EG
33
If necessary, get help
These instructions are all you need for most installation sites and maintenance conditions.
If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional
instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure
to follow the instructions in this document.
SPECIAL PRECAUTIONS
•Duringinstallation,connectbeforethehydraulicandrefrigerantsystemandthenthewiringone;proceedinthe
reverse order when removing the unit.
ELECTRICALSHOCKCANCAUSESEVEREPERSONALINJURYORDEATH.
ONLYQUALIFIED,EXPERIENCEDELECTRICIANSSHOULDATTEMPTTOWIRETHISSYSTEM.
•Donotsupplypowertotheunituntilallwiringandtubingarecompletedorreconnectedandchecked,toensure
the grounding.
•Highlydangerouselectricalvoltagesareusedinthissystem.Carefullyrefertothewiringdiagramandthese
instructions when wiring.
Improper connections and inadequate grounding can cause accidental injury and death.
•Ground the unit following local electrical codes.
•TheYellow/Greenwirecannotbeusedforanyconnectiondifferentfromthegroundconnection.
•Connectallwiringtightly.Loosewiringmaycauseoverheatingatconnectionpointsandapossiblefirehazard.
•Donotallowwiringtotouchtherefrigeranttubing.
•Donotusemulticorecablewhenwiringthepowersupplyandcontrollines.Useseparatecablesforeachtypeof
line.
When transporting
Becarefulwhenpickingupandmovingtheunit.Getapartnertohelp,andbendyourkneeswhenliftingtoreduce
strain on your back. Sharp edges or thin aluminium fins on the unit can cut your fingers.
When installing
... In a room
Properly insulate any tubing run inside a room to prevent “sweating”, which can cause dripping and water damage
to walls and floors.
... In a wall or floor
Make sure they are strong enough to hold the unit weight. It may be necessary to build a strong wooden or metal
frame to provide added support.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for the unit.
This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the unit down with bolts and a metal frame. Provide a suitable air baffle.
... In a snowy area
Install the unit on a raised platform that is higher than drifting snow. Provide snow vents.
When connecting refrigerant tubing of Emix / Emix-Tank
•Usetheflaremethodforconnectingtubing.
•Applyrefrigerantlubricanttothematchingsurfacesoftheflareanduniontubesbeforeconnectingthem;screw
by hand and then tighten the nut with a torque wrench for a leak-free connection.
•Checkcarefullyforleaksbeforestarting.
•Insulatethetubeswithfoamedpolyethylene(min.thickness8mm).
When connecting hydraulic tubing
•Keepalltubingrunsasshortaspossible.
•Insulatethetubing.
•Checkcarefullyforleaksbeforestarting.
When servicing
•TurnthepowerOFFatthemainpowerboardbeforeopeningtheunittocheckorrepairelectricalpartsandwiring.
•Keepyourfingersandclothingawayfromanymovingparts.
•Cleanupthesiteafterthework,rememberingtocheckthatnometalscrapsorbitsofwiringhavebeenleftinside
the unit being serviced.
•Ventilatetheroomduringtheinstallationortestingtherefrigerationsystem;makesurethat,aftertheinstallation,
nogasleaksarepresent,becausethiscouldproducetoxicgasanddangerousifincontactwithflamesorheat-
sources.
When wiring
WARNING