Asco 565 User manual

Surge Protective Devices Installation & Operation Manual
Model 575
Model 565

Installation, Operation and Maintenance Manual IO-70074 Rev- 04-192

Installation, Operation and Maintenance Manual IO-70074 Rev- 04-193
ASCO SURGE PROTECTIVE DEVICE
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
TABLE OF CONTENTS
LOCATION CONSIDERATIONS
Environment
Audible Noise
Service Clearances
Mounting
Warnings Defined
4
4
4
4
4
5
575 & 565 MODEL NUMBERS 5
ELECTRICAL CONNECTIONS
Voltage Ratings and Power Source Configurations
Wire Connections
Over Current Protection
NEC®Considerations
Voltage Protection Rating
Circuit Ampacity Limitations
System Grounding and Bonding
Neutral Connection
Parallel Connection / Wire Diagram
6
6
6
6
6
7
7
7
8
8
UNPACKING AND INSTALLATION
Unpacking and Preliminary Inspection
Storage
4
4
4
INSTALLATION INSTRUCTIONS
Product Installation
Suggested Circuit Breaker and Wire Size – Model 575/565
Dimensional Information – Model 575/565
8
8
10
10
MONITORING FEATURES
Visable Status Indicators (Standard)
Summary Alarm Contact (Standard)
9
9
9
TROUBLESHOOTING / SERVICING / MAINTENANCE
Troubleshooting
Servicing
Corrective Maintenance
Preventative Maintenance
12
12
12
12
12

Installation, Operation and Maintenance Manual IO-70074 Rev- 04-194
UNPACKING AND INSTALLATION
Unpacking and Preliminary Inspection
1. Inspect the shipping crate(s) for damage or signs of mishandling before unpacking the unit.
2. Remove any securing bands and cardboard packing and inspect the unit for any obvious
shipping damages.
3. If any damage as a result of shipping is observed, immediately file a claim with the shipping
agency and forward a copy to your local ASCO Surge Protection Sales Representative.
Storage
The unit should be stored in a clean, dry environment. Storage temperature range is -55ºC (-67ºF)
to +85ºC (+185ºF). Care should be taken to avoid condensation. All packing and shipping materials
should be left intact until the unit is ready for final installation. If the unit has been stored for an extended
period of time, the unit should be cleaned and carefully inspected before placing into service.
LOCATION CONSIDERATIONS
For optimum transient surge protection, coordinated surge suppression should be applied at the
service entrance and all other electrical connections to the building (telephone, CATV, etc.), at known
surge generating loads within the building (large motors, arc welders, switched capacitors, etc.),
as well as at sensitive electronic loads (such as computers, electronic appliances, solid state motor
drives, etc.). For interconnected electronic loads (such as by way of data cabling), transient surge
suppression should also be applied to the interconnecting wiring (data cables).
Environment
Unit is designed for operation indoors in ambient temperatures of -35ºC (-31ºF) to +40ºC (+104ºF) with
a relative humidity of 0% to 95% (non-condensing).
The unit is provided in an industrial use enclosure, which is dust-tight and drip-tight and should not be
installed in areas with excessive dust, corrosive vapors, flammable materials or explosive atmospheres.
Audible Noise
The audible noise of the unit is less than 40 dB at 5 feet, which allows its placement within almost any
room if desired.
Service Clearances
Service clearance is needed for units with hinged doors on the front that are capable of being opened.
Thirty-six inches (36 in/914 mm) minimum is recommended.
Mounting
Unit is intended to be wall mounted. Refer to installation instructions for mounting dimensions and
weight.

Installation, Operation and Maintenance Manual IO-70074 Rev- 04-195
Warnings Defined
Danger: Indicate[s] a hazardous situation which, if not avoided, will result
in death or serious injury. The signal word “DANGER” is to be limited to
the most extreme situations. DANGER [signs] should not be used for property damage hazards unless
personal injury risk appropriate to these levels is also involved.
Danger: Indique une situation dangereuse qui, si elle n’est pas évitée, entraînera la mort ou des
blessures graves. Le mot comme signal DANGER doit être limité aux situations les plus extrêmes. Les
signes DANGER ne doivent pas être utilisés pour les risques de dommages à la propriété, sauf si le
risque de blessures appropriées à ces niveaux est également impliqué.
Warning: Indicate[s] a hazardous situation which, if not avoided, could
result in death or serious injury. WARNING [signs] should not be used for
property damage hazards unless personal injury risk appropriate to this level is also involved.
Avertissement: Indique une situation dangereuse qui, si elle n’est pas évitée, pourrait entraîner la mort
ou des blessures graves. Les signes AVERTISSEMENT ne doivent pas être utilisés pour les risques
de dommages à la propriété, sauf si le risque de blessures appropriées à ce niveau est également
impliqué.
Caution: Indicate[s] a hazardous situation which, if not avoided, could
result in minor or moderate injury. CAUTION [signs] without a safety alert
symbol may be used to alert against unsafe practices that can result in property damage only.
Attention: Indique une situation dangereuse qui, si elle n’est pas évitée, pourrait entraîner des
blessures mineures ou modérées. Les signes ATTENTION sans symbole d’alerte de sécurité peuvent
être utilisés pour mettre en garde contre des pratiques dangereuses qui peuvent entraîner des
dommages matériels seulement.
575 & 565 MODEL NUMBERS
ASCO Catalog
Number
UL Legacy Part
Number Voltage Motorola
R56 Type
UL
Type
cUL
Type MCOV
575120SP16FCRJ20 SS550120SFNSP2 120S (Fig 1) 2A 2 2 138
575120YP16FCRJ20 SS550120YFNSP2 120Y (Fig 2) 2A 2 2 138
575277YP16FCRJ20 SS550277YFNSP2 277Y (Fig 2) 2A 2 2 320
565120SP16FCRJ20 SS500120SFNSP2 120S (Fig 1) 2B 2 2 138
565120YP16FCRJ20 SS500120YFNSP2 120Y (Fig 2) 2B 2 2 138
565277YP16FCRJ20 SS500277YFNSP2 277Y (Fig 2) 2B 2 2 320
Figure 1
SPLIT
2 Phases, 1 Neutral,
1 Ground
Phase B (Black)
Phase A (Black)
Neutral (White)
V
V
}
}
Ground (Green)
Figure 2
WYE
3 Phases, 1 Neutral,
1 Ground
}
Phase A (Black)
Phase B (Black)
Neutral (White)
Phase C (Black)
Ground (Green)
A
C
N
V
B

Installation, Operation and Maintenance Manual IO-70074 Rev- 04-196
ELECTRICAL CONNECTIONS
All wiring must comply with the National Electrical Code (NEC®) and applicable local codes.
DANGER! ONLY QUALIFIED PERSONNEL SHOULD INSTALL OR
SERVICE THIS SYSTEM. ELECTRICAL SAFETY PRE-CAUTIONS MUST
BE FOLLOWED WHEN INSTALLING OR SERVICING THIS EQUIPMENT. TO PREVENT RISK OF
ELECTRICAL SHOCK, TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE
MAKING ELECTRICAL CONNECTIONS OR SERVICING.
DANGER! SEULEMENT LE PERSONNEL QUALIFIÉ DOIT INSTALLER OU MAINTENIR CE
SYSTÈME. DES PRÉCAUTIONS DE SÉCURITÉ EN ÉLECTRICITÉ DOIVENT ÊTRE SUIVIS LORS DE
L’INSTALLATION OU DE LA MAINTENANCE DE CET EQUIPEMENT. POUR EVITER TOUT RISQUE DE
CHOC ÉLECTRIQUE, DÉBRANCHEZ ET VEROUILLER TOUTES LES SOURCES D’ ALIMENTATION
DE CET EQUIPEMENT AVANT DE LE BRANCHER OU LE MAINTENIR.
Voltage Ratings and Power Source Configurations
Before making connections to the unit, verify that the unit model number and nameplate voltage
rating are appropriate for connection to the intended power source. See the chart for voltage rating
applications with typical power source configurations.
Wire Connections
With parallel connection, the size of the wiring to the SPD unit is independent of the protected circuit’s
ampacity. NEC®Article 285-21(B) requires surge suppressor connecting conductors to be at least #14
copper or #12 aluminum. To reduce the wiring impedance to surge currents, it is recommended that
the phase, neutral (if required), and ground conductors are twisted together and routed in the same
raceway (conduit). Avoid any sharp bends in the conductors.
Overcurrent Protection
The SPD unit conducts practically no current under normal operation and only conducts very short
duration transient surge currents.
NEC®Considerations
The following is from the National Electric Code 2017 Edition.
NEC®285.21 Connection.
NEC®285.24 Type 2 SPDs. Type 2 SPDs shall be installed in accordance with 285.24(A) through (C).
A. Service-Supplied Building or Structure. Type 2 SPDs shall be connected anywhere on the
load side of a service disconnect overcurrent device required in 230.91, unless installed in
accordance with 230.82(8).
B. Feeder-Supplied Building or Structure. Type 2 SPDs shall be connected at the building or
structure anywhere on the load side of the first overcurrent device at the building or structure.
C. Separately Derived System. The SPD shall be connected on the load side of the first overcurrent
device in a separately derived system.

Installation, Operation and Maintenance Manual IO-70074 Rev- 04-197
Voltage Protection Ratings
To obtain the voltage protection ratings (VPRs), as obtained by Underwriters Laboratory, Incorporated,
in accordance with the Standard for Safety, Surge Protective Devices (SPDs), Standard 1449, Fourth
Edition, marked on this product, the wire size listed for each product must be utilized to connect the
unit to your facilities’ power grid. Connections made with conductors other than the wire size listed
may result in dierent VPRs.
Circuit Ampacity Limitations
Representative samples of these products have been investigated by Underwriters Laboratories,
Incorporated to withstand, without exposing live circuits or components at system voltages and fault
currents up to 200,000 AIC, as described in the Standard for Safety, Surge Protective Devices (SPDs),
Standard 1449, Fourth Edition.
System Grounding and Bonding
The performance and safety of any SPD system is dependent on proper grounding and bonding.
Grounding is required for safety. Correct implementation also enhances equipment performance.
Incorrect grounding can reduce or impede the SPD’s operation. All electrical circuits to the SPD must
include an equipment- grounding conductor as required by the NEC and local codes.
An insulated grounding conductor is required in addition to any metallic raceway, which may be used
as a grounding conductor. For parallel-connected SPDs, the grounding conductor should be the same
wire size as the associated power conductors.
UNGROUNDED POWER SYSTEMS ARE INHERENTLY UNSTABLE AND CAN PRODUCE
EXCESSIVELY HIGH LINE-TO-GROUND VOLTAGES DURING CERTAIN FAULT CONDITIONS.
DURING THESE FAULT CONDITIONS ANY ELECTRICAL EQUIPMENT, INCLUDING AN SPD,
MAY BE SUBJECTED TO VOLTAGES WHICH EXCEED THEIR DESIGNED RATINGS. THIS
INFORMATION IS BEING PROVIDED TO THE USER SO THAT AN INFORMED DECISION CAN BE
MADE BEFORE INSTALLING ANY ELECTRICAL EQUIPMENT ON AN UNGROUNDED POWER
SYSTEM. CONTACT FACTORY FOR UNGROUNDED APPLICATIONS.
ATTENTION – LES SYSTÈMES D’ALIMENTATION NON-MISES À LA TERRE SONT INTRINSÈQUEMENT
INSTABLES ET PEUVENT PRODUIRE DES TENSIONS DE PHASE TRÈS ÉLEVÉES AU COURS DE
CERTAINES CONDITIONS DE DÉFAUT. PENDANT CES CONDITIONS DE DÉFAUT TOUT ÉQUIPEMENT
ÉLECTRIQUE, Y COMPRIS UN SPD (PROTECTEUR DE SURTENSION), PEUT ETRE SOUMIS A DES
TENSIONS SUPERIEURES À LEURS VALEURS STANDARDS. CETTE INFORMATION EST FOURNIE
À L’UTILISATEUR AFIN QU’UNE DÉCISION CORRECTE PEUT ÊTRE PRISE AVANT D’INSTALLER UN
ÉQUIPEMENT ÉLECTRIQUE SUPPLIMENTAIRE SUR UN SYSTÈME D’ALIMENTATION NON-MISE À
LA TERRE. CONTACTER L’USINE POUR LES APPLICATIONS NON-MISES À LA TERRE.
The use of isolating bushings or other means to interrupt a metallic conduit run is a potential safety
hazard and is not recommended.

Installation, Operation and Maintenance Manual IO-70074 Rev- 04-198
Neutral Connection
NOTICE - FOR PROPER AND SAFE OPERATION, THE SPD’s NEUTRAL MUST BE RELIABLY
CONNECTED TO THE NEUTRAL OF THE SOURCE. FAILURE TO PROVIDE A RELIABLE NEUTRAL
CONNECTION MAY RESULT IN FAILURE!
The ASCO Models 575/565 Surge Protective Devices (SPDs) are high quality, high energy surge
current diversion systems designed to protect sensitive equipment from damaging transient voltage
surges. Proper installation is required for maximum system performance.
The installer should perform the following steps to assure a quality installation. The entire installation
manual should be read before starting installation. These instructions do not replace national or
local electrical codes. Check applicable electrical codes to ensure compliance. Installation of the
SPD system should only be performed by qualified personnel. Model 575/565 is a type 2 device that
requires over current protection.
1. Insure that all power is removed before beginning installation. A qualified licensed electrician
shall install all electrical connections.
2. The standard SPD is provided in a NEMA 4X (575/565) rated enclosure suitable for use in indoor
or outdoor installations.
3. Determine where the SPD is to be mounted, allowing for minimum length of wire between itself
and the input power terminals of the service panel. Punch or cut the proper hole size in the side
of the SPD closest to the knockout to be utilized in the service panel. Drill mounting holes
in wall at location picked for SPD next to service panel using mounting dimensions shown in the
table below. Mount surge suppressor to wall using 3/8” mounting hardware.
4. Connect black wires (line or phase) marked L1/A, L2/B or L3/C and the white wire (neutral)
marked N to the SPD using the wire range listed below. To yield the best performance of the
SPD within the electrical distribution system, keep all conductors as short as possible and avoid
sharp bends.
PARALLEL CONNECTION / WIRE DIAGRAM

Installation, Operation and Maintenance Manual IO-70074 Rev- 04-199
5. Connection to the unit’s summary alarm contacts shall be with #18 – 22 AWG. The ratings of the
Form ‘C’ contacts are 5 amps at 250 VAC maximum with a power factor of 1.0. For additional
information, see “Monitoring” section.
6. Apply power. The surge protector is fully operational when the GREEN LEDs on the modules are
illuminated. If the GREEN LEDs are extinguished or a RED LED is illuminated, check to ensure
that power is applied to the SPD. If an abnormal indication is present, remove power to the SPD
and contact ASCO Surge Protection at 1-800-237-4567 or 1-727-535-6339.
7. Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LED’s are
extinguished or the RED LED is illuminated. Please contact ASCO Surge Protection at 1-800-237-
4567 or 1-727-535-6339.
8. The protection modules in these SPDs are replaceable, contact ASCO Surge Protection for
replacement.
NOTICE - If the SPD model is configured to include a neutral connection (“Y”, “S”), and a Neutral
connection is not available, please contact factory.
MONITORING FEATURES
Visable Status Indicators (Standard)
These indicators provide a summary of the status of the surge SPD module. For normal conditions, the
green LED is illuminated. If the surge SPD module requires replacement, the green LED is turned o.
Summary Alarm Contact (Standard)
Two sets of summary alarm Form C relay contacts (2 N.O. and 2 N.C.) are provided for remote
indication of the failed surge SPD module. Contacts are rated 5 amps at 250 VAC maximum with a
power factor of 1.0. Access to the contacts is provided via contact terminals located on the printed
circuit board mounted on the inside of the unit’s cover.
(With AC Applied)
Pin 1 = Normally Open
Pin 2 = Common
Pin 3 = Normally Closed
Summary Alarm Contacts (X2)

Installation, Operation and Maintenance Manual IO-70074 Rev- 04-1910
Model 575 / Model 565 - Motorola R56 Approved Models
Suggested Circuit Breaker And Wire Size – 575/565 Series
Surge Rating
Per Mode
Allowable Range Factory Suggested Size
Circuit Breaker Size Connection Wire Size Circuit Breaker Size Connection Wire Size
All Model 575
& Model 565 15A-175A #14-2/O 80 Amp #4 AWG
Dimensional Information – Model 575/565
Model Number R56 Type Weight
575120SP16FCRJ20 Type 2A (MOV/SAD Hybrid) 28 lb. (12.7 kg)
575120YP16FCRJ20 Type 2A (MOV/SAD Hybrid) 32 lb. (14.5 kg)
575277YP16FCRJ20 Type 2A (MOV/SAD Hybrid) 32 lb. (14.5 kg)
565120SP16FCRJ20 Type 2B (MOV Only) 28 lb. (12.7 kg)
565120YP16FCRJ20 Type 2B (MOV Only) 32 lb. (14.5 kg)
565277YP16FCRJ20 Type 2B (MOV Only) 32 lb. (14.5 kg)

Installation, Operation and Maintenance Manual IO-70074 Rev- 04-1911
TROUBLESHOOTING/SERVICING MAINTENANCE
Troubleshooting
If status failure indication occurs or summary alarm contacts have changed state, a qualified
electrician shall first determine if the systems voltage and proper phasing exists.
If the SPD remains in an alarm condition once the electrician is satisfied that the electrical system and
its connections are normal, the unit should be repaired.
At this point consult the factory, having available the following information:
• Model number and serial number detailed on the units’ data label
(located on the front of the enclosure).
• Nature of problem – (including condition of all status indicators and alarms).
Servicing
The ASCO Models 575/565 include a ten year parts warranty. For servicing assistance, contact your
local Sales Representative or ASCO, Surge Protection at 1-800-237-4567 or 1-727-535-6339.
DANGER! ONLY QUALIFIED PERSONNEL SHOULD INSTALL OR
SERVICE THIS SYSTEM. ELECTRICAL SAFETY PRE-CAUTIONS MUST
BE FOLLOWED WHEN INSTALLING OR SERVICING THIS EQUIPMENT. TO PREVENT RISK OF
ELECTRICAL SHOCK, TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE
MAKING ELECTRICAL CONNECTIONS OR SERVICING.
DANGER! SEULEMENT LE PERSONNEL QUALIFIÉ DOIT INSTALLER OU MAINTENIR CE
SYSTÈME. DES PRÉCAUTIONS DE SÉCURITÉ EN ÉLECTRICITÉ DOIVENT ÊTRE SUIVIS LORS DE
L’INSTALLATION OU DE LA MAINTENANCE DE CET EQUIPEMENT. POUR EVITER TOUT RISQUE DE
CHOC ÉLECTRIQUE, DÉBRANCHEZ ET VEROUILLER TOUTES LES SOURCES D’ ALIMENTATION
DE CET EQUIPEMENT AVANT DE LE BRANCHER OU LE MAINTENIR.
Corrective Maintenance
The ASCO Model 575/565 SPDs are designed for years of trouble-free operation. However, even the
most reliable equipment may fail under abnormal conditions. Diagnostic indicators are provided to
indicate when the unit needs repair or replacement. To ensure continuity of surge protection, failed
units should be repaired or replaced at the earliest convenient service opportunity. When replacing
surge modules, other components should be inspected for damage and replaced if necessary.
Standard electrical troubleshooting procedures should be used to isolate problems other than failed
surge current diverter modules. When replacing components, use identically rated components for
continued proper operation and safety. Please contact factory for information on replacement parts.
Preventative Maintenance (Inspection and Cleaning)
Periodic system inspections, cleaning, and connection checks are recommended to ensure reliable
system performance and continued surge transient protection.
It is dicult to establish a schedule for preventative maintenance since conditions vary from site to site.
Inspections for failed surge modules using available diagnostics should be done routinely (weekly or
monthly).

14550 58th Street North
Clearwater, Florida 33760
P (800) 237-4567
P (727) 535-6339
F (727) 539-8955
E customercare@ascopower.com IO-70100 Rev- 04-18
While every precaution has been taken to ensure accuracy
and completeness in this literature, ASCO Power Technologies
assumes no responsibility, and disclaims all liability for damages
resulting from use of this information or for any errors or omissions.
This manual suits for next models
1
Table of contents
Other Asco Protection Device manuals