Autronica AUTROSAFE 4 - User manual

116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01, Autronica Fire And Security AS
Commissioning Handbook
AutroSafe Interactive Fire Detection System
Release 4

COPYRIGHT ©
This publication, or parts thereof, may
not be reproduced in any form, by any
method, for any purpose.
Autronica Fire and Security AS and its
subsidiaries assume no responsibility
for any errors that may appear in the
publication, or for damages arising
from the information in it. No
information in this publication should
be regarded as a warranty made by
Autronica Fire and Security AS. The
information in this publication may be
updated without notice.
Product names mentioned in this
publication may be trademarks. They
are used only for identification.
Commissioning Handbook, AutroSafe Interactive Fire Detection System, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01, Autronica Fire and Security
E-1676
This product contains static-sensitive devices. Avoid any electrostatic discharge.
The WEEE Directive
When the marking below is shown on the
product and/or its literature, it means that
the product should not be disposed with
other household wastes at the end of its
life cycle. During waste treatment,
disposal and collection, please separate
the product from other types of wastes
and recycle it responsibly to promote the
sustainable reuse of material resources.
This product should not be mixed with
other commercial wastes for disposal.

Introduction
Table of Contents
1. Introduction......................................................................5
1.1 About the Handbook..........................................................................5
1.2 The Reader .......................................................................................5
1.3 Reference Documentation.................................................................6
2. Quick Reference Guide ...................................................7
2.1 Initial Commissioning ........................................................................7
2.2 Upgrading System Software and Configuration................................7
3. Verifying the Loops .........................................................8
3.1 AS-2000 Loop Diagnostic Tool .........................................................8
3.2 Verification Procedure.......................................................................8
4. Consistency Check of Configuration Data.....................9
4.1 Introduction........................................................................................9
4.2 Parameters Used for the Consistency Check...................................9
4.3 Importing Loop Data from the AS-2000 Tool ....................................10
4.4 Consistency Check Using the AS-2000 / Config Mismatch Tool.....10
4.5 Generating Configuration Files .........................................................10
5. Power Commissioning....................................................11
5.1 Addressing Power Boards on the AutroFieldBus..............................11
5.1.1 Switch Settings on Power Board BSF-400 .............................11
5.1.2 Location of Switches...............................................................11
5.1.3 AutroFieldBus Addresses .......................................................13
5.1.4 Power Board Configuration Switches .....................................14
5.2 Calibration Procedure - Power Unit BPS-410...................................15
6. Addressing Panels ..........................................................16
6.1 Definitions..........................................................................................16
6.1.1 Network ID ..............................................................................16
6.1.2 Panel ID ..................................................................................16
6.2 Location of Switches .........................................................................17
6.3 Assigning Network IDs......................................................................18
6.4 Assigning Panel IDs..........................................................................19
7. Verifying the System Before Startup..............................21
8. Startup Procedure ...........................................................22
8.1 Applying Power to the System ..........................................................22
8.2 IP Number Structure..........................................................................24
8.3 Assigning IP Adresses ......................................................................24
8.3.1 Automatic Addressing Mode...................................................25
8.3.2 Manual Addressing Mode .......................................................27

Introduction
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 4
8.3.3 Configuration Missing..............................................................28
8.4 Configuration File ..............................................................................29
8.4.1 Name, Format and Extension .................................................29
8.4.2 Copying the Zip File to a USB Stick........................................29
8.5 Uploading Configuration Files to the System....................................30
8.6 Configuration Mismatch.....................................................................33
8.7 Entering Required Access Levels .....................................................34
9. Verifying the System after an Upload.............................36
9.1 General System Verification Procedure............................................36
9.2 Verifying Detection Loops During Normal Operation........................37
10.Upgrading the System.....................................................38
10.1 Introduction........................................................................................38
10.2 Upgrading During Normal Operation (SW/Config)............................38
10.2.1Introduction .............................................................................38
10.2.2Upgrading Software During Normal Operation.......................39
10.2.3Upgrading Configuration During Normal Operation................39
10.3 Upgrading when Panels are Added/Removed..................................40
10.4 Upgrading if IP Addresses are to be Changed..................................40
10.5 Upgrading a Single Panel..................................................................40
10.6 Upgrading by Remote Access to a Web site.....................................41
10.7 Upgrading Software Version 4.0.1 to 4.1.1.......................................42
10.7.1General ...................................................................................42
10.7.2Preparing a System in Normal Operation...............................42
10.7.3Preparing a System in System Fault Condition ......................43
10.8 Upgrading Software Version 4.0.1 or 4.1.1 to 4.3.1..........................44
10.8.1Example 1: Upgrading all Panels from SW Version 4.0.1
or 4.1.1 to 4.3.1......................................................................44
10.8.2Example 2: Adding a BS-420/BS-430 panel with SW
Version 4.1.1 to a System Running on SW Version 4.3.1......44
10.8.3Example 3: Adding a BC-420 Controller with SW Version
4.1.1 to a System Running on SW Version 4.3.1 ...................44
10.8.4Example 4: Adding a Panel with SW Version 4.3.1 to a
System Running on SW Version 4.1.1....................................45
11.Startup Procedure for a Dual Safety System.................46
11.1 Introduction........................................................................................46
11.2 Guidelines – Startup Procedure........................................................47
12.Fault Messages during Uploading..................................49
12.1 Introduction........................................................................................49
12.2 Invalid File on USB Stick...................................................................49
12.3 Data Transmission Timeout ..............................................................49
12.4 Corrupt File........................................................................................49
12.5 Fail to Unpack Files...........................................................................50

Introduction
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 5
1. Introduction
E-1676
This product contains static-sensitive devices.
Always use an antistatic wrist strap / ground bracelet to avoid any
electrostatic discharge.
1.1 About the Handbook
This handbook is intended to provide all necessary information for the
commissioning of the AutroSafe Interactive Fire Detection System,
Release 4.
The handbook covers the commissioning of a standalone system (Fire
Alarm Control Panel), as well as the commissioning of a distributed
system with several system units, operating on Autronica’s local area
network; AutroNet, including:
Power Boards in Power Cabinet BP-405 and
Power Unit BPS-405/BPS-410 (AutroFieldBus addressing)
Fire Alarm Control Panel BS-420
Controller BC-420 / BC-440
Operating Panel BS-430
Repeater Panel BU-BV-420
1.2 The Reader
The handbook is intended to be used by Autronica Fire and Security
trained service and technical personnel who are responsible for the
installation of the AutroSafe Interactive Fire Detection System,
Release 4.

Introduction
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 6
1.3 Reference Documentation
The table below shows an overview of the technical marketing
documentation for AutroSafe Interactive Fire Detection System,
Release 4.
Document Name
Part number
File name
System Description
116-P-ASAFE-SYSTEMD/EGB
asafesystemd_egb
Installation Handbook
116-P-ASAFE-INSTALL/DGB
asafeinstall_dgb
Commissioning Handbook
116-P-ASAFE-COMMISS/EGB
asafecommiss_egb
User Guide, Remote Access
116-P-ASAFE-REMOTEAC/EGB
asaferemoteac_egb
Connecting Loop Units
116-P-CONNECTLOOPUNIT/DGB
connectloopunit_dgb
Operator’s Handbook
116-P-ASAFE-OPERATE/FGB
asafeoperate_fgb
User Guide
116-P-ASAFE-USERGUI/LGB
asafeusergui_lgb
Wall Chart
116-P-ASAFE-WALLCHA/LGB
asafewallcha_lgb
Menu Structure
116-P-ASAFE-MENUSTR/MGB
asafemenustr_mgb
Datasheet; Fire Alarm Control Panel BS-420
116-P-BS420/CGB
bs420_cgb
Datasheet; Operator Panel BS-430
116-P-BS430/CGB
bs430_cgb
Datasheet; Repeater Panel BU-BV-420
116-P-BUBV420/CGB
bubv420_cgb
Datasheet; Fire Brigade Loop Panel BU-110
116-P-BU110/CGB
bu110_cgb
Datasheet; Information Loop Panel BV-110
116-P-BV110/CGB
bv110_cgb
Datasheet; Controller BC-420
116-P-BC420/CGB
bc420_cgb
Datasheet; Controller Unit Rack BC-440
116-P-BC440/CGB
bc440_cgb
Datasheet; Power Cabinet BP-405
116-P-BP405/CGB
bp405_cgb
Datasheet; Power Unit BPS-405
116-P-BPS405/CGB
bps405_cgb
Datasheet; Power Unit BPS-410
116-P-BPS410/CGB
bps410_cgb
Datasheet; AutroKeeper BN-180
116-P-BN180/CGB
bn180_cgb

Quick Reference Guide
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 7
2. Quick Reference Guide
This quick reference guide outlines all the necessary steps to
successfully commission the AutroSafe Interactive Fire Detection
System the very first time, assuming that the system software is
already uploaded to the system, and no configuration files have been
uploaded.
Configuration upgrade and system software upgrade are described in
a separate chapter (Chapter 10).
2.1 Initial Commissioning
Step Action Chapter
1
Verify the detection loops by means of the AS-2000 tool. Chapter 3
2
Perform a consistency check of the configuration data
using the results from the AS-2000 verification and the data
that has been configured by means of the AutroSafe
Configuration Tool.
Chapter 4
3
Assign an AutroFieldBus address to each Power Board
BSF-400 (rotary switches) / AutroFieldBus unit. Chapter 5
4
Assign a Network ID to each panel by means of rotary
switches (on BSA-400). Chapter 6.3
5
Assign a Panel ID to each panel by means of switches (dip-
switches and rotary switches on BSA-400). Chapter 6.3
6
Verify the system before startup Chapter 7
7
Apply power to the system Chapter 8.1
8
Assign an IP Address to each panel Chapter 8.3
9
Upload configuration data to all panels from one central
point (a panel). Chapter 8.5
10
Verify the system after an upload Chapter 9
2.2 Upgrading System Software and Configuration
For information regarding configuration upgrade and system software
upgrade, refer to Chapter 10.

Verifying the Loops
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 8
3. Verifying the Loops
3.1 AS-2000 Loop Diagnostic Tool
All loops should be verified with the AS-2000 Loop Diagnostic Tool
before startup. Although this is presumably already done at an earlier
stage (shortly after the installation), it is recommended that all loops
are verified once again in case minor changes have been done. By
doing this, you will eliminate possible problems which could occur
during the startup procedure and upgrading of configuration data.
The AS-2000 allows you to find all points connected to the selected
loop driver, and present them graphically.
AS-2000 can be connected directly to an AutroSafe
operating panel, or directly to a detection loop by means of an
external interface unit, WAS-2000.
3.2 Verification Procedure
Pressing the START button in the Topology window (AS-2000) tells
AS-2000 to find all points connected to the selected loop driver, and
present them graphically in a correct electrical sequence. Points will
be presented with unique symbols for each type of Loop Unit, and with
important information such as Production Number (PN), and the Loop
Sequence Index (LSI). In case of illegal topologies, like multiple
branch-offs and loop breaks, these will be presented with self-
explaining symbols.
Use the AS-2000 to;
register all loop units on each loop, including:
−the Loop Unit type
(detector type, manual call point, electronic sounder, I/O unit)
−Loop Sequence Indexes LSI
(order/location)
register all branch offs and loop break positions
locate any breaks on the loop wire (both positive and negative
wires)
measure the loops’ total resistance, current consumption and
voltage drop
earth fault
You will find detailed information on the installation and use of
AS-2000 in the User Guide, AS-2000 Loop Diagnostic Tool.

Consistency Check
of Configuration Data
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 9
4. Consistency Check
of Configuration Data
4.1 Introduction
4.2 Parameters Used for the Consistency Check
The table below provides a description of two of the parameters that
are used for the consistency check. These parameters are shown in
the Topology View in AS-2000, as well as in the topology view in the
AutroSafe Configuration Tool.
Parameter
Abbreviation
Description
Illustration
Loop Unit The loop unit
can be a
detector, a
manual call
point, a loop
sounder or an
I/O unit.
(Examples)
Heat detector (BD-200/300/500)
Optical smoke detector (BH-200/300/500)
MultiSensor detector (BH-220/320/520)
Manual callpoint (BF-200/300/500)
Electronic addressable sounder
(BBR-200)
Input / Output unit (BN-300, BN-310, BN-320 etc.)
Loop
Sequence
Index LSI A loop specific
index telling the
exact Loop Unit
order on the
loop
(sequencially
numbered).
A branch-off is
described by a
decimal
followed by a
sequencial
index.
NOTE:
To ensure a problem-
free upload of configuration data, always
perform a consistency check, using the results from the
AS-2000 verification and the data that has been configured by
means of the AutroSafe Configuration Tool.
(Example)

Consistency Check
of Configuration Data
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 10
4.3 Importing Loop Data from the AS-2000 Tool
The AutroSafe Configuration Tool features an Import command
allowing you to import loop data directly from the AS-2000 Loop
Diagnostic tool. In this way, it is possible to ensure that the point types
and sequence indexes in the configuration will be identical to the real
loop. Tag Names and optional Detection Zones (DZs) will be assigned
to the points during import.
For further information, refer to the Help System for AutroSafe
Configuration Tool and the User Guide for the AS-2000 Loop
Diagnostic Tool.
4.4 Consistency Check Using the
AS-2000 / Config Mismatch Tool
4.5 Generating Configuration Files
System configuration is done from a computer by the means of the
AutroSafe Configuration Tool. This tool allows you to generate
configuration files, which then can be uploaded to target after the
system has been verified.
The AutroSafe Configuration Tool allows you to do a
consistency check of configuration data by means of a menu
called AS-2000 / Config Mismatch Tool (in the Tool menu).
This feature allows you to easily compare the actual
configuration data downloaded from a detection loop and
imported to the AutroSafe Configuration Tool (using
the AS-2000) with the configuration data you have entered in
the AutroSafe Configuration Tool.

Power Commissioning
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 11
5. Power Commissioning
5.1 Addressing Power Boards on the AutroFieldBus
5.1.1 Switch Settings on Power Board BSF-400
The board is configured by means of two switches:
Rotary switches X10 and X11 - AutroFieldBus address switch.
Each Power Board is given a unique address.
Dipswitch S5/S6 – configuration (refer to dipswitch table, chapter
5.1.4)
5.1.2 Location of Switches
The location of the dipswitch S5 and S6, plus the rotary switches X10
and X11 are shown on the drawing.

Power Commissioning
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 12
1
2
3
AFB A
AFB A"
AFB CT A
4
5
6
AFB Earth Fault Sense
AFB B
AFB B"
7
8AFB CT B
AFB Earth Fault Sense
J2
16
1
2
3
A
A
R
4
5
6
F
F
F
F1
F2
J19
S1 Reset
High Low
8
7
6
5
4
3
2
1
J24
J23
J22
0V
C2
J21
F2AL
F3 B1
F2AL
F4 B2
F2AL
F5 C1
F2AL
F6 C2
A
1
2
3
Earth Fa
Battery
AFB pre
4
5
6
Battery
61
S6
ON
OFF
15
5
4
3
2
1
Therm.+
Therm.-
PSF
-V
Vcon +-
BATT
J20
J17
F7 Battery
F8 Charger
1
Charger +24V
J18
+
0V
+
C1
0V
+
B2
0V
+
B1
0V
+
A2
0V
+
A1
X11 X10
BP-410/01
BP-405/01
T10
T5
T10
T5
F7 F8
AH AH
AH AH
S5
AFB Earth Fault Off
AFB Earth Fault On
1
OFF
ON
2
OFF
ON
Dipswitch S6
AutroFieldBus
Address Switch
X10, X11
Dipswitch S5
S1 Reset button

Power Commissioning
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 13
5.1.3 AutroFieldBus Addresses
Each AutroFieldBus unit/Power Board BSF-400 on an AutroFieldBus
must be assigned a unique address by means of an rotary switch (see
previous page).
The drawing below shows the AutroFieldBus connections on the main
terminal block, list L1 mounted on a DIN rail inside the cabinet
(BS-420/BC-420). The first AutroFieldBus unit is connected to the
terminals L1.9 / L1.11 (AFB A). The last unit is connected to L1.3 /
L1.5 (AFB B).
CT (CenterTap) of transformer shall not be connected (terminal 3 and
11). Shield is connected to earth at one end only.
L1.3
L1.5
L1.7
L1.15
L1.9
L1.11
L1.13
Last AFB unit
First AFB unit
SA 400 with shielded AF cable
BSA-400 with unshielded AFB cable
L1.9
L1.11 Last AFB unit
A maximum of 31 AutroFieldBus units can be connected to one
AutroFieldBus, giving the number range 01 to 31. The physical
addresses are set by means of the rotary switches on the board.
The illustration below shows an example of the system topology
window. 4 AutroFieldBus units are added to the AutroFieldBus
interface.
The sequence of the units in the topology window determines the
switch settings on each unit, i.e. the first unit (the uppermost unit in
the topology window) is to be given switch address 01, the next is to
be given switch address 02, and so on.
Note that the physical sequence of AutroFieldBus units on the
AutroFieldBus must not necessarily correspond to the sequence
shown in the topology window, however this is recommended.
Addressing AutroFieldBus units on the AutroFieldBus
Fire Alarm Control
Panel BS-420
BSA-400
BSF-400
BSD-321
BSF-400
AutroFieldBus
Switch
Address 01
BSF-400
Switch
Address 02
Switch
Address 03
Switch
Address 04
Always address 00
The first AutroFieldBus unit
Example: System topology window in
the AutroSafe Configuration Tool
Switch address 01
Switch address 02
Switch address 03
Switch address 04
Main terminal block, list L1
inside the BS-420/BC-420
AFB
AFB

Power Commissioning
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 14
5.1.4 Power Board Configuration Switches
The settings of the dipswitches are read during startup. If the switches
are changed for any reason, the changes will not take affect until the
Power Board is restarted (pressing the reset button S1 on the Power
Board).
Dipswitch table – S5
S5.1
S5.2
Function
OFF
OFF
AutroFieldBus earth fault OFF
ON
ON
AutroFieldBus earth fault ON
Dipswitch table –S6
Switch
Name
Comment
S6-1 Earth Fault
ON: Earth fault monitoring
activated
OFF: Earth fault monitoring
deactivated
S6-2 NA
Must always be set to OFF
(default).
S6-3 AutroFieldBus
ON: AutroFieldBus connected
OFF: AutroFieldBus not
connected
S6-4
NA
-
S6-5
Battery
ON: Battery connected
OFF: Battery not connected
S6-6
Power Unit Type
ON: BPS-405
OFF: BPS-410

Power Commissioning
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 15
5.2 Calibration Procedure - Power Unit BPS-410
When using Power Unit BPS-410 (including a 24V/10A power supply),
a calibration procedure must be performed. This is necessary in order
to obtain a correct temperature compensated charging voltage to the
batteries. The procedure is as follows:
Before applying power to the system, the power supply’s
temperature sensor (thermistor delivered with the power unit) must
be temporarily replaced with a fixed 2,2kresistor (terminal point 2
and 6 from the left, marked with a stippled line from terminal point
2 to the thermistor symbol at point 6).
Apply power to the system by connecting the mains cable to the
mains socket or by switching the power ON from an external main
fuse box.
Measure the voltage on the BSF-400’s battery terminals (BATT +/-)
while adjusting the voltage with a small screw driver to 27,4V on
the power supply (OUT ADJ).
Disconnect mains power from the power supply and remove
charger fuse F8.
Remove the resistor and reinsert the thermistor.
Insert the charger fuse F8 and re-connect mains power to the
power supply.
15
5
4
3
2
1
Therm.+
Therm.-
PSF
-V
Vcon +-
BATT
J20
J17
arger
1
+24V
BP-405/01 T5 T5
AH AH
AH AH
0V
C2
15
5
4
3
2
1
Therm.+
Therm.-
PSF
-V
Vcon +-
BATT
J20
J17
F7 Battery
F8 Charger
1
Charger +24V
BP-410/01
BP-405/01
T10
T5
T10
T5
F7 F8
AH AH
AH AH
Measure
Adjust
Charger fuse F8

Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 16
6. Addressing Panels
6.1 Definitions
6.1.1 Network ID
A panel’s Network ID indicates which system and unique configuration
a panel belongs to. All panels communicating on the same AutroNet
network must have the same Network ID, usually set to 01 (switch
setting; rotary switches X5 and X3).
The Network ID also determines the specific number series of the IP
Addresses (which are set during commissioning by operating the
AutroSafe menu).
6.1.2 Panel ID
Each panel in the system must be assigned a unique Panel ID (switch
setting; rotary switches X6 and X4, plus the settings of dip-switch S2).
For each different panel type (i.e. BS-420 or BU-420) the addressing
on the rotary switches always starts on 0-1.
The Configuration Tool generates a catalogue structure with the
following number series of Panel IDs for the different panel types.
(Note that the physical adressing on the rotary switches does not
follow the numbering series generated by the Configuration Tool).
Panel Panel IDs
Number Series
Panel IDs
Hexadecimal
values
BS-420
1-31
01-1F
BC-420
33-63
21–3F
BC-440
33-63
21–3F
BS-430
65-95
41-5F
BU-420
97-159
61-9F
BV-420
161-223
A1-DF

Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 17
6.2 Location of Switches
The switches are located on the lower left hand side of the BSA-400
circuit board, easily accessible through the hole in the metal cover.
The BSA-400 circuit board
X3
X5
X6
X4
S2

Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 18
6.3 Assigning Network IDs
The settings of the rotary switches X5 and X3 determine the panel’s
Network ID, i.e. which system and unique configuration the panel
belongs to.
All panels communicating on the same AutroNet network must have
the same Network ID, usually set to 01.
X5 is set to 0
X3 is set to 1
If there is a second network, this network can be set to 02, a third can
be set to 03, etc.
Switch X5 corresponds to the most significant digit in the address.
X3
X5

Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 19
6.4 Assigning Panel IDs
Each panel in the system must be assigned a unique Panel ID (switch
setting; rotary switches X6 and X4, plus the settings of dip-switch S2).
For each different panel type (i.e. BS-420 or BU-420) the addressing
on the rotary switches always starts on 0-1.
Note that a standalone Fire Alarm Control Panel BS-420 always has
Panel ID=00.
Switch X6 corresponds to the most significant digit in the address.
Note that the correct switch settings for the panel type in question is
preset at the factory (dipswitch S2) - except for the BU-BV-420 panel,
as this panel can be defined both as a Information Panel and Fire
Brigade Panel.
The following table deals with the Panel IDs when several panels
communicate on the AutroNet (local area network).
Panel
Panel ID
Panel ID
Hex.
values Rotary
switch X6
Rotary
switch X4
Panel Type
Dip-switch S2
0=OFF, 1=ON
Switch 1 2 3 4
BS-420
1-31
01-1F
0-3
0-9
0 0 0 0
BC-420
33-63
21–3F
0-3
0-9
1 0 0 0
BC-440
33-63
21–3F
0-3
0-9
1 0 0 1
BS-430
65-95
41-5F
0-3
0-9
0 1 0 0
BU-420
97-159
61-9F
0-6
0-9
1 1 0 0
BV-420
161-223
A1-DF
0-6
0-9
1 0 1 0
X6
X4
S2

Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 20
Example:
A network configuration consists of two BS-420 panels, one BS-430
panel and one BU-BV-420 panel (a BU-BV-420 panel defined as a
Fire Brigade Panel).
In this example, the following addressing applies:
Panel
Panel ID
Rotary
switch X6
Rotary
switch X4
Panel Type
Dip-switch S2
0=OFF, 1=ON
Switch 1 2 3 4
BS-420
1
0
1
0 0 0 0
BS-420
2
0
2
0 0 0 0
BS-430
65
0
1
0 1 0 0
BU-BV-420
97
0
1
1 1 0 0
Other manuals for AUTROSAFE 4 -
1
Table of contents
Other Autronica Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Keller
Keller CellaTemp PA 4 Series quick start guide

Smart Sensor
Smart Sensor AR925 instruction manual

PCB Piezotronics
PCB Piezotronics J352C34 Installation and operating manual

Precision Rated Optics
Precision Rated Optics LS-100 SERIES Operation guide

Solinst
Solinst 102 instructions

Tenmars
Tenmars HB2TM102001 user manual