AQ M-TECH HJCU-COM User manual

1/12
Heater Jacket
Control unit
Model HJCU-COM
Manual

2/12
Heater Jacket
CONTROL UNIT
Model HJCU-COM
Manual version 2.5
April 2020
AQ M-Tech AB

3/12
Table of contents
1. Manufactor information 4
CE Declaration of conformity 4
Limited Warranty 4
Warning 4
Manufacturer information 4
2. Check list 5
3. Introduction 5
Heater Jacket Control Unit 5
4. Installing Heater Jacket Control Unit 5
5. Rating signs 6
6. Connections 6
Connector connections 6
Alarm description 6
Replacing the supply cable 6
7. Replacing the Main Fuse 7
8. Regulator settings 7
Regulator descriptions 7
Temperature settings 7
Alarm outputs 7
Regulator communication 7
9. Dimensions and weight 7
10. Technical specification 8
11. Cleaning 8
12. Material selection 9
13. Accessories/ Spare parts 9
Control Unit 9
Fuses 9
Extension cables and alarm cables 9
Communication software 9
14. Dealer 10
15. Fault tracing 11

4/12
1. Manufactor information
AQ M-Tech AB operates a policy of on-going development and reserves the right to make changes
and improvements to any of the products described in this manual without prior notice.
Under no circumstances shall AQ M-Tech AB be held responsible for any loss or indirect damage howsoever
caused. The contents of this document are provided as it is. AQ M-Tech AB reserves the
right to revise this document or withdraw it at any time without prior notice.
CE Declaration of Conformity
Manufacturer: AQ M-Tech AB Sweden declares, that the product:
Heater Jacket Control Unit marked with CE-label conforms to the following standards:
EN 61000-6-2:2005, EN 61000-6-4:2007, WEEE Directive 2012/19/EU, RoHS Directive 2011/65/EU,
EN55011 (Group 1, Class B).
Limited Warranty
AQ M-Tech AB gives its end customers a warranty that the Heater Jacket Control Unit is free
from defects in its materials and operation for a period of one year from the date of purchase.
Should the Heater Jacket Control Unit show signs of manufacturing defects or material defects
during the warranty period, AQ M-Tech AB will repair or replace the defective product at no charge.
The warranty becomes void immediately should the Heater Jacket Control Unit, during the warranty
period, in any way be, modified, used incorrectly or be subject to tampering, abnormal working
conditions. Such as overheating or used in any other way than what is described in this manual.
The repair or replacement of other equipment in addition to the Heater Jacket Control Unit can
not be provided under the terms of this warranty.
The purchaser pays the carriage charges to AQ M-Tech AB. AQ M-Tech AB can in no way be
held liable by the purchaser for damage caused to any other equipment.
Warning
Ensure that the Heater Jacket Control Unit is connected to an earthed outlet socket.
Check the supply voltage in relation to Heater Jacket before connecting
The Heater Jacket is manufactured with different supply voltages. The supply voltage to the
Heater Jacket Control Unit is governed by the prescribed supply voltage for Heater Jacket.
When the supply voltage to the Heater Jacket Control Unit is changed, the
Heater Jacket must also be changed.
Always disconnect the voltage when working on the Heater Jacket Control Unit, for example
when replacing the fuse.
Use an exact type and size when replacing the fuse. See the “Technical Specification”
The Heater Jacket Control Unit may only be connected to an approved Heater Jacket
The Heater Jacket (Model HJSA...-..., HJSB...-...) must not be heated above 140C
When routing Heater Jacket cables, only cables provided by AQ M-Tech AB may be used.
The Heater Jacket Control Unit may only be connected to one Heater Jacket.
The Heater Jacket Control Unit is not approved for use in Ex-classified environments.
Manufacturer information
Manufacturer: AQ M-Tech AB
Adress: Bolandsgatan 10
SE-753 23 Uppsala
Sweden
Phone: +46 (0)18-470 29 00
Fax: +46 (0)18-10 50 04
Web: www.aqmtech.se
E-mail: [email protected]

5/12
2. Check list
This material is included in your shipment.
One “Heater Jacket Control Unit Communication”(HJCU-COM).
One “Heater Jacket” (HJSA ...-...or one HJSB ...-...)
One “Extension cable kit”, includes two cables each 2,5 meter (Temp & Heat cable)
One “Alarm” connector, “Alarm output” 4-way female
One “Mains” connector, Mains input power 3-way female
One “Communication” connector, Communication RS-485 4-way male
Two Spare fuses 5X20mm, one T 4,0A L/250VAC and one T 8,0A L/250VAC
One “Heater Jacket Control Unit” manual, model HJCU-COM
One “Heater Jacket” manual, model HJSA & HJSB
Three “E5CN Temperature Controller” manuals, six languages (ENG - JPN, DE - IT, FR - ES)
One “E5CN Temperature Controller Communication Event Input” manuals, six languages (ENG, DE, FR, JPN, IT, ES)
One “E5CN Temperature Controller Option Units” manuals (E53-CNQO3N), six languages (ENG, DE, FR, JPN, IT, ES)
IF TCViews are ordered this also includes
One TCViews Software
One TCViews Manual
3. Introduction Heater Jacket Control Unit
Heater Jacket Control Unit (HJCU) is designed for use together with one Heater Jacket (HJ).
HJCU monitors and controls the Heater Jacket temperature. The temperature on HJ1can easily
be altered. HJCU has two alarm outputs, upper limit and lower limit.
HJCU-COM communicates with RS-485.
4. Installing Heater Jacket Control Unit
Check the main fuse, make sure it’s of the correct value in relation to the mains voltage and conforms to
specifications for the HJ. See “Technical specification”.
Mount the HJCU on a vertical wall with screws intended for the supporting surface. Use the screw holes
under the cover screws.
Mount the HJCU so that the mains switch and regulator are not blocked.
Connect the HJ to the HJCU using “Extension cable kit”.
If used, connect the alarm cable to the HJCU. See “Alarm description” & “Technical specification”.
Fit the HJ as described in the manual “Heater Jacket HJSA & HJSB”
Connect Mains to the HJCU using the correct supply cable to an earthed electrical outlet socket.
Requisite knowledge is required.
Press the power switch. The equipment is now operational.
The default factory setting of SV2is 80ºC. SV can be changed within the range 30ºC to 140ºC
Should an error message be displayed on the regulator see the manual Omron E5CN Temperature controller.
In the event of a fault see “Fault tracing”
1. HJ = Heater Jacket, HJSA...-..., HJSB...-…
2. SV = Set value, Set working temperature.

6/12
1
2
3
5. Rating signs
Rating sign Connector Explanation
Heater 3-way female Supply to the Heater Jacket
Temp 2-way female Temperature detection on Heater Jacket
Alarm 4-way male Alarm 1 (HT)3and Alarm 2 (LT)4
Mains 3-way male Supply voltage to the Heater Jacket Control Unit
Communication 4-way female RS-485 and output 12VDC , 21mA
6. Connections
Connector connections
Name Connector type Connection Description
Heater Jacket 3-way female pin L & pin N Supply to the Heater Jacket
pin Earth connection
Temp input 2-way female pin 1 Temperature sensor on Heater Jacket
(PT100), A
pin 2 B & B
Alarm output 4-way male pin 2 & pin 3 Alarm 13(NO)
pin 1 & pin 3 Alarm 24(NO)
Mains 3-way male pin L & pin N Supply to the Heater Jacket Control Unit
pin Earth connection
Communication 4-way female pin 1 RS-485 (B)
pin 2 RS-485 (A)
pin 3 Output, +12VDC , 21mA
pin 4 Output, -12VDC , 21mA
Alarm description
Alarm outputs may be connected to external devices. Use the supplied connector for connection of alarms.
Use approved cables with an outside diameter of Ø6–8 mm, max wire area 1.5 mm2(see “Material selection”)
We can supply you with an Alarm cable (HJAC, se Accessories / Spare parts) with following connections:
Black to pin 1, Brown to pin 2 and Blue to pin 3.
Connection terminals for alarms connectors see the section “Connections”
For more information read the instructions in the manual for Omron E5CN Temperature controller.
Replacing the supply cable
Read the text in the section “Warning” before replacing the supply cable!
Also, remember that the earth wire should be the longest so that it releases last.
Replacing the supply cable: With 230 VAC connect: Black to L, Blue to N and Yellow/Green to .(Earth)
With 115 VAC connect: Black to L, White to N and Yellow/Green to .(Earth)
3. HT = High temperature alarm.
4. LT = Low temperature alarm.
Alarm 1
Alarm 2

7/12
Level Key
Mode Key
UP Key
Display 2
Shows SV
Set Value
7. Replacing the Main Fuse
Unplug the supply cable “Mains” from the HJCU.
Unscrew the cover on the HJCU.
Open the fuse holder, marked F1, pull the tab straight up using your forefinger, see figure 1.
Press out the fuse and replace with a new fuse Use the fuse size & type, according
to “Technical specification”. otherwise a fire or other danger can occur.
Press the fuse holder back into its original position.
A click should be heard
Screw on the cover on the HJCU
Plug-in the supply cable “Mains” to the HJCU.
Figure 1
8. Regulator settings
Regulator Description
Level key, change levels
MMode key, scroll parameters
DDown key, decrement the value shown on display 2
UUp key, increment the value shown on display 2
OUT1 OUT1 indicates HJ is heating
Temperature settings
Set value (SV) is initially set to 80C and is changeable with Up Key and Down Key.
Alarm outputs
Alarm 1: High temperature alarm Is initially set to: SV + 5C
Alarm 2: Low temperature alarm Is initially set to: SV - 5C
Regulator Communication
The communication connector on HJCU-COM can be connected to a PC (Personal Computer)
via a PC-Transformer5. TCViews is a logging program that gives the user a possibility to view 32 HJCU-COM
at the same time on a PC screen. TCViews provides you with a possibility to operate, monitor and change
temperature controller parameters. With TCViews you create projects, add users with different access rights,
change operating parameters, log and view data (temperature graphs according to time scale are available).
More information can be found in TCViews manual.
For further information about the regulator see the manual for Omron E5CN Temperature Controller.
For further information about the regulator communication see the manual for Omron E5CN Temperature
Controller Communication Event Input and Temperature Controller Option Unit E53-CNQ03N2.
9. Dimensions and weight
Item Width Height Depth Weight Item no.
mm mm mm kg
Heater Jacket Control Unit 125 175 110 1,3 HJCU
Heater Jacket Control Unit Communication 125 175 110 1,3 HJCU-COM
Heater Jacket Control Unit Current Com. 125 175 110 1,3 HJCU-COM-S
Display 1
Shows PV
Process Value
Actual temp. in HJ.
Output indication
Alarm indication
Down Key

8/12
5. PC-Transformer = Transforms Communication signal from HJCU-COM RS-485 to RS-232 for PC connection.
10. Technical specification
Connection voltage 115 VAC (100-120 VAC) 50/60 Hz 230 VAC (220-240 VAC) 50 Hz
Maximum power consumption 800 Watt 800 Watt
Temperature range (SV)630C –140C 30C –140C
Normal working temperature 30C –100C 30C –100C
Main fuse (FUSE, F1) T 8.0 A L/250VAC7, 5x20mm T 4.0 A L/250VAC8, 5x20mm
Output voltage 100-120 VAC 50-60 Hz 220-240 VAC 50 Hz
Protection class IP 65 IP 65
Working temperature +5C –+40C +5C –+40C
Alarm outputs (Relay output) High & Low, NO High & Low, NO
Maximum resistive load / alarm output 1A, 250 VAC 1A, 250 VAC
Communication RS-485 RS-485
11. Cleaning
The Heater Jacket Control Unit is cleaned using washing-up liquid on a slightly damp cloth.
12. Material selection
All devices & cables on the product are/shall be approved according to UL, CSA & CE.
6.SV = Set value, Set working temperature. Shown on the regulator's display.

9/12
7. Fuse supplied on delivery. Intended for Heater Jacket supply voltage. 100-120 VAC 50-60 Hz.
8. The fuse is fitted in the fuse holder on the Heater Jacket Control Unit. Intended for Heater Jacket supply voltage. 220-240 VAC 50 Hz
13. Accessories / Spare parts
Heater Jacket Control Unit
Item Model Size (WxLxH) Item no.
Control Unit 230/115 VAC 125x175x110 mm HJCU
Control Unit Communication 230/115 VAC 125x175x110 mm HJCU-COM9
Control Unit Current Com. 230/115 VAC 125x175x110 mm HJCU-COM-S10
Supply and alarm connector without cable is included.
Fuses
Item Model Size Connection voltage Item no.
Heater Jacket
Main fuse (Fuse, F1) 5x20 mm T 4.0 A L/250 Vac 230 VAC HJFT2
Main fuse (Fuse, F1) 5x20 mm T 8.0 A L/250 Vac 115 VAC HJFT4
Extension cables and alarm cables
Item Length Approval Type Item
designation number
Supply cable Control unit Sweden 2.0 metres CEE 7/VII Y003-B/B CCUS
Supply cable Control unit USA/Canada 2.4 metres UL817, CSA- TA-3/2.4mG/SVT CCUU
CC22.2n21
Extension cable kit Heater Jacket11 2.5 metres CE, UL, CSA Silflex, 3G1,0 HJEC-3M
Extension cable kit Heater Jacket11 5.0 metres CE, UL, CSA Silflex, 3G1,0 HJEC-5M
Extension cable kit Heater Jacket11 10.0 metres CE, UL, CSA Silflex, 3G1,0 HJEC-10M
Alarm Cable Heater Jacket 2.5 metres CE, UL, CSA Silflex, 3G1,0 HJAC-3M
Alarm Cable Heater Jacket 5.0 metres CE, UL, CSA Silflex, 3G1,0 HJAC-5M
Alarm Cable Heater Jacket 10.0 metres CE, UL, CSA Silflex, 3G1,0 HJAC-10M
Communication software
Item Designation Item number
TCViews PC Logging software COM-Views

10/12
9. HJCU-COM –Communication with RS-485
10. HJCU-COM-S –Communication with 4-20mA DC
11. The cable kit includes 2 cables (Temp & Heater cables).
14. Dealer
Sweden
Dealer: AQ M-Tech AB
Adress: Bolandsgatan 10
SE-753 23 Uppsala
Sweden
Phone: +46 (0)18-470 29 00
Fax: +46 (0)18-10 50 04
Web: www.aqmtech.se
E-mail: [email protected]

11/12
15. Fault tracing
Problem
Probable cause
Corrective action12
The E5CN regulator on the
HJCU does not start
Power switch not pressed in
No voltage
Fuse blown in the HJCU
Faulty regulator
Press the power switch
Check the incoming voltage
Change the main fuse in the HJCU
(F1)
Contact the dealer
HJ does not become warm
Power switch not pressed in
No voltage
Fuse blown
HJCU or HJ faulty
Press the power switch
Check the incoming voltage
Change the main fuse in the HJCU
(F1)
Contact the dealer
Error message on the E5CN
regulator
(s.err)
Faulty cable connection HJ
Short circuit in HJ
Faulty cable connection Temp
Check the connection
Contact the dealer
Check the connection
HJ becomes significantly
warmer than the set value
Faulty temp element
Faulty overheating cut-out
HJCU
Contact the dealer
Contact the dealer
Contact the dealer
No alarm on the alarm output
Faulty cable connection
Faulty setting on the E5CN
regulator
Check the connection
Check the settings, see the
Manual for Omron E5CN
Temperature controller

12/12
12. The Heater Jacket Control Unit must be disconnected from the main supply when working inside the enclosure.
Table of contents