ASCO POWER TECHNOLOGIES 5010 User manual

ASCO 5010 Remote Display Unit
1
Installation Considerations
Installation and maintenance of the ASCO 5010 Remote
Display Unit should only be performed by qualified,
competent personnel that have appropriate training and
experience with high voltage and current devices. The meter
must be installed in accordance with all Local and National
Electrical Codes and regulations.
This equipment has no user serviceable parts.
.
Important Symbols Used in This Manual
TABLE OF CONTENTS
Section Page
1 .............. Introduction ............................................................. 3
2 .............. Getting Started........................................................ 4
3 .............. Hardware Description ............................................. 6
4 .............. Mounting ................................................................. 9
5 .............. Wiring.................................................................... 10
6 .............. Navigating through the screens ............................ 12
7 .............. Basic Configuration............................................... 14
8 .............. Using the ASCO 5010 Remote Display Unit......... 18
9 .............. Monitoring ............................................................. 32
10 ............. Troubleshooting .................................................... 42
11 ............. Technical Definitions............................................. 45
12 ............. ASCO 5400 Series Website
Reference ............................................................. 48
Figure Page
Figure 1. ASCO 5400 Series Basic Module Unit .................... 2
Figure 2. ASCO 5010 Functional Display Unit........................ 6
Figure 3 External Display Panel (Rear View)......................... 7
Figure 4 ASCO 5010 RDU -Technical Drawing ..................... 7
Figure 5 Screw Holes for Affixing RDU to a Panel................. 9
Figure 6 Mounting the Remote Display Device
to a Panel................................................................. 9
Figure 7 Power Over Ethernet PoE Connection .................. 11
Figure 8 Terminals for RS485/422 on the Rear Side
of the ASCO 5010 RDU......................................... 11
Figure 9 The ASCO 5010 RDU Main Menu......................... 12
Figure 10 The ASCO Welcome Screen followed by the
Connection Configuration Page............................. 14
Figure 11 The ASCO Search Utility for Finding ASCO Elements
on the LAN............................................................. 24
Figure 12 The Two Page Configuration Menu ....................... 25
Figure 13 The Information Page ............................................ 26
Figure 14 Read-only "About" Information .............................. 26
Figure 15 Current transformer conductor inserted correctly
through the ASCO 5400 Series ............................. 28
Figure 16 PT/CT Settings- inputting the Primary
PT Value ................................................................ 28
Figure 17 The Main Menu- Default on Power Up .................. 32
Figure 18 Large Digits Display- A Typical Page Layout......... 34
Figure 19 The Factors Summary Page: K-factor and
Crest Factor ........................................................... 36
Figure 20 Volt/Amp Summary................................................ 36
Figure 21 The Power Summary Page.................................... 37
Figure 22 The THD Summary Page ...................................... 37
Figure 23 Waveforms Main Menu.......................................... 38
Figure 24 Navigating the Oscilloscope .................................. 39
Figure 25 A Harmonic Spectrum Screen ............................... 40
Figure 26 The Phasor Display ............................................... 41
Figure 27 The Flickering Summary........................................ 42
Figure 28 A Detailed Flicker Summary .................................. 43
P
O
WER Florham Park, New Jersey 07932-1591
TECHNOLOGIES For sales or service, call: 1 800-800-2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA, PO Box 1238, 17 Airport Road
Brantford, Ontario, Canada N3T 5T3
Series ASCO 5010 Series
IO-70051 Rev. 0 9/12
5010 Remote
Display Unit
1Operator’s Manual
WARNING is used in this manual to warn of a hazardous
situation which, if not avoided, could result in death or
serious in
j
ur
y
.
W
ARNING
CAUTION
CAUTION is used in this manual to warn of a hazardous
situation which, if not avoided, could result in minor or
moderate injury.
NOTICE is used in this manual to address practices not related
to physical injury.
NOTIC
E
DANGER is used in this manual to warn of a hazardous
situation which, if not avoided, will result in death or
serious injury.
DANGER

ASCO 5010 Remote Display Unit
2
Acronyms
A Ampere
CT Current Transformer
DHCP Dynamic Host Configuration Protocol
IP Internet Protocol
OPC (formerly OLE for Process Control), a series of standards specifications
PF Power Factor
PoE Power over Ethernet
PT Potential Transformer
RDU Remote Display Unit
SCADA Supervisory Control and Data Acquisition
SMTP Simple Mail Transfer Protocol
SNTP Simple Network Time Protocol
SSL Secure Sockets Layer
Subnet masking Local Internet subnet masking determined usually by IP admin
THD Total Harmonic Distortion
Figure 1: The ASCO 5400 Series Basic Module Unit

ASCO 5010 Remote Display Unit
3
Section 2. Introduction
This manual is the last chapter in a series of seven, and will instruct the user in the installation, configuration and use of the
Remote Display Unit to monitor and configure any Power Quality Data Center, using a direct connection or through a LAN/WAN
The seven chapters comprising the ASCO manual set for the Power Quality Data Center series are listed as follows:
1. ASCO 5400 Series Power Quality Data Center Installation and Wiring Manual- This manual instructs the user on
installing the Power Quality Meter into an electric panel and how to begin using the Power Quality Data Center.
2. ASCO 5400 Series Power Quality Meter Operation Manual- This manual describes the interface for monitoring and
configuring the ASCO 5400 Series Power Quality Meter using the onboard WEB server as it is accessible from a
standard web browser from any PC connected to the Internet (or LAN).
3. PQSCADA Site Manager Installation Manual- This manual instructs the user in installing the server based Site
Manager Software that will manage the Nodes that will collect, store and analyze the compressed data produced by
the ASCO 5400 Series Power Quality Meter.
4. PQSCADA Site Manager User Manual- This manual instructs the user in setting up the server based Site Manager
with Nodes that will collect, store and analyze the compressed data from the ASCO 5400 Series Power Quality
Meter. The manual instructs the user in surfing to the Site Manager, adding and removing Nodes and operating the
ASCO Power Quality Reporting Tool.
5. Investigator Installation Manual- This manual instructs the user in installing the Investigator software used to access,
load and analyze data from different ASCO 5400 Series Power Quality Meters in order to understand the cause for
power quality events that occurred in the system.
6. Investigator User Manual- This manual instructs the user in the use of the Investigator software to load and analyze
data from different ASCO 5400 Series Power Quality Meters in order to understand the cause for power quality
events that occurred in the system.
7. ASCO 5010 Remote Display Installation and Operation Manual- This manual instructs the user in the installation,
configuration and use of the Remote Display to monitor and configure any Power Quality Meter, using a direct
connection or through a LAN/WAN.
2.1 Overview
The ASCO 5010 LCD Remote Display Unit is an integral part of the ASCO Power Quality Meter system, allowing
interconnectivity with the ASCO 5400 Series Power Quality Meter for configuring and monitoring the electrical distribution
system.
The ASCO 5010 Remote Display Unit (RDU) connects and communicates with the ASCO 5400 Series Power Quality Meter
directly via RJ45 network cable or through IP communication from anywhere in the world. One RDU can be used to monitor and
configure many ASCO 5400 Series Power Quality Meters.
The ASCO 5010 RDU enables configuring all aspects of the ASCO 5400 Series Power Quality Meter and displays all monitored
real time values. Figure 1 describes the role of the ASCO 5010 RDU in managing power quality data in a power distribution
system.
The ASCO 5400 Series Power Quality Meter (1) is connected to the electrical system via current and potential transformers.
These instruments constantly record the voltage and current waveforms at a resolution of up to 1024 samples per cycle. This data
is compressed on board using the ASCO PQZip technology. The PQZip files are transferred to a PNode (4) running on a server
managed by the Site Manager. The PNode stores the data collected from the instrument and responds to requests from client
workstations running ASCO Investigator software (5). When an engineer using the Investigator software wishes to analyze the
data collected by the instrument from a certain time frame, the PNode decompresses the requested data, performs the necessary
mathematical calculations to display the electrical parameters requested by the client and then arranges and configures the data to
be displayed on the specific screen used by the client.
Every ASCO 5400 Series Power Quality Meter hosts an onboard Website allowing access to data from any web browser.
Inputting the IP address of the instrument in the address window of an internet browser will bring the ASCO 5400 Series webpage
to the browser with current real time monitored values (2). Configuration of the ASCO 5400 Series may also be achieved via the
Website.

ASCO 5010 Remote Display Unit
4
The ASCO IP Address Search Tool (6) is an important element in the ASCO Power Quality Meter System. This utility allows all
ASCO 5400 Series Power Quality Meter and ASCO 5010 RDU connected to a LAN to be found and identified on line.
The ASCO 5010 (3) Remote Display LCD is used to both configure and monitor the ASCO 5400 Series Power Quality Meter
achieving much the same effect as when using a web browser but with the added tactile feedback only a dedicated LCD display
can offer. The ASCO 5010 RDU can be used as a hand held monitoring and configuring tool connecting to each ASCO 5400
Series Power Quality Meter in turn using a CAT 5e/6 network cable with a RJ45 plug, or optionally plugging into a network
connection and alternately inputting the IP addresses of the different instruments.
Section 2. Getting Started
2.1 Unpacking
The ASCO 5400 Series Power Quality Data Center is shipped with the following:
# Description Quantity
1 ASCO 5010 LCD Remote Display Unit (RDU) 1
2 LAN cable 1
3 ASCO 5010 Display Installation & Operation Manual 1
4 RS485/422 Communication terminal block connector - BL3.5/4/90LF SW- 4p Black Clamping yoke, 1
5 48DC terminal block connector - BL3.5/2/90LF SW – 2p Black Clamping yoke 1
6 Screws for mounting to wall metal plate 2
7 Flat fastening disk for mounting with screws 2
8 Screw-nut 2

ASCO 5010 Remote Display Unit
5
2.2 Safety Precautions
Before working with the ASCO 5010 Remote Display Unit, please read this User Manual carefully. The manufacturer will not be
responsible for damage or injury due to misuse.
The following general safety guidelines apply to ASCO 5010 RDU installation and operation. When performing any operation
with the ASCO 5010, always observe these safety precautions.
The instructions contained in this manual are intended for qualified personnel only. To avoid personal injury, do not
perform any activity other than as contained herein unless you are qualified to do so.
Before connecting cables to the ASCO 5010 RDU, verify that the 48VDC supply is disconnected.
To prevent shock or fire hazard, do not expose the ASCO 5010 RDU to rain or moisture.
Do not make unauthorized modifications to the ASCO 5010.
Always operate the ASCO 5010 RDU within the specified power tolerances.
To use and operate the ASCO 5010 RDU, strictly follow the specifications of this manual. The manufacturer will
not be responsible for any damage or injury resulting from equipment misuse and/or unsafe work practices.
W
ARNING
NOTIC
E

ASCO 5010 Remote Display Unit
6
Section 3. Hardware Description
3.1 ASCO 5010 Remote Display Unit Overview
The ASCO 5010 Remote Display Unit shown in Figure 2 can be divided into three conceptual sections. The upper section
contains the Status LEDs, the middle section contains the visual interface; a header and the monitor screen and the lower section
contains the input interface; 5 Function keys and a Network key.
Figure 2: The ASCO 5010 Remote Display Unit
The Status LEDs indicate as follows:
Green LED – External power indication
Red LED – Failure or indication of incomplete configuration
The Header contains the name of the instrument currently connected and the time of day.
The five Function keys are context sensitive, offering dynamic functionality as the unit is used, with the current function
appearing above the key.
The Network key is used to disconnect with the current instrument, enabling connectivity with another instrument.
Network key

ASCO 5010 Remote Display Unit
7
Figure 3 shows the ASCO 5010 RDU connectors as follows:
a. RJ45 – used for both communication & power sourcing the unit (PoE – power over the Ethernet cable coming from
ASCO 5400 Series Power Quality Meter). By factory default, the ASCO 5010 RDU is ready for connecting to
any ASCO 5400 Series unit at the LCD port. A simple CAT5e/6 cable connecting directly between the ASCO
5010 RDU and ASCO 5450 and 5490 LAN2/LCD port will automatically power up, connect and open the main
menu screen relevant for that specific ASCO 5400 Series PQM currently connected. Remote connectivity
(through an IP network) is also applicable but requires configuration as described later in this manual.
b. DC 48V – Used for alternative power source (for remote connectivity when PoE is not available)
c. RS485/422 – Used in industrial applications for multi-drop series communication when IP networking is not
available.
Figure 3: The ASCO 5010 Remote Display Unit – Rear View
48V DC
RJ45
RS485/422

ASCO 5010 Remote Display Unit
8
3.2 ASCO Technical and Environmental Specifications
3.2.1 Physical Specifications
Figure 4: ASCO 5010 RDU - Technical Drawing

ASCO 5010 Remote Display Unit
9
3.2.1.1 ASCO 5010 Remote Display Specifications
3.2.2 Environmental Specifications
Intended use Indoor- mounted in a low voltage electrical distribution panel
Altitude Up to 2000 meters
Operating temperature range -4º to +140º F (-20º to +60º C )
Maximum relative humidity 95%
Power requirements 10 VA
Fuse rating 2 A fuse mounted in line with the AC power supply phase wire
Installation Category Class III
Pollution Degree Degree 2
Dimensions (H×W×D) 197×200×46 mm
Panel cutout: 135×135 mm
Power supply 48 VDC
LAN1 PoE in
LED backlight 160×128 pixels graphic screen

ASCO 5010 Remote Display Unit
10
Section 4. Mounting
The ASCO 5010 Remote Display Unit is designed for mounting on a flat panel through a 138x138mm cutout with two 5mm
holes. Two screws are supplied for fixing the display unit to the panel from behind. A typical location for mounting the ASCO
5010 RDU is on the front panel of an electrical distribution panel. Figure 5 and Figure 6 aid in describing the method of attaching
the RDU to a panel.
A 138 x138 hole is cut out from the panel and the RDU is slid in to place from in front. The RDU is then fixed in place using two
screws from behind.
Figure 5: Screw Holes for Affixing RDU to a Panel
Figure 6: Mounting the Remote Display Device to a Panel

ASCO 5010 Remote Display Unit
11
Section 5. Wiring
5.1 Connecting the Power Supply and LAN
The ASCO 5010 Remote Display Unit requires 48V DC to operate. The unit can receive this power from one of two inputs:
1. 48V DC power input terminal
2. The LAN jack using PoE (Power over Ethernet) from the ASCO 5400 Series Power Quality Meter labeled LAN2/LCD.
When both inputs are in use, the primary source of power is from the 48V DC input terminal, with the PoE offering backup
redundancy.
5.2 Connecting the 48V DC Terminal
For safely connecting 48V DC follow these instructions:
Ensure the panel under work is de-energized.
Prepare the 48V DC terminal block connector provided with the ASCO 5010 Package
Attach lugged ends of wires to the terminal block using a properly sized screw driver
√The positive wire is to be attached to the terminal marked +
√The negative wire is to be attached to the terminal marked -
Insert the 48VDC terminal block into the socket marked "48V DC" as shown above in
Figure 3.
The ASCO 5010 Remote Display Unit will operate efficiently using a voltage range from 24-51V DC, however only 48V DC
may be used through the PoE input (LAN2/LCD socket on the ASCO 5450 and 5490 Power Quality Meters).
5.3 Power over Ethernet (PoE)
POE is a standard for feeding DC power to an RTU (Remote Terminal Unit) using the network RJ45 cable without the
need for additional external power.
The ASCO 5010 contains a single LAN port with support for receiving PoE (In) but not for providing PoE (Out) to other
devices.
To take advantage of the PoE option, connect the RJ45 jack to the port marked "LAN2/LCD" on the ASCO 5400 Series Power
Quality Meter as shown in Figure 7.

ASCO 5010 Remote Display Unit
12
5.4 Recommended Mode of LAN Connection for ASCO 5400 Series
It is suggested that the ASCO 5010 RDU be connected to the port marked LAN2/LCD on the ASCO 5450/5490 Power Quality
Meter and that the LAN1 port on the 5410 be used to connect to the LAN for communicating PQZip files to the Node on the
power quality server.
Figure 7: Power Over Ethernet PoE Connection
5.5 USB Connection
Follow accepted USB protocol connection procedures.
5.6 RS485/422
The RS485/422 serial communications hardware protocol is an industrial standard using 2 or 4 wires for communication. The
wires are to be connected to the terminals marked RS485/422 on the ASCO 5010 RDU as shown in Figure 8 and to the marked
terminals on the CPU module of the ASCO 5400 Series Power Quality Meter.
Figure 8: Terminals for RS485/422 on the Rear Side of the ASCO 5010 RDU
To enable understanding of the protocol for the purpose of enabling efficient communication, basic elements of the protocol are
described here:
√Voltage is typically 5V DC
√Cable is comprised of 2 shielded twisted pairs
√Typical length of cable is < 1000 meter with no repeater
√Units are connected in multi-drop (“daisy chain”) configuration. In 2 wire mode, the wires coming in and going out
share the same terminal on the instrument
√Shield MUST be grounded, but ONLY at one point in the chain.
ASCO 5010 Remote
Dis
p
la
y
Unit

ASCO 5010 Remote Display Unit
13
Section 6. Navigating Through the Screens
All ASCO 5010 Remote Display Unit functions are accessible through the 5 function keys located at the bottom of the panel.
These function keys are context sensitive and will change functions depending on the screen being viewed. The function
performed by the key at any time will be displayed on the Function Key Tag immediately above the function key.
Figure 9: The ASCO 5010 Remote Display Unit Main Menu
Figure 9 presents the Main Menu. The chapters of the menu are displayed graphically in the center of the display and described
textually just above the function key tags. Navigation is achieved by pressing the function key under the arrows. Entering a
chapter is accomplished by pressing the key under the (F3) symbol. The ASCO 5010 Remote Display Unit displays
three distinct types of screens:
Numeric Display - This type of display emulates an electrical panel power meter display comprising three rows of
electrical parameters presented in large digits. Clicking on the appropriate function key toggles through all the electrical
parameters and pages of electrical parameter summaries
Graphic Display - This type of display is used to present waveforms, phasors and harmonics
Text Display - This type of display is use to display textual information such as reports, alarms and warnings

ASCO 5010 Remote Display Unit
14
Favorites List
The Favorites list contains monitored parameters often accessed by the operator. The Favorite parameters most interesting an
operator are easily toggled through the F5 key from any measurement screen displaying electrical parameters, as opposed to going
back to the previous menu and entering the next page of parameters.
Menu Key
The F4 key is used to get to the main menu from any of the display modes.
Help Function
The Help function is activated by pressing the F1 key where ever the help function is relevant.
Cancel and Back Functions
In order to activate the CANCEL and BACK Functions, use the F2 key. CANCEL will close the menu and will return to the
previous display mode, while BACK will close the current submenu and return to the previous menu.
Enter, Next, Select and Close Functions
The F3 key is used for ENTER, NEXT, SELECT or CLOSE. All these functions accept the entered information.
ENTER is also used to open a submenu and to select a menu item.
At the Installation Wizard, NEXT will accept the entered data and move to the next screen. SELECT will toggle between the
selected inputs, and CLOSE will accept data and close the page.
UP and DOWN Functions
In most screens the F4 and F5 keys activate the (up) and (down) functions. When in a Large Digit screen (see section 9.1.1
on page 35), the Down key will toggle through the "Favorites List".
At the data entry windows, the (up) button will increment the value by 1, while the (down) button will decrement the value
by 1. Holding the button down continuously will change the value in steps of 10.
At all other windows, (up) will move the selection bar one line up and (down) will move it one line down.

ASCO 5010 Remote Display Unit
15
Section 7. Basic Configuration
When powered up after being installed into an electrical panel, or powered up by being connected to the ASCO 5450 and 5490
Power Quality Meters via the LAN2/LCD socket, the ASCO 5010 is ready to be configured before being used to configure, set up
and monitor a ASCO 5400 Series PQM.
When the LAN and power cables are first connected, the device boots up, first showing the ASCO welcome screen and then
arriving at the Connection Configuration page shown in Figure 10, from where the ASCO 5010 RDU can be configured. After a
few seconds (configurable- see below "Auto connect page"), the page changes to the ASCO 5400 Series Power Quality Meter’s
main entry menu page, from where the ASCO 5400 Series PQM is to be configured (Figure 9). To return to the ASCO 5010 RDU
configuration page, simply push the Network Key or use the right arrow ( ) and left arrow ( ) to navigate to and select the Log
Off option, that will return to the 'Connection Configuration' page.
Figure 10: The ASCO Welcome Screen followed by the Connection Configuration Page
As seen from Figure 10, the Connection Configuration screen displays the following headings:
IP address: This heading displays the last ASCO 5400 Series Power Quality Meter to which the ASCO 5010 RDU was
connected. Entering here allows the user to connect to any ASCO 5400 Series PQM on the network.
Password: The default password is 123. An administration password is supplied separately by ASCO. From this
heading, the administrator may input his password and freely change parameters on the ASCO 5400 Series Power
Quality Meter being configured until he presses the Network key or the keypad is idle for 5 minutes. There is no need
for any password to change the parameters of the ASCO 5010 RDU from these pages.
Language: From this screen the user chooses the interface language.
Configuration: Navigate to this heading using the F4 and F5 keys in order to configure the ASCO 5010 Remote Display
Unit with the following options:
√General information- this screen offers the serial number and version information for all software resident in the
ASCO 5010 RDU
√Auto connect configuration- In this page the time for presenting the Connection Configuration page is set. After
this time, the ASCO 5010 RDU will automatically connect to the last ASCO 5400 Series instrument to which it
was connected.
√LCD Contrast- the contrast ratio between black and white for the LCD is set in this screen
√LCD Backlight timeout- this screen allows for setting a time until the backlight extinguishes automatically
√Network configuration- this screen is used to configure the network parameters for the ASCO 5010 Remote
Display Unit in order that it may be plugged into the LAN/WAN and communicate with any ASCO 5400 Series
anywhere in the world. The parameters that must be configured are as follows (these parameters are explained in
section 7.1- Network Parameters- Table 1):

ASCO 5010 Remote Display Unit
16
DHCP- This value may be toggled ON or OFF. If this parameter is toggled on, then the IP address, Subnet
mask and Gateway cannot be configured manually. The ASCO 5010 RDU is factory set with the DHCP set to
off, and the network parameters set as defined in the following sections.
IP address: The factory default address for the ASCO 5010 RDU is 192.168.168.100
Subnet mask: The factory default subnet mask for the ASCO 5010 RDU is 255.255.255.0
Gateway: The factory default Gateway for the ASCO 5010 is 192.168.168.168 (which is the default address
for the ASCO 5450 and 5490 LAN2/LCD port.
NTP address: this is the address for taking the UTC.
SMTP address- in the event that this parameter is used by the system.
√Firmware upgrade- the ASCO 5010 RDU firmware can be updated from this screen by using the following sub
menus:
FTP address- input the FTP address from where the firmware is to be downloaded
FTP login- input the user name required to enter and download from the FTP site
FTP password- input the password required to enter and download from the FTP site
FW filename- input the filename to be downloaded from the site
These procedures will be described and explained in the following sections.
7.1 Network Parameters
This section will explain the Network Parameters necessary to enable the configuring and monitoring of the ASCO 5400 Power
Quality Meter using the ASCO 5010 Remote Display Unit.
The network parameters are defined in Table 1.
Table 1: Network Parameters
No User network parameter Definition
1 DHCP Status toggle DHCP – Dynamic Host Configuration Protocol. ASCO enables 2 run modes: DHCP enable and
disable.
DHCP enabled: The ASCO 5400 Series network configuration is automated by the Internet
server, the ASCO 5400 Series will not keep user input network parameters; rather the Internet
server configures the network parameters automatically.
DHCP disabled: The ASCO 5400 Series network parameters are input by the user, and remain
static
Parameters affecting DHCP disabled
2 IP address Internet address of the ASCO 5400 Series Power Quality Meter.
Configuring an IP Address for ASCO 5010 RDU – refer to section 7.2
3 Subnet Mask A local bit mask (set of flags) that specifies which bits of the IP address specify a particular IP
network or a host within a sub-network. An IP address of 128.66.12.1 with a subnet mask of
255.255.255.0 specifies host 1 on subnet 128.66.12.0. The subnet mask determines the
maximum number of hosts on a sub-network
4 Gateway A Gateway is a computing node on the local Internet network that allows or controls access to
that network.
5
SNTP address SNTP – Simple Network Time Protocol. A PC server or an ASCO 5400 Series Power Quality
Meter can be used as a time reference (UTC). SNTP is a protocol used to reference that time to
the local machine. Example: An ASCO 5400 Series Power Quality Meter with IP address
100.100.100.69 is configured as the NTP address. The ASCO 5400 Series that is being
configured by the ASCO 5010 device is IP address 100.100.100.63. The configured device will
relate to 100.100.100.69 as the reference UTC server clock. That clock is essential to the
generation of coherent PQZIP files.

ASCO 5010 Remote Display Unit
17
6SMTP address SMTP - Simple Mail Transfer Protocol. Currently not in use. A protocol which controls the transfer
of e-mail messages between two mail servers.
Table 2, shown below, presents the factory default values for the ASCO 5400 Series Power Quality Meter and the ASCO 5010
RDU.
Table 2: Factory Default Network Parameters
No Parameter ASCO 5010 ASCO
5450/5490
LAN2/LCD
ASCO 5400
Series LAN1
1 DHCP Status toggle OFF OFF ON
2 IP address 192.168.168.100 192.168.168.168 169.254.249.247
3 Subnet Mask 255.255.255.0 255.255.255.0 255.255.0.0
4Gateway 192.168.168.168 169.254.249.254 169.254.249.254
7.2 Changing the ASCO 5010 RDU IP Address
Changing the IP address of the ASCO 5010 RDU is necessary to connect to a network in order to enable connection to one or
more ASCO 5400 Series Power Quality Meter via the network.
Changing the IP address of the ASCO 5010 RDU will disable direct communication via the LAN2/LCD port on the ASCO 5400 Series
Power Quality Meter. To re-enable this direct communication requires changing the IP address of the ASCO 5010 RDU back to the factory
default of 192.168.168.100 with subnet mask 255.255.255.0
Navigate to the 'Connection Configuration' page, shown in Figure 10 on page 15, by pressing on the Network key or logging off
from the main menu:
Navigate to the "Configuration" chapter and press enter
Navigate to the Network Configuration and press enter
Select 'DHCP status toggle' and ensure that the DHCP is disabled. If DHCP is not disabled, then any change to the
network IP address will not stay.
If the screen asks: "Do you want to enable DHCP?" press X; if the screen asks "Do you want to disable DHCP?"
press OK.
Select 'IP address' and the following screen will appear:

ASCO 5010 Remote Display Unit
18
Navigate between the 4 address elements using the right arrow. Change the address elements using the up and down arrows. Lock
in the address by pushing the OK button.
Select 'Subnet mask' and change as necessary using the right, up and down arrows
Select the 'Gateway' and change as necessary using the right, up and down arrows

ASCO 5010 Remote Display Unit
19
Section 8. Using the ASCO 5010 Remote Display Unit
After the ASCO 5010 Remote Display Unit has been configured, it may be used to configure and display the measured
parameters of the ASCO 5400 Series Power Quality Meter. One RDU can be used to configure and monitor a number of ASCO
5400 Series PQM by changing the IP address of the instrument to be monitored.
The setup and configuration procedure of the ASCO 5400 Series instrument includes:
ASCO 5400 Series Unit setup:
√Administration authorization
√Site name
√Operator name
√Site description.
Electrical system parameters:
√Phase configuration (Y, ∆)
√Nominal values (V, I, f)
√CT/PT ratios (Configuring these parameters must not precede the configuration of the Nominal values)
√Polarity of input waveforms (normal/reverse)
Network setup
√Assign IP address
√other internet relevant configuration parameters
Firmware upgrade
These procedures will be described and explained in the following sections.
8.1 Connecting for the First Time
Connecting to the ASCO 5400 Series Power Quality Meter with the ASCO 5010 Remote Display Unit is accomplished
differently depending on the manner in which the connection is made, and the purpose of the connection.
Connecting a ASCO 5010 RDU as a static display for a single ASCO 5400 Series PQM requires less configuration than
connecting a single ASCO 5010 unit to multiple ASCO 5400 Series PQM’s over the internet, though this configuration is not
overly complicated requiring only a basic understanding of IP addressing and system parameters from the LAN administrator.
When attempting to make changes to the ASCO 5400 Series configuration, the user will be asked to enter an administrative
password.

ASCO 5010 Remote Display Unit
20
8.1.1 Admin Access Privilege
Modifying setup parameters requires administrative or Admin authorization. When the user attempts to modify the first
parameter, an access level modification page will appear:
Pressing on X will return to the previous menu, pressing OK will bring up the Admin authorization page:
Delete the default user password, 123, by navigating to the "Del" key and pressing SELECT three times. Enter the password
supplied by ASCO to authorize Admin level access by using the arrows to navigate to each character of the password and
pressing SELECT. When the whole password is displayed on the screen, press OK. The previous configuration screen will
appear, with "write" authorization.
8.2 Connecting and Communicating
8.2.1 Connecting a Single ASCO 5010 RDU to a Single ASCO 5400 Series Power Quality Meter
If the ASCO 5010 RDU is to be used as a permanent display for a single ASCO 5400 Series Power Quality Meter, the connection
is made simply from the ASCO 5010 RDU port to the ASCO 5400 Series LAN2/LCD port using a regular LAN Cat5e/6 cable
with RJ45 plugs on both ends. No configuring is necessary; the communication is "plug and play". Both the ASCO 5400 Series
and the ASCO 5010 RDU are factory programmed with default IP addresses and subnet masks to enable immediate
communication between them. These default values are listed in Table 1 on page 16.
8.2.2 Using the ASCO 5010 RDU for the ASCO 5400 Series Power Quality Meter LAN Configuration Before
Initialization
If the ASCO 5010 is to be used to configure an ASCO 5400 Series Power Quality Meter offline before connecting to a LAN, the
factory defaults can be used to enhance the communication configuration task.
Before allowing connection to the LAN, connect the ASCO 5010 RDU to the LAN2/LCD port on the ASCO 5450
and 5490 Power Quality Meter
Other ASCO POWER TECHNOLOGIES Control System manuals
Popular Control System manuals by other brands

roco
roco LOKMAUS 2 manual

OBSIDIAN CONTROL SYSTEMS
OBSIDIAN CONTROL SYSTEMS NX2 installation guide

kozy heat
kozy heat SIT Proflame II System Overview & Troubleshooting Guide

CYBELEC
CYBELEC CybTouch 12 user manual

Ecolab
Ecolab Apex2 Installation and operation manual

Avid CNC
Avid CNC PRO 60120 Series Assembly instructions