
-4-
INSTALLATION
POSITIONING THE STOVE
It is very important to position the stove as close as possible to the chimney, and in an area that will favor the
most efcient heat distribution possible throughout the house. The stove must therefore be installed in the room
where the most time is spent, and in the most spacious room possible. Recall that stoves produce radiating
heat, the heat we feel when we are close to a stove. A stove also functions by convection, that is through
the displacement of hot air accelerated upwards and its replacement with cooler air. If necessary, the hot air
distribution from the stove may be facilitated by the use of a fan or blower.
FREE STANDING STOVE INSTALLATION
A stove must never be installed in a hallway or near a staircase, since it may block the way in case of re or fail
to respect required clearances. It is of the utmost importance that the clearances to combustible materials be
strictly adhered to during installation of the stove. Refer to the table and diagrams below for minimum required
clearances.
• Do not place any combustible material within 4’ (1.2m) of the front of the unit.
• The clearance between the ue pipe and a wall are valid only for vertical walls and for vertical ue pipe.
• The chimney connector must not pass through an attic or roof space, closet or similar concealed space, a
oor, or a ceiling.
Back wall / Arrière Mur
Side wall / Paroi Latérale
Side wall / Paroi Latérale
Back wall / Arrière Mur
Side wall / Paroi Latérale
Side wall / Paroi Latérale
Back wall / Arrière Mur
Ceiling / Plafond
Floor Protector / Protection de Plancher
K
H
L
J
M M
C
B
A
E
E
D
D
F
G
Back wall / Arrière Mur
Side wall / Paroi Latérale
Side wall / Paroi Latérale
Back wall / Arrière Mur
Side wall / Paroi Latérale
Side wall / Paroi Latérale
Back wall / Arrière Mur
Ceiling / Plafond
Floor Protector / Protection de Plancher
K
H
L
J
M M
C
B
A
E
E
D
D
F
G
Back wall / Arrière Mur
Side wall / Paroi Latérale
Side wall / Paroi Latérale
Back wall / Arrière Mur
Side wall / Paroi Latérale
Side wall / Paroi Latérale
Back wall / Arrière Mur
Ceiling / Plafond
Floor Protector / Protection de Plancher
K
H
L
J
M M
C
B
A
E
E
D
D
F
G
Dimension Inch mm
A Backwall to Stove 11 280
B Sidewall to Stove 7 178
C Sidewall to Flue 17.3 440
D Wall to Stove (Angled
Installation)
3 77
E Wall to Flue (Angled Installation) 14.4 366
F Ceiling Height 84 2134
G Backwall to Flue 14.8 376
SAFETY NOTICE
• If this stove is not properly installed, a house re may result. To reduce the risk of re, follow the installation
instructions.
• Consult your municipal building department or re ofcials about permits, restrictions and installations
requirements in your area.
• Use smoke detectors in the room where your stove is installed.
• Smoke expelled from the unit, by either paint curing, opening the fuel loading door, or a negative pressure
inside the home, could trigger the smoke detectors. Mount smoke detectors at least 10’ from stove
• Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter uid, or similar liquids to start or
“freshen up” a re in this heater. Keep all such liquids well away from the heater while it is in use.
• In the event of a chimney re, push the air control full closed to deprive the re of oxygen. Call the re
department.
• A source of fresh air into the room or space heated shall be provided when required.
• Room heater, solid fuel type, also for use in mobile homes.
• For Canadian installations, where passage
through a wall, or partition of combustible
construction is desired, the installation must
conform to CAN/CSA-B365.
• A ue pipe crossing a combustible wall
must have a minimum clearance of 18”
(457.2mm).
• To reduce ue clearances from
combustible materials, contact your local
safety department.