Ashcroft IXLdp User manual

© 2015 Ashcroft Inc., 250 East Main St., Stratford, CT 06614-5145, U.S.A. Tel: 203-378-8281, Fax: 203-385-0499, email: info@ashcroft.com, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M011-10062 (250-2985) Rev. I 06/15
MODEL IXLdp TRANSDUCER
INSTRUCTION SHEET
MODEL IXLdp TRANSDUCER
INSTRUCTION SHEET
WARNING! READ
BEFORE INSTALLATION
1. GENERAL:
A failure resulting in injury or damage
may be caused by excessive overpres-
sure, excessive vibration or pressure pul-
sation, excessive instrument temperature,
corrosion of the pressure containing parts,
or other misuse. Consult Ashcroft Inc.,
Stratford, Connecticut, USA before installing
if there are any questions or concerns.
2. O ERPRESSURE:
Pressure spikes in excess of the rated over-
pressure capability of the transducer may
cause irreversible electrical and/or
mechanical damage to the pressure mea-
suring and containing elements.
3. STATIC ELECTRICAL CHARGES:
Any electrical device may be susceptible to
damage when exposed to static electrical
charges. To avoid damage to the transducer
observe the following:
• round the body of the transducer
BEFORE
making any electrical connections.
• When disconnecting, remove the ground
LAST!
Note: The shield and drain wire in the cable
(if supplied) is not connected to the trans-
ducer body, and is not a suitable ground.
DESCRIPTION
The Industrial Low Pressure Differential
Transducer consists of a silicon diaphragm
supported between two layers of metallized
glass. The Si- las technology combines the
inherent high sensitivity of a variable capaci-
tance trans ducer using a micro-machined, sin-
gle crystal diaphragm which provides excellent
stability and repeatability.
The transducer should be used with clean, dry
air or other dry non-corrosive gases. Both
unidirectional (e.g. 0/1.0 in. W.C.) and bidirec-
tional (e.g. +/– 5.0 in. W.C.) pressure ranges
are offered as well as a wide selection of out-
put signals.
The storage temperature limits of the trans-
ducer are –40 to 210°F. The unit can operate
between –20 and 185°F and is temperature
compensated between 0 and 160°F.
For units with FM approval Please see
schematic diagram 71B241.
MOUNTING
The unit should be mounted with #8 or #10
screws using the three mounting feet provided
(see Fig. 1). Easy access to the covers may
be a consideration when mounting. The trans-
ducer can be mounted in any orientation with
virtually no effect on calibration. Any minor

zero pressure offsets that are encountered
can be adjusted using the zero adjust poten-
tiometer. (See the Calibration section for more
details on the zeroing procedure.)
PIPING
The “high” and “low” pressure connection ports
are plugged to avoid debris entering the unit.
The plugs should be left in place until the tub-
ing and fittings are connected. The two 1⁄4˝ NPT
pressure connections should be sealed to the
transducer housing using teflon tape. The use
of a dope-type sealant should not be used
since it may cause measurement errors
because of outgassing.
WIRING
oltage Output:
The IXLdp requires 12-36 VDC excitation for
operation and will typically draw less than
5mA. The warm-up is typically less than 15
seconds.
Current Output without FM Approval:
The voltage required for a 4-20mA output is
dependent upon the loop resistance of the cir-
cuit (see Fig. 2). The voltage required is pro-
portional to the load (loop resistance) being
driven. Figure 2 shows the minimum supply
voltage (Vmin) required for a given loop resis-
tance. The warm-up time is typically less than
15 seconds.
Current Output with FM Approval:
IXKdps with the option FM approval must be
wired using the schematic diagram, 71B241,
found on page 3 of the Installation and
Maintenance instructions.
The field wiring terminals can be accessed by
unscrewing the four cover screws and remov-
ing the terminal block access cover (see Fig.
1). Once the cover is removed, make sure no
contaminants, (e.g. water, oil, chemicals,
grease, dirt, etc.), enter the inside of the
enclosure. Feed the cable from the conduit
through one of the conduit attachment holes
into the terminal area. Connect the conduit to
the conduit connection threaded hole on the
side of the transducer. Attach the cable wires
to the appropriate terminals. The unused con-
nection hole should be closed with a suitable
conduit plug.
The transducer should be wired with a multi-
conductor shielded cable. Figures 3 and 4
show how the current and voltage output
transducers should be wired. The transducer
housing should be earth grounded at the
ground screw using one of the cable’s conduc-
tors as shown in Figures 3 and 4.
When the cover is reinstalled, make sure the
gasket is seated correctly and all four screws
are properly engaged and tightened.
© 2015 Ashcroft Inc., 250 East Main St., Stratford, CT 06614-5145, U.S.A. Tel: 203-378-8281, Fax: 203-385-0499, email: info@ashcroft.com, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M011-10062 (250-2985) Rev. I 06/15
CALIBRATION
The zero adjustment for the transducer can be
accessed by unscrewing the four cover screws
and removing the zero pot access cover (see
Fig. 1). Once the cover is removed, make sure
no contaminants, (e.g. water, oil, chemicals,
grease, dirt, etc.), enter the enclosure. The
zero adjustment range is approximately ±10%
of span.
The offset or zero adjustment potentiometer is
shown in Figure 1. A hole is provided in the
fiber insulation board to access the pot adjust-
ment screw. Before you adjust, make sure a
short tube is connected from the “low” port to
the “high” port of the transducer. This connec-
tion will ensure that both ports are at the same
pressure. A clockwise rotation raises the output.
DO NOT ADJUST THE SPAN
ADJUSTMENT POTENTIOMETER
Proper span calibration requires a pressure
standard three to five times more accurate
than the accuracy of the transducer.
When the cover is reinstalled, make sure the
gasket is seated properly and all four screws
are properly engaged and tightened.
SERVICE
There are no user serviceable parts inside the
transducer. Servicing should only be carried
out by factory-trained personnel. Service prob-
lems encountered in the field might be
mechanical or electrical in nature.
Mechanical problems might be attributed to
plugged or leaking pressure lines, or faulty
pressure sources.
Electrical problems might be attributed to
improper wiring, bad connections (e.g. open,
shorts, etc.), malfunctioning or improper power
supply.
PH SICAL
Weight: approx. 2 lbs.
NEMA 4X rated enclosure
OPTIONAL FEATURES
Variable Damping
A third potentiometer, placed to the left of
the zero potentiometer, allows the user to
adjust the unit’s response time.
Multiple Range
By relocating the shunt jumper, the user can
“re-range” the unit. The unit can be re-
ranged by a 1⁄2, 1⁄3, 1⁄4and a 1⁄5. For example, a
unidirectional 5 in. W.C. unit can become a
2.5 in. W.C., 1.67 in. W.C., 1.25 in. W.C. or a
1.0 in. W.C. range.
THIS PAGE
INTENTIONALLY
BLANK
I&M 011-10062-1-01 250-2985-I.qxp_special 6/24/15 10:31 AM Page 4
71B241 H

250 EAST MAIN STREET,








CAD GENERATED DRAWING,
DO NOT MANUALLY UPDATE

 
for any other purpose or discosed to others, and it will
DIMENSIONAL TOLERANCES
FRACTIONS DECIMALS ANGLES
CHAMFER:
PRESSURE TRANSMITTERS
DATE
SERIES DIFFERENTIAL
STRATFORD, CT 06614
K. Kavgaci
01-06-2014
UNLESS OTHERWISE SPECIFIED
UNLESS OTHERWISE SPECIFIED
DRAWN BY
1 deg
B
DIMENSIONS ARE IN INCHES
TOLERANCES ARE:
be returned on demand.
ANGLE:
FOR TYPE IXLdp, RoHS, XFM
!
" #
SHEET 1 OF 1
$%
SCHEMATIC DIAGRAM
5 deg
DO NOT SCALE DRAWING
!
#"&
'
(
)
) ( ' &
3 PLACE DECIMAL: .000 .007
2 PLACE DECIMAL: .00 .015
1 PLACE DECIMAL: .0 .030
This drawing includes confidential information which is
the property of ASHCROFT INC.
This copy is loaned for a specific purpose, with the
understanding that it will not be reproduced or used
IMPORTANT:
DIMENSIONS WITHIN OVAL AND NOTES IDENTIFIED WITH " * " REQUIRE MANDATORY INSPECTION.
$*++,-.-/-.$+/,$0$+
1,2


3..$+
0/.$-$3
HAZARDOUS (CLASSIFIED) LOCATION
4554!4,4"67"89:;<,<
NON-HAZARDOUS (UNCLASSIFIED) LOCATION
4554 4,4"67"89:;<=<

*
->,$%>!&8%$-$%
*!
0%,$.0$
,,$..$+0%
,..$++/,0$-0.$-,$*0$+
1+,20+$%?%:;5$?:;5
$@A5$B@A5.?.

*#
$%0+.$$,$/-++..$%
*"$,/$$$-+,$/-++..$%0,+$
*&1/.,2
0/.$,$/,..$+0
..$+00,$+
%:;+B%5%+<
:;BC5<
.:;.B.<
B@A<
B@A
*'
.$4$. !'
*(
,$% 50,+$,
..$+0,-..$%+$/.
*)
,$%!+%,$
.50..$+0,-..$%
+$0/.$%,$.
*D$*.0$
* 8$*E+.-+$F
*0$+
*
=.:C4*G,.:<
%:;7#8%5:;7 88:5.:;7 57&8,578H0
Item Qty Part No Description Material Finish Dwg. No. Used On
H 6354 REDRAW IN S'WORKS. DELETED SHEET 2,3&4.
ADDED THE FM CONT. DOC. TABLE KK 3/10/2014
G 0002246
REDRAWN IN SOLIDWORKS. REVISED FORMAT &
VIEW TO DELETE REFERENCE TO DRESSER AND
REPLACE WITH ASHCROFT INC.
ALH 02/13/2006
Rev ECO DESCRIPTION BY DATE
AGENCY: FILE/CERT#
CSA N/A
FM 2V5A0AX
CONTROLLED DOCUMENT
No changes permitted without prior approval by:
MOUNTING
FOOT
➤
➤
➤
➤
➤
➤
➤
ø 0.2
1.4
4.31
➤
➤
➤
➤
➤
0.2 TYP
2) PLACES
MOUNTING FOOT
2.68
ACCESS COVER (TERMINAL BLOCK)
➤
➤
MOUNTING FOOT
SPAN POT
ZERO POT
LOCATION
➤
➤
➤
➤
➤
➤
2.7
4.6
➤
➤
0.7
➤
➤
5
➤
1/2 NPSM THREAD TYP BOTH
SIDES FOR CONDUIT PIPING
ACCESS COVER
(ZERO AND SPAN POTS)
3
➤
➤
➤
➤
2.5
➤
➤
➤
➤
➤
➤
➤
➤
0.8 1.34
3.0
0.7
HIGH LOW
1/4 NPT
PRESSURE
FITTINGS
➤
➤
Figure 1.
General Dimensions (INCHES)
OPERATING
REGION
LOOP SUPPLY VOLTAGE (VDC)
010 12 20 30 36 40
1250
1045
1000
750
500
250
0
LOOP RESISTANCE (OHMS)
LOAD LIMITATION 4-20mA OUTPUT ONLY
Figure 2. Loop Supply Voltage vs. Loop Resistance
Figure 3.
Current (4-20mA) Output Wiring
min = 12 + (.022A x RL)
RL= RS+ RW
RL= Loop Resistance (ohms)
RS= Sense Resistance (ohms)
RW= Wire Resistance (ohms)
*INCLUDES A 10% SAFETY FACTOR
Figure 4.
Voltage Output Wiring
MODEL IXLdp TRANSDUCER
INSTRUCTION SHEET
Hazardous Area Specific Guidelines:
1. Do not open unit when energized.
2 .Do not disconnect equipment unless area is
known to be non-hazardous.
FM Installation Notes:
SEE DRAWIN 71B241-1
Intrinsically-Safe Entity Barrier Parameters:
Definition of Entity Concept: The entity concept
allows interconnection of intrinsically safe
apparatus to associated apparatus not specifi-
cally examined in such combination. The crite-
ria for interconnection is that the voltage and
current which intrinsically-safe apparatus can
receive and remain intrinsically-safe, consider-
ing faults, must be equal to or greater than the
voltage and current levels which can be deliv-
ered by the associated apparatus, considering
faults and applicable factors. In addition, the
maximum unprotected capacitance and induc-
tance of the IS apparatus, including the inter-
connecting wiring, must be equal or less than
the capacitance and inductance which can be
safely connected to the associated apparatus.
The “entity parameters” were broadened to
allow IXLdp users the freedom to apply the
IXLdp into a wider array of applications.
Additionally, the inclusion of a “nonincendive”
rating gives our customers the ability to
choose an intrinsically safe barrier from any
barrier manufacturer meeting the below ratings.
© 2015 Ashcroft Inc., 250 East Main St., Stratford, CT 06614-5145, U.S.A. Tel: 203-378-8281, Fax: 203-385-0499, email: info@ashcroft.com, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M011-10062 (250-2985) Rev. I 06/15 © 2015 Ashcroft Inc., 250 East Main St., Stratford, CT 06614-5145, U.S.A. Tel: 203-378-8281, Fax: 203-385-0499, email: info@ashcroft.com, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M011-10062 (250-2985) Rev. I 06/15
I&M 011-10062-1-01 250-2985-I.qxp_special 6/24/15 10:31 AM Page 2

Other Ashcroft Transducer manuals

Ashcroft GC30 User manual

Ashcroft

Ashcroft GC30 User manual

Ashcroft GC55 User manual

Ashcroft

Ashcroft GC55 User manual

Ashcroft CXLdp Instruction Manual

Ashcroft

Ashcroft CXLdp Instruction Manual

Ashcroft IXLdp User manual

Ashcroft

Ashcroft IXLdp User manual

Ashcroft IXLdp User manual

Ashcroft

Ashcroft IXLdp User manual

Ashcroft IXLdp User manual

Ashcroft

Ashcroft IXLdp User manual

Ashcroft ZL91 Instruction Manual

Ashcroft

Ashcroft ZL91 Instruction Manual

Ashcroft A2X User manual

Ashcroft

Ashcroft A2X User manual

Ashcroft CXLdp Assembly instructions

Ashcroft

Ashcroft CXLdp Assembly instructions

Ashcroft k1 User manual

Ashcroft

Ashcroft k1 User manual

Ashcroft KM15 User manual

Ashcroft

Ashcroft KM15 User manual

Popular Transducer manuals by other brands

S+S Regeltechnik THERMASGARD TM 65 - EtherCAT P Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik THERMASGARD TM 65 - EtherCAT P Operating Instructions, Mounting & Installation

MKS 907 Series instruction manual

MKS

MKS 907 Series instruction manual

Simrad 200-28E -  REV B datasheet

Simrad

Simrad 200-28E - REV B datasheet

Lumel P30U series user manual

Lumel

Lumel P30U series user manual

HBM T5 Mounting instructions

HBM

HBM T5 Mounting instructions

HBM TB1A Mounting instructions

HBM

HBM TB1A Mounting instructions

Daiichi Electronics FAETT2-92A-33 instruction manual

Daiichi Electronics

Daiichi Electronics FAETT2-92A-33 instruction manual

Multitek PowerSig M560-AT operating manual

Multitek

Multitek PowerSig M560-AT operating manual

Electro-Voice 3-Inch High Frequency Neodymium Transducer... Technical specifications

Electro-Voice

Electro-Voice 3-Inch High Frequency Neodymium Transducer... Technical specifications

Endress+Hauser Cerabar T PMC131 technical information

Endress+Hauser

Endress+Hauser Cerabar T PMC131 technical information

novotechnik LWG Series manual

novotechnik

novotechnik LWG Series manual

halstrup-walcher PU10 instruction manual

halstrup-walcher

halstrup-walcher PU10 instruction manual

Omega PX279 manual

Omega

Omega PX279 manual

HBM PAD4001A quick start guide

HBM

HBM PAD4001A quick start guide

OHIO SEMITRONICS DCT Series operating instructions

OHIO SEMITRONICS

OHIO SEMITRONICS DCT Series operating instructions

Siemens XRS-5 Quick start manual

Siemens

Siemens XRS-5 Quick start manual

M-system 18PV instruction manual

M-system

M-system 18PV instruction manual

Raymarine DownVision CPT-70 installation instructions

Raymarine

Raymarine DownVision CPT-70 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.