Ascon tecnologic TRH200 User manual

Ascon Tecnologic - TRH200 - USER MANUAL - PAG. 1
TRH200
RELATIVE HUMIDITY
MEASUREMENT SENSOR
User manual
22/10 - Code: ISTR_M_TRH200_E_01_--
ASCON TECNOLOGIC S.r.l.
Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY
TEL.: +39 0381 69871 - FAX: +39 0381 698730
sito: http:\\www.ascontecnologic.com
e-mail: [email protected]
PREFACE
D This manual contains the information necessary for the
product to be installed correctly and also instructions for
its maintenance and use; we therefore recommend that
the utmost attention is paid to the following instructions
and to save it.
This document is the exclusive property of Ascon Tecnologic
S.r.l. which forbids any reproduction and divulgation, even par-
tially, of the document, unless expressly authorized.
Ascon Tecnologic S.r.l. reserves the right to make any formal or
functional changes at any moment and without any notice.
Ascon Tecnologic S.r.l. and its legal representatives do not
assume any responsibility for any damage to people, things or
animals deriving from violation, wrong or improper use or in
any case not in compliance with the instrument features.
D Whenever a failure or a malfunction of the device may
cause dangerous situations for persons, thing or animals,
please remember that the plant has to be equipped with
additional devices which will guarantee safety.
1. INSTRUMENT DESCRIPTION
1.1 General description
The probes of the TRH200 series are devices with 4 ÷ 20 mA
current output for monitoring relative humidity characterized
by a very low energy consumption.
The TRH200 uses a high-precision sensor and its conver-
sion / retransmission devices are of quality to ensure high
reliability and excellent long-term stability.
2. USAGE WARNINGS
2.1 Admitted usage
D The instrument has been projected and manufactured
as a measuring and control device to be used accord-
ing to EN60730-1 at altitudes operation below 2000 m.
Using the instrument for applications not expressly permitted
by the above mentioned rule must adopt all the necessary
protective measures.
The instrument must not be used in dangerous environ-
ments (flammable or explosive) without adequate protections.
D The installer must ensure that the EMC rules are
respected, also after the instrument installation, if
necessary using proper filters.
3. INSTALLATION WARNINGS
3.1 Mounting requirements
Select a mounting location having the following characteristics:
• It should be easily accessible;
• It must not be subjected to vibrations or impacts;
• Must be free from corrosive gases;
• Must be free from water or other fluids (condensation).
3.2 Installation position
Wall fixing is done by clips. Particular attention must be paid
to the sensor positioning, it must be kept away from heat
sources that can influence the humidity measurement.
It is a good idea to mount the probe with the sensor facing
downwards (output cable upwards) and NEVER with the
sensor facing upwards and also horizontally to avoid possi-
ble measurement errors due to self-heating.
NO
OK
NO
BEST
Cable
Any error in humidity measurement may be due to the settling
time of the probe, in this case it will be necessary to wait for
the time necessary to achieve a stable measurement.
Steam jets, water sprays, drafts, direct sun exposure, conden-
sation on the sensor or mounting on a wall made cold by the
outside temperature can also cause important measurement
errors; due to these conditions, during the installation, the
probe must be protected from any possible external influence.
Ascon Tecnologic - TRH200 - USER MANUAL - PAG. 2
3.3 Electrical Connections
General notes on electrical connections
• The probe cables must be kept separated from high
power voltage wiring.
3.3.1 Electrical wiring
VDC
Out-RH
Control
i
Power supply voltage: 9 ÷ 30 VDC;
Current consumption: 20 mA;
Reverse polarity protection: Diode;
Cable length: 2 meters.
4. PROBLEMS AND MAINTENANCE
4.1 Cleaning
We recommend to clean the instrument with a slightly wet
cloth using water and not abrasive cleaners or solvents only.
Should it be necessary to remove the sensor, avoid to me-
chanical stress it and in particular avoid touching the humid-
ity sensor.
4.2 Disposal
The appliance (or the product) must be
disposed of separately in compliance
with the local standards in force on
waste disposal.
5. WARRANTY AND REPAIRS
The instrument is under warranty against manufacturing
flaws or faulty material, that are found within 18 months from
delivery date. The warranty is limited to repairs or to the
replacement of the instrument.
The eventual opening of the housing, the violation of the instru-
ment or the improper use and installation of the product will
bring about the immediate withdrawal of the warranty effects.
In the event of a faulty instrument, either within the period of
warranty, or further to its expiry, please contact our sales de-
partment to obtain authorisation for sending the instrument
to our company.
The faulty product must be shipped to Ascon Tecnologic with
a detailed description of the faults found, without any fees or
charge for Ascon Tecnologic, except in the event of alterna-
tive agreements.
6. TEHNICAL DATA
6.1 Sensor characteristics
Sensor type: CMOS-C.
6.1.1 Relative humidity
Parameter Condition Min. Typical Max. Units
Resolution 12bit 0.04 %RH
8 bit 0.7 %RH
Accuracy/
Tolerance
Typical ±3.0 %RH
Max. See figure %RH
Repeatability ±0.1 %RH
Hysteresis ±1 %RH
Non-linearity <0.1 %RH
Response time t63% 8 s
Operative range Extended 0 100 %RH
Long-term drift Normal <0.5 %RH/year
DRH (%RH)
Relative humidity (%RH)
0102030405060708090 100
±0
±2
±4
±6
±8
±10
Maximum tolerance
Typical tolerance
Ascon Tecnologic - TRH200 - USER MANUAL - PAG. 3
6.2 Filter characteristics
6.2.1 Technical specifications
Parameter Value
Operative range -40 ÷ +125
Protction degree (1) IP67
RoHS Compliant
Body material
Polybutylene terephthalate (PBT)
Body colour Black
UL94 (body material only) UL-94 V-0 (0.73 mm)
Filter material PTFE with polyester scrim
Filter thickness 0.13 mm
Filter colour Black
Filter pore size 1.5 mm
Filtration efficiency (2) 99.99%
Oleophobic Range (filter)(3)
8
Mullen Hydrostatic >100 mbar (>1 m water)
Notes: 1. IP67: dusyt tight, protected agains harmful water
immersion up to 1 m water column
(http://en.wikipwdia.org/wiki/IP67);
2. 0.1 mm particles at 0.05 m/s air flow;
3. Repellence of oil and hydrocarbons according to
AATC 118.1992 standard. Rating goes from 0 ÷ 8
while 8 is the most repellent.
6.3 Functional features
Protection degree: IP54 (protected against dust and water
splashes from all directions);
Installation method: With clip;
Electrical connections: With 2 m wire;
Dimensions (mm): L = 100 mm + spyral, Ø16 mm;
Ambient temperature: -30 ÷ +70°C;
Ambient humidity: 0 ÷ 100% RH;
Sensor type: CMOS;
Humidity measuring range: 0 ÷ 100% RH;
Output current: 4 (0%) ÷ 20mA (100%);
Internal dissipative element;
Sensor: Interchangeable;
Refresh: 5 s;
Response time at constant conditions (63%) at 23°C: 30 s;
Recovery time from saturation: 90 s;
Storage temperature: -30 ÷ +80°C;
Max. load: 250 W;
Sensor output signal: 4 ÷ 20mA.
The output current is normally passed through the input
resistance of the reading instrument and transformed into a
voltage that can be read by the instrument.
In order to minimize self-heating, this model of probe uses the
“switching mode” technique for controlling the output current.
Ascon Tecnologic - TRH200 - USER MANUAL - PAG. 4

Other Ascon tecnologic Measuring Instrument manuals

Ascon tecnologic TRH42 User manual

Ascon tecnologic

Ascon tecnologic TRH42 User manual

Ascon tecnologic TLI40 User manual

Ascon tecnologic

Ascon tecnologic TLI40 User manual

Ascon tecnologic K V Series User manual

Ascon tecnologic

Ascon tecnologic K V Series User manual

Ascon tecnologic TRH324 User manual

Ascon tecnologic

Ascon tecnologic TRH324 User manual

Ascon tecnologic TRH301 User manual

Ascon tecnologic

Ascon tecnologic TRH301 User manual

Ascon tecnologic TRH22 User manual

Ascon tecnologic

Ascon tecnologic TRH22 User manual

Ascon tecnologic TRH514 User manual

Ascon tecnologic

Ascon tecnologic TRH514 User manual

Popular Measuring Instrument manuals by other brands

globalwater RG200 manual

globalwater

globalwater RG200 manual

In-situ Aqua TROLL quick start guide

In-situ

In-situ Aqua TROLL quick start guide

PerkinElmer Lambda 365 Fiber Coupling Module installation instructions

PerkinElmer

PerkinElmer Lambda 365 Fiber Coupling Module installation instructions

Mind Media NeXus-4 user manual

Mind Media

Mind Media NeXus-4 user manual

Sel BOX BASIC RI 3000 EtherNet/IP instruction manual

Sel

Sel BOX BASIC RI 3000 EtherNet/IP instruction manual

digi-tech AT Wizard M5 manual

digi-tech

digi-tech AT Wizard M5 manual

Spot-on 29360 product manual

Spot-on

Spot-on 29360 product manual

B+K precision 2831C Lnstruction manual

B+K precision

B+K precision 2831C Lnstruction manual

AutomationDirect ProSense DPM2 Series user manual

AutomationDirect

AutomationDirect ProSense DPM2 Series user manual

Powerline XL2G instruction manual

Powerline

Powerline XL2G instruction manual

FRO­NIUS Smart Meter 50kA-3 operating instructions

FRO­NIUS

FRO­NIUS Smart Meter 50kA-3 operating instructions

Promax Prolite-50 manual

Promax

Promax Prolite-50 manual

RF Technology Sensatec ST750 instruction manual

RF Technology

RF Technology Sensatec ST750 instruction manual

Metrix 5500 installation manual

Metrix

Metrix 5500 installation manual

red lion Legend Plus Series manual

red lion

red lion Legend Plus Series manual

Almaco FLEXICOMPT AUTONOME+ operating guide

Almaco

Almaco FLEXICOMPT AUTONOME+ operating guide

B+K precision PR-55 Instruction folder

B+K precision

B+K precision PR-55 Instruction folder

SIAM DDIM-2 operating manual

SIAM

SIAM DDIM-2 operating manual