Argo AE2MI56AH User manual

85264189902000
Contents Page
IMPORTANT!
Please Read Before Starting .................................. 1
1. GENERAL.......................................................... 2
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Unit
1-3. Optional Copper Tubing Kit
1-4. Type of Copper Tube and Insulation Material
1-5. Additional Materials Required for Installation
2. INSTALLATION SITE SELECTION ................... 3
2-1. Indoor Unit
2-2. Embedding the Tubing and Wiring
3. HOW TO INSTALL THE INDOOR UNIT............ 9
3-1. Remove the Rear Panel from the Unit
3-2. Make a Hole
3-3. Install the Rear Panel on the Wall
3-4. Remove the Grille to Install the Indoor Unit
3-5. Shape the Indoor Side Tubing
3-6. Wiring Instructions
3-7. Wiring Instructions for Inter-unit Connections
3-8. Mounting
3-9. Drain Hose
4. HOW TO SECURE THE WIRELESS REMOTE
CONTROL UNIT................................................ 18
4-1. Mounting on a Wall
5. ADDRESS SETTING OF THE REMOTE
CONTROL UNIT................................................ 19
5-1. Setting the Remote Controller Address
5-2. Operating Multiple Indoor Units with a Single
Remote Controller
6. TEST RUN......................................................... 20
7. INSTALLATION CHECK SHEET...................... 20
Model Combinations
Combine indoor and outdoor units only as listed
below.
Indoor Unit Outdoor Unit
AWMI28AHL AE2MI56AH
AWMI36AHL AE3MI70AH
AWMI50AHL AE4MI91AH
AWMI70AHL
Power Source:
50 Hz, single-phase, 220 – 240 V / 60 Hz,
single-phase 220 V
Combinations of indoor and outdoor units
Connect indoor and outdoor units only in the com-
binations listed in the catalog or installation manual.
Connecting any other model may result in
operation failure and system damage.
COOL/DRY/HEAT Model
CAUTION
This air conditioner uses the new refrigerant R410A.
INSTALLATION INSTRUCTIONS
- Split system air conditioner -
02/2004


1
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and oper-
ating standards. As the installer or service person, it is an
important part of your job to install or service the system
so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
●Carefully read this instruction booklet before beginning.
●Follow each installation or repair step exactly as shown.
●Observe all local, state, and national electrical codes.
●Pay close attention to all warning and caution notices
given in this manual. This symbol refers to a hazard
or unsafe practice which can
result in severe personal injury
or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or
product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for
a special problem, contact our sales/service outlet or
your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tub-
ing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections
and inadequate grounding can cause accidental
injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over-
heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and out-
door units. Get a partner to help, and bend your knees when
lifting to reduce strain on your back. Sharp edges or thin alu-
minum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
When Connecting Refrigerant Tubing
• Do not add any refrigerant, air, or substance into the
refrigeration circuit other than the designated refriger-
ant (R410A). Adding anything other than the specified
refrigerant may cause the pressure to rise excessively
in the refrigeration circuit, rupturing the circuit and
causing injury or damage.
• Use all-new tubing and flare nuts to make the tubing
connections. Using any previous parts (from R22-
based systems) may result in damage to the equip-
ment, and may lead to the refrigeration circuit ruptur-
ing, causing a serious accident.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them,
then tighten the nut with a torque wrench for a leak-
free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to
check that no metal scraps or bits of wiring have been
left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the
refrigeration system. Escaped refrigerant gas, on contact
with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant
gas is leaking. If escaped gas comes in contact with a
stove, gas water heater, electric room heater or other
heat source, it can produce dangerously toxic gas.
WARNING
WARNING
CAUTION
CAUTION

2
1. General
This booklet briefly outlines where and how to install
the air conditioning system. Please read over the entire
set of instructions for the indoor and outdoor units and
make sure all accessory parts listed are with the sys-
tem before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
Table 1
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the
indoor unit is available in kits which contain the narrow
and wide tubing, fittings and insulation. Consult your
nearest sales outlet or A/C workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from
a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant
tubing as detailed in Table 2.
Cut each tube to the appropriate lengths +30 cm to
40 cm to dampen vibration between units.
Table 2
2. Foamed polyethylene insulation for the specified
copper tubes as required to precise length of tub-
ing. Wall thickness of the insulation should be not
less than 8 mm.
3. Use insulated copper wire for field wiring. Wire size
varies with the total length of wiring. Refer to 3-6.
Wiring Instructions for details.
Parts Figure Q’ty Parts PartsFigure FigureQ’ty Q’ty
1
2
18
4 × 16 mm
AAA alkaline
battery
Remote
control unit Remote
control holder
Tapping
screw 2
Truss-
head
screw
Tapping
screw
Truss-
head
screw 4 × 30 mm
CAUTION
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions or
limitations.
Model Narrow Tube Wide Tube
Outer Dia. Thickness Outer Dia. Thickness
AWMI28AHL 6.35 mm 0.8 mm 9.52 mm 0.8 mm
AWMI36AHL 6.35 mm 0.8 mm 9.52 mm 0.8 mm
AWMI50AHL 6.35 mm 0.8 mm 9.52 mm 0.8 mm
AWMI70AHL 6.35 mm 0.8 mm 12.7 mm 0.8 mm

3
1-5. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See local codes)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
AVOID:
●direct sunlight.
●nearby heat sources that may affect performance of
the unit.
●areas where leakage of flammable gas may be
expected.
●placing or allowing any obstructions near the A/C
inlet or outlet.
●installing in rooms that contain instant-on (rapid-
start) fluorescent lamps. (These may prevent the A/C
from receiving signals.)
●places where large amounts of oil mist exist.
●installing in locations where there are devices that
generate high-frequency emissions.
DO:
●select an appropriate position from which every cor-
ner of the room can be uniformly cooled. (High on a
wall is best.)
●select a location that will hold the weight of the unit.
●select a location where tubing and drain hose have
the shortest run to the outside. (Fig. 1)
●allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 2)
●install the inter-unit cable more than 1 meter away
from any antenna or power lines or connecting wires
used for television, radio, telephone, security sys-
tem, or intercom. Electrical noise from any of these
sources may affect operation.
Drain hose
Indoor unit
Outside drainage
Fig. 1
Fig. 2
WARNING
To prevent abnormal heat gen-
eration and the possibility of
fire, do not place obstacles,
enclosures, and grilles in front
of or surrounding the air con-
ditioner in a way that may
block air flow.
15 cm
min. 15 cm
min.
15 cm min.
Front View

4
●install in a sturdy manner to avoid increased operat-
ing noise.
●install the unit within the maximum elevation differ-
ence (H1, H2, H3, H4) above or below the outdoor
unit and within a total tubing length (L1+L2,
L1+L2+L3, L1+L2+L3+L4) from the outdoor unit as
detailed in Table 3 and Fig. 3a.
Table 3
Max. Allowable Tubing Limit of Total Tubing Limit of Elevation
Model Length per unit Length (L1+L2), (L1+L2+L3) Difference (H)
(Outdoor unit) (m) or (L1+L2+L3+L4) (m) (m)
AE2MI56AH 25 35 (L1+L2) 10
AE3MI70AH 25 50 (L1+L2+L3) 10
AE4MI91AH 30 70 (L1+L2+L3+L4) 10
INDOOR
UNIT (1)
INDOOR
UNIT (4) INDOOR
UNIT (3)
INDOOR
UNIT (2)
Tubing length (L1)
L2
L3
L4
H2
H3
H4
OUTDOOR
UNIT
Elevation
difference (H1)
Fig. 3a
Indoor unit
Floor level
Wall
Minimum height
from floor level
1.5 m
Fig. 3b
For stable operation of the
air conditioner, do not
install wall-mounted type
indoor units less than 1.5 m
from floor level.
CAUTION

Fig. 2a
5
(1) Connecting indoor unit types (28 –36) at B
φ6.35
φ6.35
φ9.52
φ9.52
A
B
(28 36 type)
Outdoor unit Indoor unit
(28 36 type)
(2) Connecting indoor unit type 50 at B (Length of tube: more than 17 m)
φ6.35
φ6.35
φ9.52
Union φ12.7
φ9.52
φ9.52
A
B
(28 36 types)
Outdoor unit Indoor unit
(50 type)
Flare φ9.52
Union φ12.7 φ12.7
Flare φ9.52
A joint for connecting tubes of
different sizes
(More than 17 m)
Fig. 2b
(3) Connecting indoor unit type 50 at B (Length of tube: less than 17 m)
φ6.35
φ6.35 φ9.52
φ9.52
A
B
(28 36 types)
Outdoor unit Indoor unit
(50 type)
φ9.52
φ9.52
(Less than 17 m)
Fig. 2c
AE2MI56AH

6
Fig. 2e
Fig. 2f
φ6.35
φ6.35
φ6.35
φ9.52
φ9.52
Union φ12.7
φ9.52
φ9.52
φ9.52
A
B
C
(28 36 types)
Outdoor unit Indoor unit
(28 36 types)
(50 type)
Flare φ9.52
Union φ12.7 φ12.7
Flare φ9.52
A joint for connecting tubes of
different sizes
(More than 17 m)
φ6.35
φ6.35
φ9.52
φ9.52
φ9.52
φ6.35
φ9.52
A
φ9.52
B
φ9.52
C
(28 36 types)
Outdoor unit Indoor unit
(28 36 types)
(50 type)
(Less than 17 m)
φ6.35
φ6.35
φ9.52
φ9.52
φ9.52
φ6.35
φ9.52
A
φ9.52
B
φ9.52
C
(28 36 type)
Outdoor unit Indoor unit
(28 36 type)
(28 36 type)
AE3MI70AH
(1) Connecting indoor unit types (28 –36) at C
(2) Connecting indoor unit type 50 at C (Length of tube: more than 17 m)
(3) Connecting indoor unit type 50 at C (Length of tube: less than 17 m)
Fig. 2d
Note: It is not possible to connect the indoor unit type 70 to 2 or 3 room outdoor unit.

7
AE4MI91AH
φ6.35
φ6.35
φ6.35
φ6.35
φ9.52
φ9.52
φ9.52
φ9.52
φ9.52
A
φ9.52
B
φ9.52
C
Outdoor unit Indoor unit
Union φ9.52
Flare φ12.7
φ12.7
D
(φ12.7 → φ9.52) Supplied Reducer
(28 36 types)
(28 36 types)
(28 36 types)
(28 36 types)
(1) Connecting indoor unit types 28 to 36 at D
φ6.35
φ6.35
φ6.35
φ6.35
φ9.52
φ9.52
φ9.52
φ9.52
φ12.7
A
φ9.52
B
φ9.52
C
Outdoor unit Indoor unit
Union φ12.7 Flare φ9.52
φ12.7
D
(28 36 types)
(28 36 types)
(28 36 types)
(50 type)
(More than 17 m)
(2) Connecting indoor unit type 50 at D (Length of tube: more than 17 m)
φ6.35
φ6.35
φ6.35
φ6.35
φ9.52
φ9.52
φ9.52
φ9.52
φ9.52
A
φ9.52
B
φ9.52
C
Outdoor unit Indoor unit
Union φ9.52
Flare φ12.7
φ12.7
D
(φ12.7 → φ9.52) Supplied Reducer
(28 36 types)
(28 36 types)
(28 36 types)
(50 type)
(3) Connecting indoor unit type 50 at D (Length of tube: less than 17 m)
φ6.35
φ6.35
φ6.35
φ6.35
φ9.52
φ9.52
φ9.52
φ9.52
φ12.7
A
φ9.52
B
φ9.52
C
Outdoor unit Indoor unit
φ12.7
D
(28 36 types)
(28 36 types)
(28 36 types)
(70 type)
(4) Connecting indoor unit type 70 at D
Fig. 2a
Fig. 2b
Fig. 2c
Fig. 2d

8
2-2. Embedding the Tubing and Wiring
●Before beginning embedding installation work, con-
sult fully with agencies or offices related to the build-
ing’s foundation, construction, electricity, and water.
●Wait to make connections to the embedded portion.
Each connection step is described later in this
manual.
●Securely cover the end of the embedded tubing to
prevent intrusion of dirt or moisture.
●If an embedded tube is to be left for a long time, fill
the tube with nitrogen and seal both ends securely.
If a tube is left open for an extended time, moisture
in the air inside the tubing may condense into water
droplets, and lead to water contamination of the
refrigerant circuit.
●In order to prevent insulation breakdown and ground
faults, do not allow wiring ends to come in contact with
rainwater, or be subjected to condensation or dew.
●Apply sufficient thermal insulation to the refrigerant
tubing and drain pipes.

9
Set screw only for transportation
Fig. 5a
Screw
Attachment tab
Rear panel
Fig. 5b
Rear panel
▲marks
Fig. 6a
Left
tubing
Right tubing
Downward tubing
Right-rear
tubing
(recommended)
Left-rear
tubing
Fig. 6b
3. How to Install the Indoor Unit
3-1. Remove the Rear Panel from the Unit
(AWMI28AHL)
(1) Remove and discard the set screw on the rear
panel. (Fig. 5a)
(2) Press the 2 ▲▲marks on the frame cover and disen-
gage the stationary tabs from the frame. (Fig. 6a)
(3) Remove the rear panel.
(AWMI36/50AHL)
First, remove the rear panel from the indoor unit.
Remove the screws attaching the panel and push up
the attachment tabs to permit a slight space, then com-
pletely remove the panel.
(The removed screws are no longer needed.)
Tubing can be extended in 5 directions as shown in
Fig. 6a. Select the direction you need providing the
shortest run to the outside unit.
●When left tubing is to be done, switch the drain hose
and drain cap. (For details, refer to “Switching drain
hose and drain cap”on page 13.)
3-2. Make a Hole
(1) Place the rear panel from the indoor unit on the wall
at the location selected. Make sure the panel is hori-
zontal, using a carpenter’s level or tape measure to
measure down from the ceiling. Wait until after cutting
the hole before attaching the rear panel to the wall.
(2) Determine which side of the unit you should make
the hole for tubing and wiring. (Figs. 7a & b)
In the case of left-rear tubing, use the outside ▼▼mark
for precise placement of the hose outlet. (Figs. 7a & b)
(3) Before making the hole, check carefully that no studs
or pipes are directly run behind the spot to be cut.
The above precautions are also applicable if tubing
goes through the wall in any other location.
NOTE
NOTE
Fig. 7a
In case of left-rear, right-rear tubing (AWMI28AHL)
CAUTION
Also avoid areas where elec-
trical wiring or conduits are
located.
(AWMI28AHL)
(AWMI28AHL)
(AWMI36/50AHL)

10
Indoor
side Outdoor
side
Plastic
cover
INSIDE OUTSIDE
Wall
Slight
angle
PVC pipe
Plastic cover
Fig. 10
PVC pipe (locally purchased)
Cut at slight angle
Fig. 9
(4) Using a sabre saw, key hole saw or hole-cutting
drill attachment, cut a hole in the wall. See Table 4
and Fig. 8.
Table 4
(5)Measure the thickness of the wall from the inside edge
to the outside edge and cut PVC pipe at a slight angle
6 mm shorter than the thickness of the wall. (Fig. 9)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert the pipe in the wall.
(Fig. 10)
3-3. Install the Rear Panel on the Wall
Be sure to confirm that the wall is strong enough to
suspend the unit.
See either Item a) or b) below depending on the wall type.
a) If Wooden Wall
(1) Attach the rear panel to the wall with the 6 screws
provided. (Fig. 11a)
If you are not able to line up the holes in the rear
panel with the beam locations marked on the wall,
use rawl plugs or toggle bolts to go through the
holes on the panel or drill 5 mm dia. holes in the
panel over the stud locations and then mount the
rear panel.
When you attach the rear panel to the wall you
must use the top installation screw holes.
Install the panel levelly, confirming with a carpen-
ter’s level.
(Alternately, you can check for levelness by hang-
ing a weighted string from the center hole of the
panel, making sure the string lines up with the trian-
gle mark at the bottom of the panel.)
(AWMI36/50AHL)
Open the extension boards as marked and check
the dimensions. Use the supplied 8 installation
screws. (Fig.11b)
Hole Dia. (mm)
AWMI28/36/50AHL AWMI70AHL
65 80
Fig. 11a
19.599
27.5 27.5
40
450
805
344
309
41
99
41
285
Hole for temporary attachment
Extension
board
Hole for tubing
(φ65 )
Fig. 11b
(AWMI28AHL)
Bending point
Bending point
Center of left-rear
tubing hole Center of right-rear
tubing hole
Fig. 7b
Fig. 7c
(AWMI36/50AHL)
(AWMI36/50AHL)
Center of
left-rear
tubing hole
Center of
right-rear
tubing hole
In case of left-rear or right-rear tubing
(AWMI70AHL)
Hole should be made at a slight downward slant to the
outdoor side.
NOTE
Fig. 8

11
(2) Double check with a ruler or carpenter’s level that
the panel is level. This is important to install the unit
properly. (Fig. 12)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise
and vibration.
b) If Block, Brick, Concrete or Similar Type Wall
Make 4.8 mm dia. holes in the wall. Insert rawl plugs
for appropriate mounting screws. (Fig. 13)
3-4. Remove the Grille to Install the Indoor Unit
Basically, these models can be installed and wired with-
out removing the grille. If access to any internal part is
needed, follow the steps as given below:
How to remove the grille (AWMI28/36/50AHL)
(1) Set the flap in the horizontal position.
(2) Unscrew the 2 screws. (Fig. 14a)
(3) Remove the grille. (Fig. 14b)
(a) Hold both corners of the air intake grille, then
pull out and up to open.
(b) Pull the lower part of the grille toward you to
remove.
(c) Use a standard screwdriver to push up the 2
tabs to remove the grille.
How to remove the grille (AWMI70AHL)
(1) Set the 2 flaps in the horizontal position.
(2) Unscrew the 3 screws. (Fig. 14c)
(3) Remove the grille.
(a) Hold both corners of the air intake grille, then
pull out and up to open. (Fig. 14d)
(b) Use a standard screwdriver to push up the 3
tabs to remove the grille. (Fig. 14d)
(c) Pull the lower part of the grille toward you to
remove. (Fig. 14c)
Screw cover
Flap
(Up and down air direction louvre)
Fig. 14a
Air intake grille
Fig. 14b
Fig. 12
4.8 mm
dia. hole
Rawl plug
(Field supply)
Fig. 13
Air intake grille
Grille
Fig. 14c
Air intake grille
Fig. 14d

12
How to replace the grille
(1) Close the flaps.
(2) Reinstall the grille into the lower part while aligning
its tabs on the upper part. (Fig. 15a) Insert the tabs
in the slots and push the lower part of the grille
back into position.
(3) Press at each of the 4 tabs to completely close the
grille. Make sure that the grille and frame are firmly
fitted together. (Fig. 15b)
3-5. Shape the Indoor Side Tubing
1) Arrangement of tubing by directions
a) Right or left tubing
Cut out the corner of the right/left frame with a
hacksaw or the like. (Figs. 16 and 17)
b) Right-rear or left-rear tubing
In this case, the corner of the frame need not be
cut.
2) To mount the indoor unit on the rear panel:
Hang the 2 mounting slots of the unit on the
upper tabs of the rear panel. (Fig. 18)
3-6. Wiring Instructions
General precautions on wiring
1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the
wiring closely following the wiring diagram.
2) Provide a power outlet to be used exclusively for
each unit, with a power supply disconnect and cir-
cuit breaker for overcurrent protection provided in
the exclusive line.
3) To prevent possible hazard due to insulation fail-
ure, the unit must be grounded.
4) Each wiring connection must be done tightly and in
accordance with the wiring system diagram. Wrong
wiring may cause the unit to misoperate or become
damaged.
5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no
responsibility for any damage or misoperation that
occurs as a result of such unauthorized changes.
Frame
Right tubing
outlet
Frame
Left tubing
outlet
Fig. 17
Fig. 18
Fig. 16
Fig. 15a
Fig. 15b
(AWMI28/36/50AHL)
Tab
Mounting slot
Fig. 19
(AWMI70AHL)

13
3-7. Wiring Instructions for Inter-unit Connections
(1) Hold both corners of the air intake grille, then pull
out and up to open.
(2) Remove the screw on the right side cover plate
and open the cover. (Fig. 20)
(3) Insert the inter-unit wiring into the through-the-wall
PVC pipe. Lead the wiring into the room allowing
approx. 30 cm for right side and 120 cm for left
side tubings to extend from the wall face. (Fig. 21a)
(4) Route the inter-unit wiring from the back of the
indoor unit and pull it toward the front for connec-
tion. (Fig. 21b)
(5) Connect the inter-unit wiring to the corresponding
terminals on the terminal plate (Fig. 21b) while
referring to the wiring diagram.
(6) Be sure to secure the wiring with the provided
clamp.
When closing the air intake grille, press on both
corners and the center. (Fig. 21c)
NOTE
Fig. 21a
Fig. 21b
Fig. 21c
Fig. 20
25 cm
120 cm
Wiring
Rear
panel
Plastic
cover
Plastic
cover

14
When connecting each power wire to the correspond-
ing terminal, follow the instructions “How to connect
wiring to the terminal”and fasten the wire securely tight
with the fixing screw of the terminal plate.
How to connect wiring to the terminal
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the wire about 7 mm. See the
label (Fig. 22) near the terminal plate.
(2) Using a screwdriver, loosen the terminal screw on
the terminal plate.
(3) Insert the wire and tighten the terminal screw com-
pletely using a screwdriver.
b) For Outdoor Unit
■For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the solid wire about 25 mm.
(Fig. 23a)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using the pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the termi-
nal plate and fix it securely with the removed termi-
nal screw using a screwdriver.
■For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the stranded wiring about 10
mm and tightly twist the wire ends. (Figs. 23b and
23c)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring connec-
tor. (Fig. 23b)
(4) Place the ring connector wire, and replace and
tighten the removed terminal screw using a screw-
driver. (Fig. 23d)
Solid wire Loop
Insulation
Strip 25 mm
Fig. 23a
STRIP
SIZE 7 mm (ACTUAL
SIZE)
Fig. 22
Stranded wire
Ring
connector
Strip 10 mm
Fig. 23b
Screw
Ring connector
Terminal plate
Wire
Special
washer
Fig. 23d
Screw and
special washer
Ring
connector
Wire
WARNING
Loose wiring may cause the
terminal to overheat or result
in unit malfunction. A fire
hazard may also exist. There-
fore, be sure all wiring is
tightly connected.
Twist wire ends
Fig. 23c

15
3-8. Mounting
(1) To install the indoor unit, mount the indoor unit onto
the tabs on the upper part of the rear plate.
(2) Hold down the air discharge outlet and press the
lower part of the indoor unit until it clicks to secure-
ly fasten to the 2 tabs on the lower part of the rear
plate. (Fig. 24a)
For tubing, choose either the right or left tubing direc-
tion and follow the steps below. Also, extend the sup-
port on the back of the indoor unit as a stand to make
your work easier. (Fig. 24b)
■Right-side tubing
(1) Shape the refrigerant tubing so that it can easily go
into the wall hole.
Wrap the tubing with duct tape or the equivalent,
together with the drain hose and inter-unit cable (if
permitted by local codes).
Position the drain hose below the pipe. Be sure
there is enough extra slack to prevent any strong
pulling forces on the drain hose. (Fig. 25)
(2) Push the wiring, refrigerant tubing, and drain hose
through the hole in the wall. Adjust the indoor unit
so it is securely seated on the rear panel. (Fig. 26)
(3) Carefully bend the tubing (if necessary) to run
along the wall in the direction of the outdoor unit
and then tape as far as the fittings. The drain hose
should come straight down the wall to a point
where water runoff won’t stain the wall.
NOTE
Cover
Refrigerant
tubing
Rear panel
Drain hose
Inter-unit
wiring
Fig. 25
Fig. 26
Push
Fig. 24a
Stand
Fig. 24b

16
Hole in wall
Bent part Narrow tube
Wide tube
Rear panel
Fig. 27a
Drain cap
Drain hose
Fig. 27b
■Left-side tubing
(1) Lead the tubing and drain hose through the wall,
allowing sufficient length for connection. Then
bend the tubing using a tube bender to make the
attachment. (Fig. 27a)
(2) Switch the drain hose and drain cap.
Switching drain hose and drain cap
(a) Locate the drain hose and drain cap.
(Fig. 27b)
(b) Remove the drain hose on the right side by
pushing and turning the hose connector
counter-clockwise to release it. (Fig. 27b)
(c) Apply moderate force to pull off the drain cap
on the left side. (If you cannot pull it off by
hand, use a long-nose pliers.)
(d) Reattach the drain hose to the left side and
the drain cap to the right side. (Fig. 27c)
Drain hose
While pushing the drain connector, turn it clock-
wise until it clicks. Slip the connector onto the out-
let firmly.
Drain cap
Use a Phillips screwdriver to push the drain cap in
firmly. (If it is difficult to push in, wet the cap with
water first.)
(3) Install the indoor unit on the rear panel.
(4) Connect the tubing and wiring led inside from out-
doors.
(5) After completing a leak test, bundle the tubing
together with armoring tape and store it inside the
tubing storage area at the back of the indoor unit
and hold it with clamps.
60°
Drain hose
Clamp
Drain cap
To slip on
To remove
Fig. 27c
Refrigerant tubing
Inter-unit wiring
Drain hose
Fig. 28

17
To unmount indoor unit
Press the 2 ▲▲marks on the lower part of the indoor
unit and unlatch the tabs. Then lift the indoor unit and
unmount. (Fig. 29)
3-9. Drain Hose
a) The drain hose should be slanted downward to the
outdoors. (Fig. 30)
b) Never form a trap in the course of the hose.
c) If the drain hose will run in the room, insulate the
hose with insulation*so that chilled condensation
will not damage furniture or floors. (Fig. 31)
*Foamed polyethylene or its equivalent is recom-
mended.
WARNING
Risk of Electric Shock
Do not supply power to the
unit or operate it until all tub-
ing and wiring to the outside
unit are completed.
;;
;;
;;
;;;;
;;;;
;;;;
;;
;;
;;
Condensation
Insulation material
(locally purchased)
must be used.
Fig. 31
Push
Fig. 29
;;
;;
;;
;;;;
;;;;
;;;;
Slant
Drain
hose
Indoor
unit
Fig. 30

18
4. How to Secure the Wireless Remote
Control Unit
The remote control unit can be operated from either a
non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly, do
not install the remote control unit in the following
places:
●In direct sunlight
●Behind a curtain or other place where it is covered
●More than 8 m away from the air conditioner
●In the path of the air conditioner’s airstream
●Where it may become extremely hot or cold
●Where it may be subject to electrical or magnetic
interference
4-1. Mounting on a Wall
a) Removable mounting
1) Confirm the indoor unit beeps when the
ON/OFF button is pressed at the wall location
where the remote control unit is to be attached,
then attach the holder to the wall. (Fig. 32)
2) When taking out the remote control unit, pull it
from the holder.
When using the remote control unit
•Point the transmission portion of the remote
control unit at the receiver area of the indoor
unit when operating the remote control unit,
and during operation of the air conditioner.
•Do not place objects that may block the trans-
mitted signals between the receiver and the
remote control unit.
b) Non-removable mounting
1) Mount the holder to the wall with one of the
screws (using only the hole in the top of the
holder) (Fig. 33).
2) Remove the cover of the remote control unit
and take out the batteries. Next, place the
remote control unit in the holder.
3) Fasten both the remote control unit and holder
to the wall with the remaining screw (using the
hole in the bottom of the holder).
4) Install the batteries in the remote control unit
and close the cover.
Truss-head
tapping screw
4 ×16 mm (supplied)
Remote
control
unit holder
Fig. 32
Holder
Holder
Truss-head
tapping screw
4 ×16 mm (supplied)
Fig. 33
This manual suits for next models
6
Table of contents
Other Argo Air Conditioner manuals

Argo
Argo POLIFEMO TALAO User manual

Argo
Argo AWIAS12DC User manual

Argo
Argo POLIFEMO BILLY User manual

Argo
Argo AWIBS9 Manual

Argo
Argo XFETTO DCI HPL User manual

Argo
Argo APOLLO User manual

Argo
Argo AER608SH Manual

Argo
Argo SLIMMY User manual

Argo
Argo DAVEN PLUS User manual

Argo
Argo GREENSTYLE PLUS DUAL 9000 UI User manual
Popular Air Conditioner manuals by other brands

Daikin
Daikin EBHQ006BAV3 Operation manual

Daikin
Daikin EWAQ004BAVP Installer's reference guide

Retro Aire
Retro Aire R30C Installation, operation & maintenance manual

intensity
intensity IDUFCI60KC-3 installation manual

Carrier
Carrier 38MHRBC12AA1 installation instructions

NuAire
NuAire UNI-X Series installation manual