Autocall A49AO-APPLW User manual

579-1034AC Rev G
TrueAlert ES Addressable Indoor A/O Notification Appliances Installation Instructions
*05791034ACG*
Cautions, warnings, and regulatory information
IMPORTANT: When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that requires
immediate attention of all occupants.
SAFETY: Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety precautions and instructions
may result in loss of life and property due to non-functioning notification appliances. Some notification appliances use high voltage. To avoid electrical
hazards and avoid damage to appliances, make sure that the electrical power for the Notification Appliance Circuit is disconnected at the control
panel before installing, repairing, or internally adjusting any notification appliances. Even with electrical power removed, some notification appliances
(such as visible strobes) store a high voltage charge. The high voltage can cause injury resulting in death from electrical shock. DO NOT TOUCH
EXPOSED CIRCUITRY.
LOCATION REFERENCE: Location and quantity of appliances required must conform to the applicable local standards and guidelines (the National
Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm Systems; the appropriate model building codes,
etc.) and specific requirements of the Local Authority Having Jurisdiction (AHJ). These notification appliances are not intended for installation within
hazardous locations as defined by the National Electrical Code (NEC) or NFPA.
Introduction
Table 1: UL listed TrueAlertES indoor product identification reference
Type Colors Models Operation
Wall Mount Horn Audible
Only (AO) Red
White
Components:
A49AO-APPLW
Backplate:
A49MP-AVVOWR
A49MP-AVVOWW
Covers:
A49AOC-WRFIRE
A49AOC-WRS
A49AOC-WWFIRE
A49AOC-WWS
These appliances provide an audible
(AO) warning of an alarm condition when
activated from the control panel of a
compatible UL/ULC Listed, Autocall Fire
Alarm System.
Note: For information about TrueAlertES appliance testing, see TrueAlert ES Addressable Appliances testing and applications guide (579-1049).
Mounting instructions
Table 2: Kit contents
Kit contents Appliance x 1 Cover x 1 Backplate x1 with 8-32 1 inch mounting screws x 2, and 6-32 1 inch mounting screws x 2.
Not included Electrical box 1-1/2 inch (38.1 mm) minimum depth required: single gang, double gang, or 4 inch (101.6 mm) square.
1. Select the mounting location and install the electrical box using screws suitable for the mounting surface. See Figure 1 for mounting and
location information.
2. Bring the building wiring through the rectangular opening in the backplate.
3. Connect the building wires to the backplate. See Wiring Instructions on page 2.
4. Secure the backplate to the electrical box using the provided hardware. Install with the writing Install this side up at the top. Use a torque
wrench to tighten the screws to 12-15 inch-pounds. Do not over-tighten the screws.
5. Attach the cover to the appliance.
6. Set the appliance settings. See Setting the address DIP Switch on page 3.
7. Attach the assembled appliance onto the backplate.
NFPA 72 requires that
the device is not
less than 80 in. (203.2 cm)
and not greater than
96 in. (243.8 cm) above
the finished floor.
Single gang, double gang, or
4 in. (101.6 mm) square electrical box
Backplate
Appliance cover
Building wire
Screws: Use 8-32 screws for a 4 in. (101.6 mm) square electrical box
Use 6-32 screws for a single or a double gang electrical box
Appliance
100%
Fig 1: Mounting Instructions

Page 2 579-1034AC Rev G
TrueAlert ES Addressable Indoor A/O Notification Appliances Installation Instructions
Wiring Instructions
WARNING: Make sure that all power is disconnected before starting the installation.
1. At the electrical box, connect the building wiring to the CKT + and CKT - terminals on the backplate.
2. To ensure proper continuity, use a torque wrench to tighten the terminal block screws to 12-15 inch-pounds.
3. Ensure that correct polarity is maintained for each unit.
4. Signaling Line Circuit (SLC) wiring must be twisted pair (TWP). CKT terminals accept two wires: 12-18 American Wire Gauge (AWG) TWP.
IMPORTANT: Do not bring the conduit through the rear of the electrical box. Strip the lead insulation to 7/16 inch maximum.
Appliance backplate
From a compatible
SLC controller,
see notes
Terminal 2
CKT+
Terminal 1
CKT-
Class A wiring, see notes
(T-tapping example)
A/O A/O A/O
A/O
A/OA/O
A/O
From a compatible
SLC controller,
see notes Class B wiring, see notes
To the next appliance
or compatible SLC
controller, see notes
100%
Fig 2: Wiring Instructions
Wiring notes
• The maximum number of appliances on a circuit or on an IDNAC SLC is 127. The maximum wire resistance between appliances is 26 ohms.
See the field wiring diagrams for the driving compatible fire alarm control panel for further instructions.
• Notification appliances are rated using an individual module label.
• Maintain the correct polarity on the terminal connections.
• Terminals 1 and 2 can each accommodate two wires, one wire going in and one wire going out to the next appliance.
• TrueAlert SLC wiring connections are supervised and power-limited.
• These appliances are rated to the operating voltage limits of 17-31 VDC. The appliance may fail to operate as intended, and cause permanent
damage to this equipment if it operates outside of these limits.
• Only operate the TrueAlertES AO appliances using a compatible power supply.
• T-tapping is not permitted on Class A wiring.

Page 3 579-1034AC Rev G
TrueAlert ES Addressable Indoor A/O Notification Appliances Installation Instructions
Setting the address DIP Switch
Each addressable TrueAlertES notification appliance has a unique address that is set using an eight position DIP switch (ADDR1). Assign up to 127
unique addresses to an SLC, however, the total appliance loading available may be less due to appliance current requirements.
To set the address, complete the following steps:
1. Insert a number 1 or number 2 Phillips screwdriver, or a similar sized object, into the opening at the bottom of the appliance and unclip the
appliance from the backplate. See Figure 3.
2. Set the switches using a non-metallic stylus, or the equivalent.
3. Record the set address.
To access the switches:
ADDR1
The DIP switch shown is
set at address 7
Not used
001 101 011 111
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
DIP SWITCHES 5 THROUGH 7
000 100 010 110
Fig 3: Setting the DIP Switch Address
Setting the horn configuration switch
Certain options for the horn can be configured directly on the appliance using the Configuration switch (CFIG1) on the back of the appliance. See
Figure 4.
Table 3: AO Settings
Position 1 Configuration Control: OFF to enable Local Audible control
(positions 2-7 below), ON for Panel control.
Position 2 Audible Volume: High (OFF), Low (ON).
Position 3 CAN Horn mode: switch must be set to OFF.
Position 4 Legacy NAC mode: switch must be set to OFF.
Position
5, 6, 7, 8
These switches are unused by the horn. Leave them set to
OFF.
To access the switches:
CFIG1
Device
configuration switch
Not used (Leave at OFF)
Fig 4: Setting the
Appliance Configuration

579-1034AC Rev G
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Autocall
product supplier for the latest status. Listings and approvals under Tyco Fire & Security GmbH, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National
Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
Appliance specifications
Table 4: Environmental specifications
Rated voltage range Special application 17 - 31 VRMS
Temperature range 32° F to 120° F (0° C to 49° C)
Humidity range 10% to 93%, non-condensing at 104° F (40° C)
Connections Terminal for 18 AWG to 12 AWG (0.82 mm² to 3.31 mm²)
Table 5: Sound pressure level measurement (dBA)
Reverberant Room at 10 Feet
in accordance with UL464 (See
Note 2)
Voltage (Vrms) Horn mode steady Horn mode coded (see note 1)
High volume setting using
addressable controller (See Note 3)
17 (Min.)
23
31 (Max.)
87.6
89.8
91.9
83.1
86
86
Low volume setting using
addressable controller (See Note 3)
17 (Min.)
23
31 (Max.)
80.6
83.4
86.2
76.9
79.2
82.3
Anechoic Room at 10 feet in accordance with ULC S525, see note 4.
High volume setting
17 (Min.)
23
31 (Max.)
89.9
92.5
94.4
89.6
92.4
93.9
Low volume setting
17 (Min.)
23
31 (Max.)
84.1
86.7
89.1
83.6
86.6
88.6
Note:
1. The coded category covers both Temporal and March time cadences.
2. Reverberant dBA measurements are a minimum UL rating based on sound power level measurements made in UL’s reverberant test chamber.
3. High and low volume settings are configured with DIP switch (CFIG1) on the controller.
4. If you install the A4905-9838 Sound Damper, the anechoic measurements decrease by approximately 9 dBA.
Table 6: Current draw
Application Appliance type Maximum RMS current
UL464/ULCS525 (0° C TO 50° C) AO 23 mA
Table 7: ULC directional characteristics for horn
Access Angle dBA
61.5° left and right -3 dBA
Horizontal 90° left and right -4.6 dBA
62° up and down -3 dBA
Vertical 90° up and down -3.8 dBA
CAUTION:
• The appliances are available in red and white. Do not paint or otherwise alter the factory finishes in any way.
• Anechoic dBA levels below 85 do not meet ULC requirements for public notification.
This manual suits for next models
2
Other Autocall Fire Alarm manuals
Popular Fire Alarm manuals by other brands

Teletek electronics
Teletek electronics SIMPO BASIC INFORMATION

Eaton
Eaton CF1100 Installation and operation manual

SILENT KNIGHT
SILENT KNIGHT INTELLIKNIGHT 5820XL installation manual

UniPOS
UniPOS EVPU FD 8010 instruction manual

Notifier
Notifier UniNet 2000 Simplex 4010 NION Installation and operation manual

Electro Detectors
Electro Detectors ZERIO PLUS EDA-Z5008 user manual

Honeywell
Honeywell Notifier AM12-24 manual

Aico
Aico Residential Fire Detection RFD Product guide

GST
GST DI-9406 quick start guide

Notifier
Notifier ID50 SERIES operating manual

Kidde Fire Systems
Kidde Fire Systems PEGAsys Installation, operation and maintenance manual

Zeta
Zeta Premier M plus Log book & certificates