Arcus-EDS KNX-IMPZ2-SK01 User manual

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
Product Page
KNX-IMPZ2 2 Channel Impulse Counter
Page 1
Impuls Counting Module KNX-IMPZ2 Product Group 1
Application : Integration of consumtion meters with impulse outputs into the KNX bus.
The IMPZ2 can be operated as two separate counters or as a counter having two scales.
The counter inputs run on the S0-Interface by default according to DIN EN 62053-31 but can also be connected with a
potential-free contact.
Product Data Base: IMPZx.vd4
KNX Readable Data: Accumulated consumption
Instantaneous consumption
Current time
Current date
Last reference value
Last reference date
Next reference date
Consumption value
Consumption Reset
Consumption reset date
Consumption reset time
Serial number
KNX-IMPZ2 Article Article Description Article No.
KNX Document: 5200_ex_IMPZ2.pdf
KNX-IMPZ2
-SK01
2 Channel S0-counter module
SK01 plastic housing: 72 x 64 x 40 mm
IP54
60201201
KNX-IMPZ2
-REG
2 Channel S0-counter module
REG-housing: 2TE (35 mm)
IP20
60201202
1. Application Description 2
5. Product Page 13
2. KNX Parameter 2
6. Technical Data 14
3. KNX Objects 8
7. Startup 15
4. Notes 12
8. Mounting 15
Imprint
S
e
it
e
1
›
»

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 2
1 Application Description
Operating Principles and Areas of Application
The consumption counter by Arcus-EDS GmbH consists of a counter module with a backup battery for data storage and a
KNX bus coupler for remote reading and monitoring of consumption data.
The counter inputs are specified with DIN EN 62053-31 S0-interfaces but can also be connected with a potential-free contact.
The two counting values can be two different meters or one meter with 2 tariffs. Switching the tariffs is done through the second
input or over KNX.
The IMPZ2 can be used as two independent counters or a counter having two scales can be operated by a switched object.
KNX sensors are set up using the ETS Tool Software in conjuction with the associated application program.
The device is delivered unprogrammed.
All functions are parameterized and programmed with ETS.
Functions, 2 Independent Counter
• Meter reading(Channel 1/2)
• Flow(Channel 1/2)
• Reference value(Channel 1/2)
• Consumption value(Channel 1/2)
• Serial number(Channel 1/2)
• Limit alarm(Channel 1/2)
• Date and Time
• Last reference date
• Next reference date
• Consumption value reset
• Reset time
• Reset date
Functions, Counter with 2 Tariffs
• Meter reading ( Scale 1/2 )
•Flow
• Reference value (Scale 1/2 )
• Consumption value ( Scale 1/2 )
• Serial number
• Scale switching
• Limit alarm ( Scale 1/2 )
• Date and Time
• Last reference date
• Next reference date
• Consumption value reset
• Reset time
• Reset date
2 KNX Parameter
2.1. General Settings 3
2.2. Parameter - 2 Independent Counter 4
2.3. Parameter - 1 Counter with 2 Scales 6
S
e
it
e
2
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 3
2.1 General Settings
General Settings - KNX-IMPZ2
Parameter Setting Description
Use Daylight Saving Time • no
• yes
Automatic daylight saving time
Reset-PIN
( 0 without Pin )
0 .. 65535 A “PIN" can be assigned in order to prevent unauthorized
persons from resetting the consumption value. In order to reset
the consumption value, that “PIN" must be confirmed. This
feature is deactivated if the assigned “PIN" is “zero".
Type of Counter 2 Independent Counters
1 Counter with 2 Scales
There are two types of counters available
If Flowrate drops Send nothing
Send value “zero“
If the current consumption goes to zero, this can be indicated by
sending a zero value on the object No.2.
Use Limit Profile yes
no
Limits are (not) used.
S
e
it
e
3
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 4
2.2 Parameter - 2 Independent Counter
Parameter - 2 Independent Counter - KNX-IMPZ2
Parameter Setting Description
Sending Values Cyclically • send nothing
• 1 .. 120 Minutes
Measured values will be sent in the preset cycle time. If cyclical
sending is disabled, measured values will only be sent if changes
in measured values occur. A minimum interval of 10 seconds is
maintained in order to restrict bus load.
Count per Unit 0 .. 99 Impulse value must be set to the counter. The value to be set can
be calculated from the impulse value of the counter.
See 4 Notes “Settings the Pulse Rating”
Exponent Exponent of ten
of
10^-10 .. 10^10
The value to be set can be calculated from the parameter value
"Counts per Unit" and the display unit.
See 4 Notes “Settings the Pulse Rating”
Preset Counter Value
( 0 - no changes )
0 .. 4.294.967.295 If there is a difference between the value displayed in the
cyclometer register and the object value 0/1 “Count of channel 1/
Channel 2", the counter can be synchronized. All impulses
already counted will be entered.
Example: A consumption of 12.553 cbm and 1 imp/l equal a
correction value of 12553.
S
e
it
e
4
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 5
Type of Flow Rate
Measurement
Volumetric Flow
Power Rating
It will be set whether flow or power is measured.
Flow Measurement Period Per Second
Per Minute
Per Hour
Per Day
Adjustment of the time base taken for the output of the amount of
energy or the volumetric flow.
Use of Limit 1 Value limit
Upper limit flow
Lower limit flow
Consumption value limit
The values are determined using the parameter sets “Limit 1"
and the corresponding “Exponent".
Limit 1 0 .. 99 Limit setting
[Exponent] Exponent of ten
of
10^-10 .. 10^10
Use of limit 2
limit 2
[Exponent]
Settings for limit value 2
Parameter - 2 Independent Counter - KNX-IMPZ2 ( continue )
Parameter Setting Description
S
e
it
e
5
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 6
2.3 Parameter - 1 Counter with 2 Scales
Parameter - 1 Counter with 2 Scales - KNX-IMPZ2
Parameter Setting Description
Sending Values Cyclically • Do Not Send
• 1 .. 120 minutes
Measured values will be sent in the preset cycle time. If cyclical
sending is disabled, measured values will only be sent if changes
in measured values occur. A minimum interval of 10 seconds is
maintained in order to restrict bus load.
Impulse value 0 - 99 Impulse value must be set to the counter. The value to be set can
be calculated from the impulse value of the counter.
See 4 Notes “Settings the Pulse Rating”
S
e
it
e
6
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 7
[ Exponent ] Exponent of ten
of 10^-10 .. 10^10
The value to be set can be calculated from the parameter value
“Counts per unit“ and the display unit.
See 4 Notes “Settings the Pulse Rating”
Preset Counter
Value Scale 1/2
( 0 - no change )
0 .. 4.294.967.295 If there is a difference between the value displayed in the
cyclometer register and the object value 0/1 “ Count Scale x“, the
counter can be synchronized. All impulses already counted will be
entered.
Example:
A consumption of 12.553 cbm and 1 imp/l equal a correction value
of 12553.
Type of Flow Rate
Measurement
Volumetric Flow
Power Rating
it is set whether flow or power is measured.
Flow Measurement Period Per Second
Per Minute
Per Hour
Per Day
Adjustment of the time base taken for the output of the amount of
energy or the volumetric flow.
Use of Limit 1 Scale 1 Value limit
Upper limit flow
Lower limit flow
Consumption value limit
The values are determined using the parameter sets “Limit 1
Scale 1" and the corresponding “Exponent".
Limit 1 Scale 1 0 .. 99 Limit setting
[ Exponent ] Exponent of ten
of 10^-10 .. 10^10
Exp.Limit 2 scale 1
Limit 2 Scale 1
[Exponent]
Settings for limit value 2
scale 1
Settings for limit 2 scale 1
Exp.Limit 1 scale 2
Limit 1 Scale 2
[ Exponent ]
Settings for limit value 1
scale 2
Settings for limit 1 scale 2
Exp.Limit 2 scale 2
Limit 2 Scale 2
[ Exponent ]
Settings for limit value 2
scale 2
Settings for limit 2 scale 2
Parameter - 1 Counter with 2 Scales - KNX-IMPZ2 ( continue )
Parameter Setting Description
S
e
it
e
7
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 8
3 KNX Objects
3.1 Objects - 2 Independent Counter
3.1. Objects - 2 Independent Counter 8
3.2. Objects - 1 Counter with 2 Scales 10
Objects - 2 Independent Counter - KNX-IMPZ2
No. Name Data Point Type Function
0 Meter reading channel 1 DPT 14.* 4 Byte Meter reading
1 Meter reading channel 2 DPT 14.* 4 Byte Meter reading
2 Capacity / Volumetric flow channel 1 DPT 14.* 4 Byte Calculated flow
3 Capacity / Volumetric flow channel 2 DPT 14.* 4 Byte Calculated flow
4 Reference value channel 1 DPT 14.* 4 Byte Consumption for
the last reference
date
5 Reference value channel 2 DPT 14.* 4 Byte Consumption for
the last reference
date
6 Consumption value channel 1 DPT 14.* 4 Byte consumption
value
7 Consumption value channel 2 DPT 14.* 4 Byte consumption
value
8 Serial number channel 1 DPT 16.000 String(ASCII) 14 Byte Serial number
9 Serial number channel 2 DPT 16.000 String(ASCII) 14 Byte Serial number
10 Limit alarm channel 1 DPT 1.001 Switch 1 Bit Limit
11 Limit alarm channel 2 DPT 1.001 Switch 1 Bit Limit
12 Current time DPT 10.001 time 3 Byte time
13 Current date DPT 11.001 date 3 Byte date
14 Last reference date DPT 11.001 date 3 Byte Reference date
15 Next reference date DPT 11.001 date 3 Byte Reference date
16 Consumption reset DPT 7.001 Pulse 2 Byte Consumption
value reset
17 Consumption reset time DPT 10.001 time 3 Byte Reset time
18 Consumption reset date DPT 11.001 date 3 Byte Reset date
19 Alarm Profile DPT 1.001 Switch 1 Bit Select time
S
e
it
e
8
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 9
Object Description - 2 Independent Counter - KNX-IMPZ2
No. Name Description
0
1
Meter reading channel 1
Meter reading channel 2
Corresponds to the current meter reading ( total consumption )
2
3
Volumetric flow channel 1
Volumetric flow channel 2
Current capacity in kWh per time unit or Volumetric flow in cbm per
time unit. The time unit can be set using the parameter “Flow
measurement period".
4
5
Reference value channel 1
Reference value channel 2
Meter reading on the last reference date at 0:00 am.
6
7
Consumption value channel 1
Consumption value channel 2
The amount consumed since the last consumption value reset
8
9
Serial number channel 1
Serial number channel 2
The unique serial number ( e.g. serial number of the counter ).
10
11
Limit alarm channel 1
Limit alarm channel 2
It will be set if limit is reached. ( see “General settings", “Use limits"
and object 19 “Alarm profile")
12 Current time Corresponds with internal time
13 Current date Corresponds with internal date
14 Last reference date The date when the last reference value was saved at 0:00 am.
15 Next reference date The date when the next reference value will be saved at 0:00 am.
16 Consumption reset Consumption value will be set to “zero“ , the objects “Consumption
reset time“ and “Consumption reset date" will be refreshed and
saved. If “Reset-PIN“ in “General Settings“ is other than “zero“, this
“PIN" must be used in order to actuate a reset. If “Reset-PIN“ is set
to “zero“, a different “PIN“ other than “zero“ must be used in order
to actuate a reset.
17 Consumption reset time The time when the last consumption reset was carried out.
18 Consumption reset date The date when the last consumption reset was carried out.
19 Alarm Profile This object is only used if the parameter “Use Limit Profile" in the
“General settings" is set to “Yes". If the setting is “ZERO", the
parameterized “Limit 1" will actuate the setting of the object “Limit
alarm". If the setting is “ONE", the parameterized “Limit 2" will
actuate the setting of the object “Limit alarm".
S
e
it
e
9
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 10
3.2 Objects - 1 Counter with 2 Scales
Objects - 1 Counter with 2 Scales - KNX-IMPZ2
No. Name Data Point Type Function
0 Scale value 1 DPT 14.* 4 Byte Meter reading
1 Scale value 2 DPT 14.* 4 Byte Meter reading
2 Capacity / Volumetric flow DPT 14.* 4 Byte Calculated flow
4 Reference value scale 1 DPT 14.* 4 Byte Consumption for
the last reference
date
5 Reference value scale 2 DPT 14.* 4 Byte Consumption for
the last reference
date
6 Consumption value scale 1 DPT 14.* 4 Byte Consumption
value
7 Consumption value scale 2 DPT 14.* 4 Byte Consumption
value
8 Serial number DPT 16.001 String(ASCII) 14 Byte Serial number
9 Selected scale DPT 1.001 Switch 1 Bit Scale
10 Limit alarm scale 1 DPT 1.001 Switch 1 Bit Limit
11 Limit alarm scale 2 DPT 1.001 Switch 1 Bit Limit
12 Current time DPT 10.001 Time 3 Byte Time
13 Current date DPT 11.001 Date 3 Byte Date
14 Last reference date DPT 11.001 Date 3 Byte Reference date
15 Next reference date DPT 11.001 Date 3 Byte Reference date
16 Consumption reset DPT 7.001 Pulse 2 Bit Consumption
value reset
17 Consumption reset time DPT 10.001 Time 3 Byte Time reset
18 Consumption reset date DPT 11.001 Date 3 Byte Date reset
19 Alarm Profile DPT 1.001 Switch 1 Bit Select limit
Objects description - 1 Counter with 2 Scales - KNX-IMPZ2
No. Name Description
0
1
Scale value 1
Scale value 2
Corresponds to the current meter reading ( total consumption ).
2 Volumetric flow Current consumption per unit time parameterized.
4
5
Reference value scale 1
Reference value scale 2
Meter reading on the last reference date at 0:00 am.
S
e
it
e
10
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 11
Following Objects can be Sent to
6
7
Consumption value scale 1
Consumption value scale 2
The consumed amount since the last consumption value reset.
8 Serial number The unique serial number (e.g. serial number of the counter).
NOTE: Can be written only once.
9 Selected scale Counter switch (scale 1 / scale 2)
10
11
Limit alarm scale 1
Limit alarm scale 2
It will be set if limit is reached.
The “object 19 : Alarm profile”determines which limit would be applied.
12 Current time Current time
13 Current date Current date
14 Last reference date The date when the last reference value was saved at 0:00 am.
15 Next reference date The date when the next reference value will be saved at 0:00 am.
16 Consumption reset Consumption value will be set to “zero" , the objects “Consumption
reset time" and “Consumption reset date" will be refreshed and
saved.
If “Reset-PIN" in “General Settings" is other than “zero", this “PIN"
must be used in order to actuate a reset.
If “Reset-PIN" is set to “zero", a different “PIN" other than “zero"
must be used in order to actuate a reset.
17 Consumption reset time The time when the last consumption value reset was carried out.
18 Consumption reset date The date when the last consumption value reset was carried out.
19 Alarm Profile This object is only used if the parameter “Use Limits" in the “General
settings" is set to „Yes".If the setting is “ZERO", the parameterized
“Limit 1" will actuate the setting of the object “Limit alarm". If the
setting is “ONE", the parameterized “Limit 2" will actuate the setting
of the object “Limit alarm".
At both settings, please pay also attention to the value of the object 9 :
“Selected scale".
When setting “Selected scale" = “ZERO", limit 1/2, scale 1 is in use.
When setting “Selected scale" = “ONE", limit 1/2, scale 2 is in use.
Objects description - 1 Counter with 2 Scales - KNX-IMPZ2 ( continue )
No. Name Description
S
e
it
e
11
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 12
4 Notes
Settings the Pulse Rating
For example, Water
For example, Current
For example, Gas
Impulse Value
Counter
Impulse / Unit
in ETS
Exponent in ETS
Display in m3
1 Imp. / 1 Liter 1 3
1 Imp. / 10 Liter 1 2
1 Imp. / 25 Liter 4 1
1 Imp. / 50 Liter 2 1
1 Imp. / 100 Liter 1 1
Impulse Value
Counter
Impulse / Unit
in ETS
Exponent in ETS
Display in kWh
500 Imp. / kWh 5 2
1000 Imp. / kWh 1 3
2000 Imp. / kWh 2 3
5000 Imp. / kWh 5 3
10.000 Imp. / kWh 10 3
Impulse Value
Counter
Impulse / Unit
in ETS
Exponent in ETS
Display in m3
1 Imp. / 0,001m3 13
1 Imp. / 0,01m3 12
1 Imp. / 0,025 m3 41
S
e
it
e
12
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Product Page
KNX-IMPZ2 2 Channel Impulse Counter
Page 13
5 Product Page
The Counter-Module KNX-IMPZ2 is used for remote reading and monitoring of
metering data
The module is suitable to detect measured values of heat-, water-, current- and
gas meters with S0-Interface.
The IMPZ2 can be used as two independent counters or be used as one
counter with scales switching.
The device has an integrated bus coupling unit and needs no auxiliary power.
The Counter-Module KNX-IMPZ2-SK01 is delivered in an impact-resistant
glass-ball reinforced plastic housing with seal and meet the protection class
IP54.
The Counter-Modul KNX-IMPZ2-REG is suitable for DIN rail mountingand meet
the IP20 degree of protection
Areas of Application
• General monitoring of consumption values
Article-No.: 6020120x
KNX-IMPZ2
2 Channel Impuls Counter
SK01 IP54
REG IP20
The counter inputs run on the S0 interface by default.
( according to the DIN 43864) but can also be connected with a
potential free contact.
Operating Temperature: -20 .. +55 °C
Storage Temperature: -20 .. +85 °C
Operating Voltage: 21 .. 32VDC
Power Consumption: ca. 240mW ( at 24VDC )
Protection Class:
KNX-IMPZ2-SK01: IP54
KNX-IMPZ2-REG: IP20
S
e
it
e
13
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Product Page
KNX-IMPZ2 2 Channel Impulse Counter
Page 14
6 Technical Data
Technical Data - KNX-IMPZ2
Operating Voltage KNX bus voltage 21 .. 32 VDC
Power Consumption ca. 240 mW ( at 24VDC )
Auxiliary Supply not required
Bus Coupler integrated
Behaviour on bus voltage failure Modified auxiliary storage size is configurable
Ambient temperature Storage: -20 .. +85 °C
Operation: -20 .. +55 °C
Start-up with ETS IMPZx.vd4
Connections KNX 2-pole clamps ( red / black )
Protection Class SK01 IP54
Assembly Type SK01 Assembly with 2 screws finery
Casing Type SK01 Plastic housing grey
Casing Dimensions SK01 72 x 64 x 40 mm ( B x H x T )
Article Number SK01 60201201
Protection Class REG IP20
Assembly Type REG DIN rail mounting
Casing Dimensions REG 2 TE ( 35 mm )
Article Number REG 60201202
S
e
it
e
14
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Product Page
KNX-IMPZ2 2 Channel Impulse Counter
Page 15
7 Startup
The KNX Sensor is set up using the ETS Tool Software and the applicable application program.
The sensor is delivered unprogrammed.
All functions are programmed and parameterized with ETS.
Please read the ETS instructions.
8 Mounting
The counter module KNX IMPZ2-SK01 is designed for outdoor installation and for (damp) area.
It conforms to the protection class IP54.
It is mounted with two screws on the wall.
The cover of the device can be removed by loosening the screws on the top.
First attach the sensor to the wall or ceiling, then insert the KNX Bus cable into the slot on the side
of the casing ( PG Connection ).
Detach the bus clamp from the device, attach the cable and replace the clamp onto the board.
After programming the device successfully,the housing cover must be closed.
Be careful not to damage the electronic parts with tools and cable ends.
The Counter Module KNX-IMPZ2-REG is intended for DIN rail mounting.
It conforms to protection class IP20.
KNX-IMPZ2 Connection view
Programming Button
KNX Terminal Block
S0-Interfaces
Programming LED
Programming Button
Programming LED
KNX Terminal Block
S
e
it
e
15
›
‹
»
«

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915 e4
Subject to change
arcus-eds
I
KNX
SM
IMPZ2
Smart Metering
Product Page
KNX-IMPZ2 2 Channel Impulse Counter
Page 16
Behaviour on bus voltage recovery
The controller’s outputs start with their current values and the ETS parameter settings are retained.
Delete Program and Reset Sensor
In order to delete the programming ( configuration ) or to reset the module back to delivery status, it must be switched to zero
potential ( disconnect the KNX bus terminal ).
Press and hold the programming button while reconnecting the KNX bus coupler and wait until the programming LED
lights up ( approx. 5-10 seconds ).
Now you can release the programming button.
The module is ready for new configuration now.
If you release the programming button too early, repeat the procedure.
S
e
it
e
16
›
‹
«
»

Arcus-EDS GmbH Rigaer Str. 88 , 10247 Berlin Tel.: +49 / (0)30 / 2593 3914
www.arcus-eds.de x [email protected] Fax.: +49 / (0)30 / 2593 3915
Subject to change
arcus-eds
I
KNX
Imprint
Editor: Arcus-EDS GmbH, Rigaer Str. 88, 10247 Berlin
Responsible for the contents: Hjalmar Hevers, Reinhard Pegelow
Reprinting in part or in whole is only permitted with the prior permission of Arcus-EDS GmbH.
All information is supplied without liability. Technical specifications and prices can be subject to change.
Liability
The choice of the devices and the assessment of their suitability for a specified purpose lie solely in the responsability of the
buyer. Arcus-EDS does not take any liability or warranty for their suitability. Product specifications in catalogues and data sheets
do not represent the assurance of certain properties, but derive from experience values and measurements. A liability of Arcus-
EDS for damages caused by incorrect operation/projecting or malfunction of devices is excluded. The operator/project developer
has to make sure that incorrect operation, planning errors and malfunctions cannot cause subsequent damages.
Safety Regulations
Attention! Installation and mounting must be carried out by a qualified electrician.
The buyer/operator of the facility has to make sure that all relevant safety regulations, issued by VDE, TÜV and the responsible
energy suppliers are respected. There is no warranty for defects and damages caused by improper use of the devices or by non-
compliance with the operating manuals.
Warranty
We take over guarantees as required by law.
Please contact us if malfunctions occur. In this case, please send the device including a description of the error to the company's
address named below.
Manufacturer
Registered Trademarks
The CE trademark is a curb market sign that exclusively directs to autorities and does not include any
assurance of product properties.
Registered trademark of the Konnex Association.
S
e
it
e
17
‹
«
This manual suits for next models
1
Table of contents
Popular Cash Counter manuals by other brands

Apodemus
Apodemus BatCounter manual

Autonics
Autonics LA8N Series quick start guide

HYOSUNG
HYOSUNG NH-2700CE Operator's manual

Conrad
Conrad 75 50 02 operating instructions

Mirion Technologies
Mirion Technologies S6LB installation manual

Spectris
Spectris Particle Measuring Systems Ultra DI 50 Operation manual