 500ms)
4
On
Horn output as horn relay, active until HQ
5
Off
LQ output as the image of the LQ key (active for 500 ms)
5
On
LQ output as collective indicator
6
Off
According operation-LED suppressed whilst fault
6
On
According operation-LED not suppressed whilst fault
7
Off
Automatic alarm acknowledgement off
8
Off
7
On
Automatic alarm acknowledgement (AAA) during 5s after energising
8
Off
7
Off
Automatic alarm acknowledgement (AAA) during 10s after energising
8
On
7
On
Automatic alarm acknowledgement (AAA) during 60s after energising
8
On
9
Off
Handle pending alarms after the AAA as new alarm
9
On
Leave pending alarms acknowledged after the AAA
10
Off
Operate in ‘new value’ mode
10
On
Operate in ‘first value’ mode
11
Off
Keep status over power loss
11
On
Reset status at power loss
12
Aus
Horn output normally open NO (requires setting DIP 4 to on)
12
Ein
Horn output normally closed NC (requires setting DIP 4 to on)
13
Aus
LQ output normally open NO (requires setting DIP 5 to on)
13
Ein
LQ output normally closed NC (requires setting DIP 5 to on)
The functionality of the LSE-D16 Operation-/Fault indicator was enhanced
continuously. Older units do not cover all described functions.
Factory settings
In the factory settings all fault- and operating inputs are NO
The setting of all virtual DIP switches is “off”
8
Functionality
New value indicator
Each incoming fault is indicated through the flashing of its associated visual
indicator. When lamp acknowledgement is activated, the visual indicator goes
from a flashing- to a continuous light as long as that the fault is still present.
The visual indicator will extinguish if the fault was removed in the meantime.
Setting with DIP-Switch 10, see page 6.
First-up value indicator
If several alerts arise one after the other, or almost simultaneously, the
indicator will only flash for the alert which was the first to arrive. If an alert
becomes inactive before lamp acknowledgement, the visual indicator will
continue to flash until lamp acknowledgement takes place. Once this occurs,
the visual indicator will extinguish. All other alerts will be indicated with a
steady light as long as they remain present. When lamp acknowledgement is
activated, the visual indicator for the first alert that was saved becomes a
permanent light, as long as the fault is still present. The visual indicator will
extinguish if the fault was removed in the meantime. Setting with DIP-Switch
10, see page 6.
Automatic alarm acknowledgement AAA
The automatic alarm acknowledgement is used to suppress alarms after
energising the unit. The suppression time can be set to 5, 10 or 60 seconds.
This functionality is meant for machinery which is raising alarms after starting
because the operation state is not reached immediately. The treatment of
alarms which are still active after the suppression time can be chosen between
raising a new alarm or leave them acknowledged. Setting with DIP-Switch 7 -
10, see page 6.
08.20
APS systems AG
Neumatt 4
CH-4626 Niederbuchsiten Tel. +41 (0)62 517 88 33
Switzerland E-Mail: systems@aps-systems.ch www.aps-systems.ch

Other APS Measuring Instrument manuals

APS LSE-D16-BS User manual

APS

APS LSE-D16-BS User manual

APS VLS-8 Series Operating and installation instructions

APS

APS VLS-8 Series Operating and installation instructions

APS LSE-D16 User manual

APS

APS LSE-D16 User manual

APS LSE-D16-AB User manual

APS

APS LSE-D16-AB User manual

APS AS1210 User manual

APS

APS AS1210 User manual

APS M2000 Series User manual

APS

APS M2000 Series User manual

APS LSC Instruction Manual

APS

APS LSC Instruction Manual

APS 3A Series User manual

APS

APS 3A Series User manual

Popular Measuring Instrument manuals by other brands

Ranger 2150 Reference manual

Ranger

Ranger 2150 Reference manual

Awair Glow C AWAIR0PD2 quick start guide

Awair

Awair Glow C AWAIR0PD2 quick start guide

Brigade MDR 600 Series Installation and operation guide

Brigade

Brigade MDR 600 Series Installation and operation guide

palintest Micro 600 manual

palintest

palintest Micro 600 manual

OPTi CCA-TS2 Operator's manual

OPTi

OPTi CCA-TS2 Operator's manual

IBA KermaX-plus 120-131 E Oem manual

IBA

IBA KermaX-plus 120-131 E Oem manual

3nh NS810 manual

3nh

3nh NS810 manual

Thermo Scientific Orion 7070iX Installation and operation

Thermo Scientific

Thermo Scientific Orion 7070iX Installation and operation

Sony TC-366-4 Owner's instruction manual

Sony

Sony TC-366-4 Owner's instruction manual

Network Technologies Incorporated ENVIROMUX-2D Quick installation guide

Network Technologies Incorporated

Network Technologies Incorporated ENVIROMUX-2D Quick installation guide

Elcomponent PQPro user manual

Elcomponent

Elcomponent PQPro user manual

PCB Piezotronics IMI SENSORS TOM607A01 Installation and operating manual

PCB Piezotronics

PCB Piezotronics IMI SENSORS TOM607A01 Installation and operating manual

METREL EurotestXC MI 3152 instruction manual

METREL

METREL EurotestXC MI 3152 instruction manual

BYK haze-gard plus Operation

BYK

BYK haze-gard plus Operation

Tanita MC-980MA instruction manual

Tanita

Tanita MC-980MA instruction manual

Flexim FLUXUS WD Operating	 instruction

Flexim

Flexim FLUXUS WD Operating instruction

Movon MDSM-7 user manual

Movon

Movon MDSM-7 user manual

BIS VISTA operating manual

BIS

BIS VISTA operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.