Ashcroft KM15 User manual

Other Ashcroft Transducer manuals

Ashcroft GC30 User manual

Ashcroft

Ashcroft GC30 User manual

Ashcroft ZL91 Instruction Manual

Ashcroft

Ashcroft ZL91 Instruction Manual

Ashcroft IXLdp User manual

Ashcroft

Ashcroft IXLdp User manual

Ashcroft CXLdp Instruction Manual

Ashcroft

Ashcroft CXLdp Instruction Manual

Ashcroft IXLdp User manual

Ashcroft

Ashcroft IXLdp User manual

Ashcroft IXLdp User manual

Ashcroft

Ashcroft IXLdp User manual

Ashcroft IXLdp User manual

Ashcroft

Ashcroft IXLdp User manual

Ashcroft k1 User manual

Ashcroft

Ashcroft k1 User manual

Ashcroft CXLdp Assembly instructions

Ashcroft

Ashcroft CXLdp Assembly instructions

Ashcroft A2X User manual

Ashcroft

Ashcroft A2X User manual

Ashcroft GC55 User manual

Ashcroft

Ashcroft GC55 User manual

Popular Transducer manuals by other brands

LEM DK series installation guide

LEM

LEM DK series installation guide

HBM AD101B quick start guide

HBM

HBM AD101B quick start guide

Camille Bauer SINEAX F534 operating instructions

Camille Bauer

Camille Bauer SINEAX F534 operating instructions

Trane KIT 16724 Installer's guide

Trane

Trane KIT 16724 Installer's guide

Lumel P18 user manual

Lumel

Lumel P18 user manual

B&C Speakers DE75PTN datasheet

B&C Speakers

B&C Speakers DE75PTN datasheet

Mianyang Weibo Electronic WB Series user manual

Mianyang Weibo Electronic

Mianyang Weibo Electronic WB Series user manual

ProMinent Dulcometer DMT operating instructions

ProMinent

ProMinent Dulcometer DMT operating instructions

Camille Bauer SIRAX CH-5610 operating instructions

Camille Bauer

Camille Bauer SIRAX CH-5610 operating instructions

Veris Industries PW Series installation guide

Veris Industries

Veris Industries PW Series installation guide

HBM TJ1-S6 installation manual

HBM

HBM TJ1-S6 installation manual

Simrad ES120-7C -  REV D Dimensions

Simrad

Simrad ES120-7C - REV D Dimensions

HBM C18 Mounting instructions

HBM

HBM C18 Mounting instructions

Spirax Sarco ITV1030 Installation and maintenance instructions

Spirax Sarco

Spirax Sarco ITV1030 Installation and maintenance instructions

MAMAC SYSTEMS PR-243 technical information

MAMAC SYSTEMS

MAMAC SYSTEMS PR-243 technical information

Balluff BTL5-P user guide

Balluff

Balluff BTL5-P user guide

MKS MicroPirani 925 Series Short form manual

MKS

MKS MicroPirani 925 Series Short form manual

WIKA WU-20 operating instructions

WIKA

WIKA WU-20 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

KM15 PRESSURE TRANSDUCER
INSTRUCTION SHEET
Output Type Ex itation Supply Current
0.5/4.5 V
Ratiometric 5V±.5 Vdc 10mA typ
1/5V 8-32 Vdc 10mA typ
© 2011 Ashcroft Inc., 250 E. Main St., Stratford, CT 06614-5145, Tel: 203-378-8281, Fax: 203-385-0408, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M011-10168. Rev. A 5/11
Teflon is a registered trademark of E. I. DuPont
RoHS Compliant
WARNING! READ
BEFORE INSTALLATION
1. GENERAL:
A failure resulting in injury or dam-
age may be caused by excessive
overpressure, excessive vibration or
pressure pulsation, excessive instru-
ment temperature, corrosion of the
pressure containing parts, or other
misuse. Consult Ashcroft Inc.,
Stratford, Connecticut, USA before
installing if there are any questions
or concerns.
2. OVERPRESSURE:
Pressure spikes in excess of the rated
overpressure capability of the trans-
ducer may cause irreversible ele tri-
al and/or me hani al damage to the
pressure measuring and containing
elements.
Fluid hammer and surges can destroy
any pressure transducer and must
always be avoided. A pressure snub-
ber should be installed to eliminate the
damaging hammer effects. Fluid ham-
mer occurs when a liquid flow is sud-
denly stopped, as with quick closing
solenoid valves. Surges occur when
flow is suddenly begun, as when a
pump is turned on at full power or a
valve is quickly opened.
Liquid surges are particularly damag-
ing to pressure transducers if the pipe
is originally empty. To avoid damaging
surges, fluid lines should remain full (if
possible), pumps should be brought up
to power slowly, and valves opened
slowly. To avoid damage from both fluid
hammer and surges, a surge chamber
should be installed.
Symptoms of fluid hammer and surge's
damaging effects:
• Pressure transducer exhibits an out-
put at zero pressure (large zero offset).
• Pressure transducer output remains
constant regardless of pressure
• In severe cases, there will be no output.
FREEZING:
Prohibit freezing of media in pressure
port. Unit should be drained (mount in
vertical position with electrical termi-
nation upward) to prevent possible
overpressure damage from frozen
media.
3. STATIC ELECTRICAL CHARGES:
Any electrical device may be suscepti-
ble to damage when exposed to static
electrical charges. To avoid damage to
the transducer observe the following:
• Ground the body of the transducer
BEFORE making any electrical con-
nections.
• When disconnecting, remove the
ground AST!
Note: The shield and drain wire in the
cable (if supplied) is not connected to
the transducer body, and is not a suit-
able ground.
Mounting
The KM15 transducer requires no special
mounting hardware, and can be mounted
in any plane with negligible position error.
Although the unit can withstand normal
vibration without damage or significant
output effects, it is always good practice
to mount the transducer where there is
minimum vibration.
For units with NPT type pressure fittings
apply Teflon®tape or an equivalent
sealant to the threads before installing.
When tightening, apply a wrench to the
hex wrench flats located just above the
pressure fitting. DO NOT tighten by using
a pipe wrench on the housing.
Noise
For minimum noise susceptibility, avoid
running the transducer’s cable in a con-
duit that contains high current AC power
cables. Where possible avoid running the
cable near inductive equipment.
Shield Wiring
(Cable Termination Only)
Connect the braided shield to the guard
terminal on the reading instrument
(meter, etc.) if available or to ground or to
the power supply negative terminal.
Vent Tube (Cable Termination Only)
The cable will have a clear Teflon®vent
tube that's required at pressure below
500 psi to provide atmospheric refer-
ence. The open end should be placed in
a dry area.
KM15 PRESSURE TRANSDUCER
INSTRUCTION SHEET
(10)(7)(14.5)
(25) DIA.
(49.5) Lead Length As Specified By Customer
Lead Length Less 50mm (2˝)
.28˝
.58˝
2˝
1˝
Protective Sleeve
Red : Power (+)
White: Output (+)
Black : Common
.4˝
0.5mm2
20 AWG Leads
2 ft. Standard Length
FLYING LEAD STYLE
Dimension Dra ing
Dimensions
in ( ) are mm
Dimension Drawing
(Height may vary slightly depending
on process connection)
Mating Conne tor
Mates to HW090 Connector by Sumitomo Wiring
Systems. Made of PBT (polybutylene terephthalate).
Flying Leads : 20AWG, 3 ft. (.9m) standard
PIN Color Fun tion
1 Red Supply (+)
2 White Output (+)
3 Black Common
(25)
DIA.
.57˝ .28˝
(64)
1.00˝
2.5˝
(14.5) (7)
1
2
3
3
2
1
Dimensions
in ( ) are mm
CONNECTOR STYLE TERMINATION
3-Wire Voltage
+
+
–
–
POWER
SUPPLY (Common)
(+ Power)
(+ Output)
METER
TRANSDUCER
METER OR
OTHER DEVICE
WIRING DIAGRAM FOR ALL KM15 TRANSDUCERS
© 2011 Ashcroft Inc., 250 E. Main St., Stratford, CT 06614-5145, Tel: 203-378-8281, Fax: 203-385-0408, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M011-10168. Rev. A 5/11
(21.3)
(B) (C) (A)
Common
Power(+)
Black
Red(B)
(A)
METRI-PACK 150 Series SHIELDED CABLE
OutPut(+)White(C)
MAT I NG CONNECTOR
(20) (50)
(10)
(24.5)
(.84")
(.97")
(.79")
.39"
1.97"
Lead Length As Specified By Customer
OPTIONAL
12065287
PIN
METRI-PACK 150 Series
OUTPUT(+) POWER(+)
COMMON
(25 DIA.)
(7)(14.5)
(71.6)
.27".57"
(2.8")
.98" DIA.
MAT E S TO OPTIONAL METRI-PACK
CONNECTOR 12065287
Dimensions
in ( ) are mm
METRI-PACK
Dimension Dra ing
Cab
le
Housing
Fitting
(870) 34
˝
Std.
(10)
( )
(50)
(14.5)
)
(7)
( )
(75.5)
(20) DIA.
.78
˝
(12)
(25) DIA.
.98
˝
(9)
(18.5)
SS Case
.27
˝
.
.57
˝
.73
˝
.47
˝
.4
˝
2
˝
3
˝
(19)
DIA.
(17)
HEX.
Red:Power(+)
White:Output(+)
Black:Common
.75˝
.35˝
.67˝
SHIELDED CABLE TERMINATION
Dimension Drawing
(Height may vary slightly depending on process connection)
Dimensions
in ( ) are mm