PanelProgramming(Elite S&S-Lite only)
Youwillneed totell the panelwhat zone the smoke detector isconnected to.
InProgrammode press <PROGRAM> <123> <ENTER> thenputinthe zone (1-16)
that the smoke ison(iffollowing the wiring diagram,that’s4) so <4> <ENTER> now
turnOnoption <5> <ENTER>.
i.e. P123E4E5E (zone 4isnow a24Hour Fire zone)
Asthe contactsofthe smoke detector are NormallyOpen(NO) youwillnow need totell
the panelthat the zone the smoke iswiredintoisNormallyOpen.
InProgrammode press <PROGRAM> <122> <ENTER> thenputinthe zone (1-16)
that the smoke ison(iffollowing the wiring diagram,that’s4) so <4> <ENTER> now
turnOnoption <2> <ENTER>.
i.e. P122E4E2E (zone 4isnow aNormallyOpenzone)
Note:Bydefaultall24 Hour Fire zoneswillonlytrigger output2onactivation,for more
informationplease consultthe FullProgramming Manual.
Gnd 12V1C23C4Tmp Gnd
Outputs
Gnd 12V1234
1
2
4
3
2k2
2k2
TerminalsofEliteS-LiteControlPanel
Joiningterminals
Infra-RedDetector
0v
12v
EOLTAMPEREOLRELAY
Gnd 12V1C23C4Tmp Gnd
Outputs
Gnd 12V1234
1
2
4
3
8k2
TerminalsofEliteS-LiteControlPanel
Low Zone(4)
4K7Resistor
HighZone(8)
8K2Resistor
4k7
STANDARDSMOKEINSTALLATION
SINGLEZONETYPE3 EXPANDEDSMOKEINSTALLATION
ZONEDOUBLING TYPE15
Ifyouwishto use zonedoubling,followthe programmingbelowaswell asthe other2programmingchanges.
Change Zone Type
Bydefaultzones1to4are Setup tobe Single zones, using a2K2Resistor (thisistype
3).Ifyouwishtouse zone doubling and your detectorshave beenwired witha4K7&
8K2(asshownabove) youwillneed tochange the zone type to15.Tochange the
zone type youwillneed togotoaddress 125and thenchoose the zone tobe changed.
(each zone 1to4canbe changed totype15).InInstaller Mode press <PROGRAM>
<125> <ENTER> thenchoose the zone tochange (1-4) (iffollowing the wiring dia-
gram,that’s4)so <4> <ENTER> now putinthe type <15> <ENTER>.
i.e. P125E4E15 E (zone 4hasbeenchanged totype15,activating zone8).
Note:The defaultand zone ability'sslightlyvaryonthe full Elite SModel
Please consultthe FullProgramming Manualfor more info.