manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Ziton
  6. •
  7. Fire Alarm
  8. •
  9. Ziton ZP755BV-4P Assembly instructions

Ziton ZP755BV-4P Assembly instructions

© 2021 Carrier. All rights reserved. 1 / 4 P/N 10-5202-501-ZV01-12 • ISS 05OCT21
ZP755BV-4P Addressable Base Sounder with
Visual Indicator Installation Sheet
Description
The ZP755BV-4P is an addressable base sounder with visual
indicator, designed for use in Ziton addressable fire detection
and alarm systems.
Note: The visual indicator of this product does not comply with
EN 54-23 and must not be used in fire alarm installations
where fire notification beacons are required.
The sounder includes a volume control, an address-setting
switch, programmable tone settings, and a pair of jumpers to
select the operating power — from the addressable loop or an
external supply. The device plugs into a base that is purchased
separately. See Table 1 for a list of model numbers.
Table 1: Models
Model
Description
ZP755
BV-4P Base sounder/Visual indicator, Polar white
ZP755
-COV-P Cover for ZP755B Base sounder
with no detector, Polar white
ZP755
-COV-R Cover for ZP755B Base sounder
with no detector, Red
SPB
–2P Mounting base, Polar white
Installation
To install the device:
1. Wire the base
2. Set the operating power
3. Set the address
4. Set the operating mode
5. Set the tone
6. Set the volume
7. Mount the sounder onto the base
The details of each step are given below
Wiring the base
Connect the loop wiring for the base as shown in Figure 1.
There is no wiring between the sounder and base.
Figure 1: Loop wiring for the base
1. Ext. 24 VDC+ IN/OUT
4.
Ext. 24 VDC ground IN/OUT
5. Loop+ IN/OUT
7. Shield
8. Loop − IN/OUT
Setting the operating power
The sounder includes a pair of power selection jumpers, J1
and J2. To select the source of the sounder operating power,
position the jumpers as shown in Figure 2.
Figure 2: Power-selection jumper configuration
1.
Loop powered 2. External 24 VDC
Note: When using an external power supply, use only one that
is CE and EN 54-4 compliant to power all the sounders on the
same loop. Ensure connection to number 1 and number 4 in
addition to the loop wiring number 5 and number 8.
8
4
5
1
J1 J1J2 J2
21
2 / 4 P/N 10-5202-501-ZV01-12 • ISS 05OCT21
Setting the address
The sounder includes a seven-segment DIP switch (SW1) for
assigning device addresses. Each switch segment has a
decimal value as shown in Figure 3. The address is the sum of
all the switch segments in the ON position. The switch is used
to set the device address in binary code. The switch may be
set to represent any address from 1 to 127.
For example, to select a device address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
Figure 3: Address switch setting
Mode, tone, and volume settings
The sounder includes a seven-segment DIP switch (SW2) to
select the operating mode, tone, and volume. See Figure 4.
Figure 4: Mode of Operation switch settings
1. Power selection jumpers
2.
SW2 configuration switch
3.
Tone
4. Addressing mode
5 Visual indicator operating
mode
6. Volume
Setting the addressing mode
Configure the base sounder to operate with or without a
detector at the same address as shown in Table 2.
Table 2: Setting address mode
Switch
Setting
SW2
-4 OFF The sounder is stand-alone with a unique
loop address not used by another detector.
SW2
-4 ON The sounder shares the address with a
detector to expand the number of devices
supported by the loop.
Configure the base sounder to enable or disable the visual
indicator as shown in Table 3.
Table 3: Setting Visual Indicator operating mode
Switch
Setting
SW2
-5 ON Enable the
visual indicator.
SW2
-5 OFF Disable the
visual indicator.
Not recommended with
Silent tone.
Setting the volume
Use SW2-6 and SW2-7 to set the volume. Level 1 is the lowest
volume setting, and level 4 is the highest as shown in Table 4.
Refer also to the measured anechoic sound levels in Figure 7.
Table 4: Volume settings
00
– Level 1 10 – Level 2 01 – Level 3 11 – Level 4
Average dBA
measurement
3
dBA less than
level 2.
3 dBA less
than level 3.
3 dBA less
than level 4.
Certified tones
[1].
[1] UK-continuous, UK intermittent, UK two-tone are EN 54-3
compliant.
Setting the tone
The control panel can operate the sounder in two different pre-
programmed tones, by selecting SW2-1, SW2-2, and SW2-3.
Refer to Table 5 Tone settings.
Note: Two additional tones are available, the Class change
and the Visual indicator only tone. However, these tones may
not be available for legacy control panels. Please refer to the
configuration options of your control panel to confirm tone
availability.
Table 5: Tone settings
Device mode
SW2 switch setting -1-2-3 Primary warning Secondary evacuation Attention (nonfire)
ZP755
0 UK intermittent UK continuous Class change
ZP755
1 UK continuous UK two-tone Class change
ZP755
2 UK two-tone UK intermittent Class change
ZP755
3 Australian whoop Australian alert Class change
ZP755
4 Swedish tone Dutch slow whoop Class change
ZP755
5 ISO8201 French two-tone Class change
ZP755
6 German Visual indicator only Class change
ZP754
7 UK intermittent UK continuous Class change
1
2
3 6
4
5
P/N 10-5202-501-ZV01-12 • ISS 05OCT21 3 / 4
Table 6: Tones
Tone
name Description Freq (Hz) Cycle time
UK
continuous [1] Continuous
(UK)
980 Continuous
UK
intermittent [1] Intermittent fast
0.5 s (UK)
980 1s (1 Hz) 0.5 s on, 0.5 s
off
UK
two-tone [1] Two-tone (UK) 980
670
0.5 s tone 1
0.5 s tone 2
Australia
n whoop Australian slow
whoop
ascending
500 to 980 4 s
Australian alert
[2] Australian alert
ISO7731
440 0.55 s on, 0.55
s off ± 10%
Swed
ish tone Swedish fast
pulse
670 0.33 – 0.55 s
(3-4 Hz)
Pulse ratio
>0.35 < 0.7
Dutch
slow whoop Dutch slow
whoop
ascending
500 to
1200
4s
3.5 s on 0.5 s off
ISO
8201 Temporal
ISO8201
3 pulse and
wait
980 4 s
0.5 s on/0.5 s off
1.5 s wait
Fr
ench two tone French two-
tone
554
440
90-110ms
380-420ms
= 500 ms ± 5%
German
German fast
whoop
descending
1200 to
500
1 s
no “off”
Class
Change
3 tones and
wait
1000,
1200, 1500
4s
Visual Indicato
r
only
Silent and
visual indicator
only
[1] The tones UK-continuous, UK-intermittent, and UK-two-tone are EN 54-3
compliant.
[2] ISO7731.
Figure 5: Mounting
1. Base
2. Release aid (3X)
3. Release/lock catch
4. Addressable sounder
Mounting the sounder
Align the addressable sounder to the base. Push up (A) and
turn the sounder until it clicks into place (B). Push the sounder
up once more to engage (C). Refer to Figure 5.
To remove the sounder from the base, the three release aid
tabs must be depressed, and then the sounder can be
detached.
Sounders per loop
The sounder can be powered directly from the loop of Ziton
control panels. Use Table 5 Tone settings, in conjunction with
Figure 6, to determine the quantity of detectors and sounders
that can be connected to a two-core shielded loop when loop
powered.
Figure 6: Detector/sounders per loop
A. Cable length panel to first sounder
B.
Cable length first to last sounder
C.
Cable length last sounder to panel
1. Detectors and Sounders
Table 7: Maximum detectors and sounders per loop
A
B C Quantity allowed [1]
10 m
980 m 10 m 60 detectors and 35 sounders
90 detectors and 30 sounders
100 m
800 m 100 m 50 detectors and 35 sounders
90 detectors and 30 sounders
200 m
600 m 200 m 40 detectors and 35 sounders
90 detectors and 30 sounders
300 m
400 m 300 m 40 detectors and 30 sounders
90 detectors and 25 sounders
[1] Using a two-core shielded loop of 1000 meters cable size 1.5 mm²
Specifications
Operating voltage
External supply
Loop supply,
ZP protocol
18 to 30 VDC
19.5 to 20.5 V pulsed, max. 4 V line
loss
Current (line powered)
Quiescent (RMS)
Alarm (RMS)
Alarm (excluding device
address)
Alarm (at device
address)
500 µA
6 mA
14 mA max.
14 mA max.
Current (externally powered)
Quiescent (RMS)
Alarm (RMS)
Maximum number
470 µA
500 µA
35 per 1 km loop (subject to cable size
and sounder spacing)
Strobe
Frequency
Light output
Flash rate 1.1 seconds
Less than 1J xenon element
4
3
2
1
A
B
C
4 / 4 P/N 10-5202-501-ZV01-12 • ISS 05OCT21
Tones
See Table 5 Tone settings.
See Table 6 Tones.
Sound distribution
Wide
Measured
anechoic sound
levels
See Figure 7
Monitoring
Operating power level
Sound output level
Tested continuously
Self test facility
Compatibility
Ziton addressable systems
Addressing method
7-segment DIP switch
Mounting
Surface, with base
Wiring
Two-core loop
Construction
Material
Weight
Dimensions (Ø × D)
Moulded thermoplastic
156 g
127 × 47 mm incl. base
Operating environment
Temperature
Relative humidity
−10 to +60°C
10 to 95%, noncondensing
Storage temperature
−20 to +70°C
Figure 7: Measured anechoic sound levels
Note: These measurements correspond to the highest level for the
EN 54-3 compliant tones of UK-continuous, UK intermittent, and UK-two-
tone.
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Certification
Certification body
0370
Declaration of
Performance number
360-5202-0199
Year of first CE
marking 14
Product Identification
ZP755BV-4P
Intended use
See the product Declaration of
Performance
Declared performance
See the product Declaration of
Performance
Manufacturer
Carrier Safety System (Hebei) Co. Ltd.,
80 Changjiang East Road, QETDZ,
Qinhuangdao 066004, Hebei, China.
Authorized EU manufacturing
representative:
Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
2012/19/EU (WEEE Directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste
in the European Union. For proper
recycling, return this product to your local
supplier upon the purchase of equivalent
new equipment, or dispose of it at
designated collection points. For more
information see: recyclethis.info.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND
INSTALLATION BY QUALIFIED PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY
ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR
“AUTHORIZED RESELLER”, IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers
and product safety information, please check
https://firesecurityproducts.com/policy/product
-
warning/
or scan the QR code:
165
O
105
O
75
O
45
O
15
O
135
O
dBA 65 70 75 80 856570758085

Other Ziton Fire Alarm manuals

Ziton ZP787-3 Assembly instructions

Ziton

Ziton ZP787-3 Assembly instructions

Ziton ZP755R-2 Assembly instructions

Ziton

Ziton ZP755R-2 Assembly instructions

Ziton ZP700 Series Assembly instructions

Ziton

Ziton ZP700 Series Assembly instructions

Ziton ZP2-AF1-S User manual

Ziton

Ziton ZP2-AF1-S User manual

Ziton ZR4ST-3 User manual

Ziton

Ziton ZR4ST-3 User manual

Ziton ZR432-2P Assembly instructions

Ziton

Ziton ZR432-2P Assembly instructions

Ziton ZP2 Series User manual

Ziton

Ziton ZP2 Series User manual

Ziton ZP2-A Series User guide

Ziton

Ziton ZP2-A Series User guide

Ziton ZR432-2P Assembly instructions

Ziton

Ziton ZR432-2P Assembly instructions

Ziton ZP2-LB Assembly instructions

Ziton

Ziton ZP2-LB Assembly instructions

Ziton ZP2 Series User guide

Ziton

Ziton ZP2 Series User guide

Ziton zp1-f Series User guide

Ziton

Ziton zp1-f Series User guide

Ziton ZP787-3 Assembly instructions

Ziton

Ziton ZP787-3 Assembly instructions

Ziton ASWP-RF User manual

Ziton

Ziton ASWP-RF User manual

Ziton ZP1-F2 User manual

Ziton

Ziton ZP1-F2 User manual

Popular Fire Alarm manuals by other brands

Bosch FPA-5000 System Information

Bosch

Bosch FPA-5000 System Information

UniPOS FD 7120 instruction manual

UniPOS

UniPOS FD 7120 instruction manual

Cooper Wheelock RSS-24110W installation instructions

Cooper Wheelock

Cooper Wheelock RSS-24110W installation instructions

Siemens FC2005 Programming manual

Siemens

Siemens FC2005 Programming manual

Secutron MR-3500 Series Installation and operation manual

Secutron

Secutron MR-3500 Series Installation and operation manual

Faraday MPC-6000 Programming manual

Faraday

Faraday MPC-6000 Programming manual

Simplex 2606-9101 Series installation guide

Simplex

Simplex 2606-9101 Series installation guide

Notifier NFS2-3030 operating instructions

Notifier

Notifier NFS2-3030 operating instructions

Potter PFC-7500 installation manual

Potter

Potter PFC-7500 installation manual

Stahl MCP/BG Series operating instructions

Stahl

Stahl MCP/BG Series operating instructions

Fire-Lite Alarms MS-4424 manual

Fire-Lite Alarms

Fire-Lite Alarms MS-4424 manual

GE 521NB installation instructions

GE

GE 521NB installation instructions

Evacuator Defender Wireless Alarm instructions

Evacuator

Evacuator Defender Wireless Alarm instructions

Notifier AFP-300 Programming manual

Notifier

Notifier AFP-300 Programming manual

Brooks RFP V2 Series Operation & installation manual

Brooks

Brooks RFP V2 Series Operation & installation manual

BR RABC Series manual

BR

BR RABC Series manual

Ellard Fire Door Control Panel Product instructions

Ellard

Ellard Fire Door Control Panel Product instructions

Autronica BS-420 Operator's handbook

Autronica

Autronica BS-420 Operator's handbook

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.