AV-GAD EasyLoader AV-2005 User manual

Ea s y L o a d e r
AV-2005 & AV-2008
Integrated Alarm Control/Communicator
Year 2000 ready
Installation and Operation Manual
Version 2.17C
Edition IIII
This product is subject to continuous enhancements and therefore
specifications may be changed or altered without prior notice

2
Table of Contents
CONTENTS PAGE
SECTION I: SYSTEM FEATURES ................................................................................ 4
1. INTRODUCTION...................................................................................................... 4
1.1 GENERAL DESCRIPTION.................................................................................... 4
1.2 FEATURES......................................................................................................... 5
1.3 PROGRAMMABLE FEATURES............................................................................. 5
1.4 ALARM OUTPUTS ............................................................................................. 5
1.5 TECHNICAL SPECIFICATIONS SERIES 2000........................................................ 7
1.6 ORDERING INFORMATION ................................................................................. 9
SECTION II: INSTALLATION ................................................................................ 10
1. MOUNTING .............................................................................................................. 10
1.1 CONTROL PANEL MOUNTING............................................................................ 10
1.2 ZONE WIRING MODE ........................................................................................ 11
1.3 KEYPAD WIRING .............................................................................................. 13
2. ALARM OUTPUTS................................................................................................... 15
2.1 SIRENS.............................................................................................................. 15
2.2 SIREN CONNECTIONS........................................................................................ 15
2.3 WIRING AND CONNECTION OF RELAY MODULE ............................................... 16
2.4 REMOTE INDICATION ........................................................................................ 16
3. WIRING AND POWERING UP ............................................................................... 17
3.1 GROUNDING – LIGHTNING PROTECTION ........................................................... 17
3.2 BACK UP BATTERY .......................................................................................... 17
3.3 BEFORE POWERING UP..................................................................................... 18
3.4 CONNECTING SMOKE DETECTORS .................................................................... 18
3.5 TELEPHONE SYSTEM (DIALER) DIALING AND WIRING ...................................... 19
3.6 SVM - VOICE MODULE .................................................................................... 19
3.7 REMOTE KEY AND WIRELESS ARMING & DISARMING...................................... 20
3.8 AUTO ARMING ................................................................................................. 20
3.9 ARMING MULTIPLE ALARM PANELS................................................................. 21
SECTION III: AV-701/702 DIGITAL KEYPAD...................................................... 22
1.1 KEYPAD FUNCTIONS......................................................................................... 22
1.2 HOLD-DOWN FUNCTIONS ................................................................................. 24
1.3 AV-2008 GOLDEN; ACCESS VIA CODE............................................................. 29
1.4 SOUNDER.......................................................................................................... 30

3
1.5 LED INDICATORS ............................................................................................. 31
1.6 KEYPAD DIGITAL DISPLAY (7-SEGMENT TYPE)................................................. 32
1.7 ARMING AND DISARMING................................................................................. 33
SECTION IV: PROGRAMMING ............................................................................. 34
1. SYSTEM CODES ...................................................................................................... 34
1.1 USER CODE PROGRAMMING ............................................................................. 35
2. FEATURE PROGRAMMING AT INSTALLER LEVEL ........................................ 36
2.1 PROGRAMMING SHEET (VERSION 2.17)............................................................. 36
2.2 INTRODUCTION ................................................................................................. 40
2.3 PROGRAMMING SHEET EXPLANATION .............................................................. 40
2.4 GLOSSARY OF PROGRAMMABLE FEATURES ...................................................... 41
2.7 PROGRAMMING EXAMPLES............................................................................... 46
2.8 RESET SYSTEM TO DEFAULT PROGRAMMING ................................................... 50
2.9 DIALER - COMMUNICATOR EXPLANATION AND PROGRAMMING....................... 51
2.9.1 DELETING TELEPHONE NUMBERS.................................................................. 52
2.9.2 USER PROGRAMMING OF ‘FOLLOW-ME’ TELEPHONE NUMBER ..................... 52
2.10 QUITTING PROGRAMMING MODE ................................................................... 53
2.11 VERIFICATION OF CURRENT PROGRAMMING .................................................. 54
2.12 REMOTE UP AND DOWNLOAD ........................................................................ 54
3. TROUBLESHOOTING ............................................................................................. 59
SECTION V: WIRING DIAGRAM .............................................................................. 62
SERIES 2000 AND 860 WIRING DIAGRAM ................................................................... 62
SECTION VI: INDEX.................................................................................................... 63
AV-GAD LIMITED WARRANTY........................................................................... 65

4
SECTION I: SYSTEM FEATURES
1. INTRODUCTION
1.1 General Description
Av-Gad's EasyLoader TM Series is a microprocessor-based intruder alarm panels with integrated
communicator and modem for up and download. They feature eight or five plus one panic zone, each
programmable.
Series 2000 represent the state-of-the-art in user-friendly, reliable alarm control panels for security
requirements of small and medium-size commercial, residential, and industrial installations.
Read this manual before installing AV-2004, AV-2048 (for further details refer to AV-2004/48
Express Installation Manual).
Av-Gad's EasyLoader TM versatile control panels meet and surpass all requirements for reliability
and maintains. Provide the added benefits of easy installation and simple operation.
The PRO Version is an upgraded model of the Series 2000 panels, specially designed to be
compatible with AV-707 and AV-706 (English Text) keypads.
The Series 2000 comprise an enhanced power supply, improved electronics and additional signaling
indicators.
The innovative keypads (AV-701, AV-702 and AV-707) are unquestionably the user-friendliest
remote station, designed to enable easy control of the system by the end-user, as well as by the
installer. For PRO users: AV-706/7 LCD keypads have a separate manual, wiring and features are
unchanged, read this manual before using and installation.
Version 2.08 - 2.17 news
Four new features as described in address 073
Improved display of AC fail during armed mode
Auto Arming option
New Tamper features and software filtering
Improved telephone interface meets international standards
Selectable ‘0V’ or ‘Low’ at alarms outputs
2.09: Sleep Mode during AC fail. Zone bypass recorded in the history log, SVM module can be
triggered by SLO or by ON output. Improved programming of user code – Pause after entering the
user index
2.10: Ring Detector with software rings counting
2.11: Ring Detector adjustment by software at address 093, new address 074-3
2.12: Available at 2000 PRO: New eight automatic timers. ‘Green Reset Zone’ default to all zones
2.13: For special PRO version with Aux. Power Cut; provides control via SLO (074-4)
2.14: Special PRO UK version; 250 events log, central station verification
2.16 PRO only; two bypass groups, Police Zone, supports AV-707B, telephone line monitor, line
fault listed in events log
2.17: Improved PCB with additional +12V terminal, New Panic Zone; address 045, enhanced
events log display, telephone line monitor, zones set to Green type by default, new ring detector
features at address 095, 096 provides answering machine bypassing, three Bypass Groups. AC fail
report to dialer, AC fail report delay.

5
1.2 Features
Accepts normally closed or normally open alarm devices, Tamper indication per zone
All features are programmable via system keypad or remote modem
Advanced static and lighting protection; unique Lighting Pro circuit for total protection
Auto arming set by end user and/or installer
Central station communicator and built-in TBR-21 or AUSTEL approved telephone dialer.
Communicator is compatible with most major formats: Contact ID, Ademco fast and slow,
Radionics, Scantronic, Sescoa, etc
Chime programmable for each zone
Digital zone-status display
Double-Pole zone. Tampering indication for each zone
Dialing Mode: Pulse or DTMF. Dialing to pagers in Hong-Kong and Singapore
Electronic fuses: Aux. Power, battery and siren/bell outputs (2)
Group bypass for three groups
Keypad sounder during local alarm
Local clock with ‘set time warning’
Modulated 2-tone siren from 24H and panic zone(s), 3-tone alarm from burglary zone(s)
Programmable 3 output drivers for remote signaling and reset of smoke detectors
Programmable 5 or 8 EOL resistor zones, or non-EOL zones
Pulse-operated battery charging circuit
Low battery indication
Signals to central station monitoring (via wire or wireless)
Remote control via DTMF phone (available with AV-2008D only)
Voice module option (SVM-40)
Up and Download via RS-232, or telephone line using a PC modem
Up to 250-alarm log (PRO version), with time and date stamped
Up to eight EOL supervised double-zones
Up to eight user codes, each code of up to six digits
1.3 Programmable Features
24-hour zones, fire zone
End of Line (EOL) zones (EOL is selectable)
Automatic bypass of open (troubled) ‘instant’ zones upon arming
Delayed, Follower (conditioned), Not In Use, Day, Tamper or Instant zones
Individual entry delays for two zone groups
Selectable response time for individual zones
Selective and Zone Group Bypass (Group Shunt)
1.4 Alarm Outputs
Three programmable open collector output drivers for remote alarm signaling
Auxiliary output for electric door strike operation
Communicator to central station and alarm sound dialer
Keypad sounder alarm programmable per zone

6
Two-timed siren outputs, each protected by separate fuses. Programmable ‘Bell Mode’
Variable siren tones for different types of zones
Signal test to central station, signaling time is programmable
Remote Signals:
24H-zone Alarm
On/Off (Arming/Disarming) indication
Programmable transmitting time of signal test to Central Station
Panic per zone
Programmable outputs for each zone or event (SLO and A1 output)

7
1.5 Technical Specifications Series 2000
Operating Temperature -10C to 60C
Relative Humidity 80% maximum
Input AC Power 16V AC step-down Transformer
Rated current: 1.2 Ampere
Dynamic Inner Memory EEprom
Auxiliary Power Output 13.6 Volts +/- 5%, Regulated
Short & Overload circuit protection
Siren Outputs (x2) Siren or Bell Selectable
Bell Mode: 13.6V DC-0.65A
Fuse protected
Siren: 8 Ohms, 20W
Dialer: Programmable 3 telephone numbers & 1
Follow-Me telephone number (4 tel. numbers).
Three tel. Interfaces are available: 600Ω, E, AS
Voice module input. Multi-format central-station
communicator. E version is TBR-21 approved, AS
version is AUSTEL approved
Pulse Dialing programmable
parameters
DTMF: Touch Tone dialing
Max. Telephone number length:
16 digits and 4 pauses.
Remote Indications on Wire Terminal Open Collector type output
300 mA Max. @ 12V DC
EOL Zone Loop Resistor (Burglary)
EOL Zone Loop Resistor (Tamper)
2,200 Ohms, 0.25W, +/- 5%
4,700 Ohms, 0.25W, +/- 5%
Zone Loop Voltage 5 to 6.5 V DC
Zone Loop Current 3 mA with End-Of-Line Resistor
RFI and EMI protection Zone line shorting, cutting, high
voltage lightning protection, RF Metal
Screen, Electro Static Discharge
Traps, RF Filters. Telephone line
Lighting protection circuit
Auxiliary Power (Max.) AV-2005/8: 13.6 VDC 0.9A
Combined Aux. Power and Keypad
outputs
Battery Charging Current (Max.) 550 mA, current limitation
Battery Test: Indication at keypad or remote
indication via communicator.
Battery monitors cut-off circuit at Golden version
Performed at 0.5A load for 1 second.
Low Battery indication below 10.5V
Tested upon Arming and every 60
minutes during Armed and Disarmed
Standby Power Consumption at Disarmed mode,
and Keypad display is Off
90 mA, +/- 10 %

8
Maximum Remote Station (Keypads) 3 Keypads AV-701TS, AV-701TI
5 Keypads AV-702
5 Keypads AV-707
Remote Station Current Consumption AV-701TS: 27mA. AV-701TI: 36mA
AV-702: 40mA. AV-706/7: 60mA
Housing Dimensions (H) 30, (D) 9, (W) 23 cm
Housing Anodized, lockable metal box
Epoxy anti-static powder painted
Gross Shipping Weight 2.2 kg. 6 PC's per master box
Fuses: Electronic Resetable Fuses Auxiliary Power: 1.25A
Sirens: 2 X 1.25A (fuse for each siren)
Backup Battery Fuse: 2.5A
Av-Gad Systems Ltd. reserves the right to modify and upgrade products without prior notice.
Starting version 2.09 New Fuse Included - Electronic Fuse Overview
The Electronic Fuse (resetable) device is installed as a series element in a circuit. In response to an over
current, it protects the circuit by going from a low-resistance to a high-resistance state that reduces the
current to a level that’s safe for the circuit elements. The change in resistance is the result of a rapid
increase in the temperature of the device. Like traditional fuses, Electronic Fuse devices interrupt the flow
of dangerous high current. But unlike traditional fuses, they automatically reset after the fault is cleared and
power to the circuit is removed. Because they are solid-state, Electronic Fuses are also able to better
withstand mechanical shock and vibration. This fuse provides reliable protection in a wide variety of
applications. In case of over current, carefully touch the fuse body (yellow round disc), hot body means the
Electronic Fuse is in protection mode, disconnect the load and wait 2-3 minutes until the fuse body gets
cooler.
Series 2000 compared to series 860
The new Series 2000 control panels is a result of long research and exploration we at Av-Gad did among
our customers, installers and end-users requirements. In late 1998, we started the R&D and design of the
Series 2000 new systems that will keep customers smile and our QC guys happy.
Our main task was to come with 100% protected system that will ensure high reliability, more features and
flexibility.
The result is an improved system, supporting the Series 860 way of programming and wiring, but offers
great advantages of improved assembly technology and features.
The Series 2000 contains new hardware with improved EMI, RFI and Lighting protection with a complete
new telephone interface to meet all the telephone standards in the world. New zone interface with improved
Alarm and Tamper reading that use the double-zone feature, new and more efficient battery test circuit,
new siren driver and more…..
Important: Test the alarm system weekly and/or before leaving your premises.
Verify that main AC supply is connected.

9
1.6 Ordering Information
Item Code Description
AV-865/8M 5 + 1 (8 + 1 for 868). Discontinued types
AV-2005/8
AV-2008D
5 + 1 zone Alarm Control Panel and Communicator/Dialer, built-in up &
download modem, options for SVM-40 and RS-232, electronic fuses. AV-
2008D provides remote control via any phone. Supports AV-701, AV-702
AV-2005/8 PRO 5+1 (8 + 1) zone Alarm Control Panel and Communicator or Dialer, built-in
up & download modem. Provides connection of voice module as SVM-40.
RS-232 socket included. Supports LCD keypad types AV-707, AV-706.
PRO types are compatible only with LCD keypad
AV-2005/8AS
AV-2008 Golden
5/8 + 1 zone Alarm Control Panel and Communicator or Dialer, built-in
up/down load modem. Provides connection of voice module as SVM-40. RS-
232 socket included. Battery monitors cut-off at AV-2008 Golden version.
AV-2005/8AS is Australian version, with AUSTEL approved telephone
interface. Supports AV-701, AV-702. PRO types are compatible with LCD
keypads AV-707, 706
TMP Tamper switch with wires for main alarm metal box. Not supplied, requires
separate order
AV-701TS Cost-saving 4-wire Keypad. 7-segment Digital Display, 4 LEDs, 12 silicon
rubber keys, and local sounder, semi-backlight. Connected to panel via 4
terminal wires
AV-701TI Identical to AV-701TS, with additional timed backlight illumination
AV-702 and
AV-702TP
New shape housing. Improved circuitry provides longer wiring and better
communication. 4-wire Keypad. 7-segment Digital Display, 4 LEDs, 12
silicon rubber keys with protection door, local sounder. Similar to AV-701.
AV-702TP with Tamper switch
AV-707/TP
AV-707B
AV-706
4-wire Keypad. LCD Display, 4 LEDs, 12 silicon rubber keys. Built-in
microprocessor. Compatible with PRO panels.
AV-707TP, AV-706TP with Tamper switch, AV-707B, BG, BS are supplied
with 3 functional buttons
5003TER Fuse-protected 220V step-down to 16V-1.2A AC transformer, wire terminal,
line filter, fits all AV-2005 and AV-2008 panels
5003 Low cost 16V-1.2A transformer
RELAYMO Relay module for driving self-powered siren.
SVM-40/60/90 Speech module, record & play, message stored without power, 40, 60 or 90
second message may be split into 2 channels. Message is recordable without
additional programmer.
AV-21 and
AV-21B
Extra 12V-1.5A, power supply and charger, supplying the power for large
installations. AV-21 supplied as PCB. AV-21B supplied as PCB housed in
metal box.

10
SECTION II: INSTALLATION
System planning
When the panel reaches you it will be factory programmed. This is done for testing purposes and for
average installation, if required without first entering to programming. This present program is
referred to as ‘Factory Defaults.’ It is advised that the engineer should be familiar with all the
features and options before attempting to program. Keypad should be specified and ordered
separately (several types available). Default arming code (user 1) is 1,2,3,4. Default programming
code is 1,9,9,4. For best results please read the manual before installation and programming.
Tips to first time installer
If you are a first time installer, don’t hook up any remote sensors yet. The most common confusion
comes about when the alarm will refuse to arm, because a zone is “troubled”. Complete the power
supply, siren, keypad and strobe wiring, and for the moment connect ALL the zone terminals to –V
with loops of wire. This will simulate a system with all zones looped out through closed switches and
no EOL resistors. The alarm is supplied already programmed with an “average” list of settings
(default) and can be used straight away, a few of the program locations may have to be changed to
suit the actual sensors and output devices used.
Read this manual carefully, it looks complicated, but all the information is there
If you are using a PRO panel carefully read the manual supplied with your LCD keypad. LCD and LED
keypads cannot operate in the same system. For AV-2008D (remote DTMF) refer this type appendix
To start with: Hook up the keypad, connect all zones to –V, power-up by applying AC only
In case the keypad displays ‘garbage’ verify the minus (-V) wire connection
Arm and disarm the system, when the Status LED light (not blinking), enter your master code; 1234
Try the hold-down functions. Hold each key for approximately 2 seconds; follow the confirmation letters
in keypad’s display
Set the system time by holding-down key ‘1’ then ‘0’, enter the time in 24 format, this will stop the blinking ‘h’
The default programming is set for siren; the siren is plain speaker horn, if your alarm device requires 12V
to alarm, you have to change the programming to Bell mode
Connect the strobe light to the SLO output (requires programming). The SLO supplies –V during alarm
Make sure you are using the Earth terminal for Grounding; it’s not a minus terminal
Typing six erroneous codes will lock the keypad keys for 30 seconds, don’t change code for starting
1. MOUNTING
1.1 Control Panel Mounting
Refer to detailed wiring diagram on page 61. Note: ‘h’ is displayed after power-up and upon Arming
to remind user to set the system time; ‘h’ will be removed after time setting, by using keys 0 and 1,
(refer to page 22, 26). Install the panel in a ventilated place, far away from RF transmitters or other
electric noise generators.
Easy as 1,2,3

11
Select a mounting location accessible to the following:
1. A continuously powered (non-switched) AC power source, compatible with any step-down
transformer. Make sure the mains (110 or 220V) are fused.
2. Cold water pipe Ground, ideally no farther than 3 meters (10 feet) from the panel. Use 16 AWG
(0.5 mm2) wires.
3. Telephone Line socket.
Always install the control panel box in a difficult-to-access location.
It is recommended to locate one of the Keypads near the Entrance/Exit door.
Install a tamper-switch to detect opening or removal of the control panel box.
Ideally, the tamper-switch is connected to a 24H zone type (24H zone is active at all times).
1.2 Zone Wiring Mode
Series 2000 allows several ways of zone wiring: Non EOL (End-of-Line) resistor loop, EOL resistor
loop, EOL for double zone loop. The EOL loop protects the zone lines against tampering. EOL mode
is safer and prevents EMI and RFI interference.
Via programming, select either EOL resistor protection, or non-EOL mode. The EOL is defined at
address 029; the default program is set at non-EOL for all zones. To set EOL mode select at address
029 the required non-EOL zone. Note that address 029 selects the non-EOL zone. Enter ‘0’ in
address 029 to enable all zones as EOL.
If E.O.L. mode selected (recommended), install the EOL resistor (2.2K/0.25 or 0.5W) inside the
detection device (e.g. PIR, Magnetic Switch). Using EOL mode is highly recommended. In EOL
mode don’t connect two or more sensors on same zone.
Starting version 2.12 ‘Green Reset Zone’ (refer to Glossary Section) programmed by default to all
zones.
Maximum zone wiring length is 200 meters when using 0.5-mm2 (gauge 22 wire) wires.
Note: ‘Zone’ and ‘Sector’ are interchangeable terms in this manual.
Do not run wire zones alongside telephone wires, high voltage wires, or transmitting antennae
It is recommended to always use EOL resistor mode, to prevent EMI and RFI interference
Double-Pole Zone wiring:
The Double-Pole Zone feature saves wiring and doubles the zone quantity by using two wires instead
of four, for both Tamper and Alarm indications. All zones common is the –V, for sensors (PIR,
Beams, etc) use a three or four wire cable; two wires for 12V power and one or two wires for zone.
For a Tamper condition: Fit the zone with EOL resistors, permit the ‘Enable Zone Tamper’ feature by
programming the address number 030.
Upon Tamper alarm, a ‘t’ will be displayed at keypad, followed by the zone number. At Disarmed
mode, holding-down key ‘9’ (Reset) disables the Tamper alarm at the alarmed zone.
Starting from version 2.08 (and up), any EOL zone will report Tamper alarm in case of zone shorting
(if it has been EOL programmed). To enable Tamper zone as 24H zone refer to address 051/1.
Upon Tamper alarm, a ‘t’ will be displayed, followed by the zone number. To disable Tamper alarm,
hold down key ‘9’.

12
Use sensors with two separate switches or relay contacts; one for Alarm and one for Tamper. Each
contact should be connected to a different E.O.L. resistor. The Eye-Spy II sensors include the EOL
resistors on board, provide fast and convenient wiring, refer to figure 1A.
Alarm contacts connected in series with a 2.2K resistor; tamper contacts with a 4.7K resistor. Both
resistors are supplied with each system.
For Double-Pole wiring, connect the two resistors (use the ALARM ‘C’ and ‘NC’ contacts) to Alarm
and Tamper as shown in the following drawing:
PIR WITH TAMPER SWITCH
TAMPER ALARM + 12V -
4.7K 2.2K
1 2 3 4
+12V -V
CONTROL PANEL
-V
Zone & Aux. Power Connection
Common -V
Tamper Resistor
Alarm Resistor
NC C POWER
RED
RED
RED
Silver
12V
Figure 1A: EYS II connected to Series 2000 Figure 1: Double-Pole wiring drawing
TamperAlarm Power
Zone Input Zone Common
1.5K Ohm 1.5K Ohm
N.C. C N.C. C -V +V
+12V
PIR Sensors wires Terminal
Figure 1A: European Double-Pole wiring drawing
Some countries are used to different double-pole wiring as shown in figure 1A. For this wiring please
follow the drawing below. This wiring way requires 1.5K resistors (1.5K resistors not supplied).
Control Panel
Z1 -V
Eye-Spy II

13
1.3 Keypad Wiring
Up to three AV-701TS/TI, five AV-702, or five AV-707/706 Keypads can be connected to
AV-2005/8 Control Panels. AV-707, AV-706 operates only with ‘PRO’ suffix panels.
LCD keypad (AV-707, AV-706) cannot be connected in same system with AV-701 or AV-702.
When using few keypads connect them in parallel (figure 2A). Don’t connect the keypad under
power. Each keypad contains four wires:
Red (+) Power, connect to + Aux. Power Orange System Data, connect to OR
Black (-) Power, connect to - Aux. Power Yellow System Strobe, connect to YE
For proper connection, refer to wiring diagrams, figures 2 and 9 (9 is at the end of the manual).
IMPORTANT! Never run Keypad wires alongside telephone wires, high voltage wires, or
transmitting antennae. Separate keypad wires, not run in same cable with other devices
(telephone, sensors etc.). Do not use the keypad wires for supplying power to sensors or other
devices. Keypads have no polarity protection; verify the 12V power polarity carefully during
wiring.
Wire length for each AV-701 Keypad should not exceed 100 meters, if AV-702 is used, maximum
recommended wiring length is 200 meters (when using 0.5 mm2 wires).
If installation requires keypad wire length for more than 100 meters, or more than five keypads:
1. Add a 470 ohm resistor between +12V and YE terminal in the control panel
2. Use two wires for the minus (–V) that supplies the keypad power
Maximum wiring length for the AV-707 Keypad is 200 meters (when using 0.5 mm2 wires)
Keypad voltage (measured on keypad’s wire terminal) should be 11.5 DC Volts minimum
Note: When a non-blinking ‘8’ is displayed and keys are not responding, it means that the
keypad is not communicating with the panel. Check wiring. Polarity error blows the panel
fuse.
C10
C12
C30
C31
C34
C37
C50
C80
C81
C90
C91
C94
C95
C107
D2
D3
D4
D5
D10
D21
D22
D23 D24
D61
D62
D64
D65
K3
K4
LD1
Q10
R1 R2 R3 R4 R5 R6 R7 R8R9 R10 R11 R12 R13 R14 R15R16
RN1
R20
R21
R22
R23
R24
R26
R40
R45
R46
R47
R48
R60
R61 R62
R63
R64
R65
R66
R67
R68
R69
R70
R93
R94
R95
R97 R99R100R102
R152
R160
R161
R162
R164
R165
R166
R176
R183
T1
U1 U2
U3
U4
U7
U12U13 U14
U15
VA1
VA2
VA3
VA4
VA6
+12V -V 1 2 3 4 56 7 8 YE OR A1 ON A2 SLO
PHONES
TEL. LINE
EOL Resistors are 2,220K Ohms
Z O N E 1 to 8
OR
YE
+V
-V
To Aux. power
E.O.L. Resistor
for tamper sw'
Tamper sw'
Short to -V
-V
Back side of AV-701TIP keypad
Figure 2: Wiring of keypad AV-701TIP (with Tamper)

14
*
7
4
1
0
8
5
2
#
9
6
3
Siren
Shunt
Display Status
Delay
Delete Chime
Test Program Reset
Shunt
Teleph one
ARMED STATUS SHUNT FIRE
ZONE
DISPLAY
EASYLOADER AV-70 1
AV-GAD AV-GAD EASYLOADER AV-701
FIRESHUNTSTATUSARMED
Test
Delete
Delay
Siren 1
4
7
*
DISPLAY
ZONE
Teleph one
Shunt
ResetProgram
Chime
StatusDisplay
Shunt 3
6
9
#
2
5
8
0 *
7
4
1
Siren
Delay
Delete
Test
ARMED STATUS SHUNT FIRE
EASYLOADER AV-70 1
AV-GAD
DISPLAY
ZONE
Teleph one
Shunt
ResetProgram
Chime
StatusDisplay
Shunt 3
6
9
#
2
5
8
0
AV-GAD EASYLOADER AV-701
FIRESHUNTSTATUSARMED
Test
Delete
Delay
Siren 1
4
7
* 0
8
5
2
#
9
6
3
Shunt
Display Status
Chime
Program Reset
Shunt
Teleph one
ZONE
DISPLAY
Panel Panel
Wrong Wiring Correct Wiring
Figure 2A: Best Keypad Wiring
For trouble free system follow the recommended wiring of few keypads, as show in figure 2A, wire
each keypad to the panel directly, prevent wiring running from one keypad to next.
Keypad Tamper Switch
The AV-701TIP, AV-702TP, AV-706/707TP keypads (keypad with tamper switch) contains a
Tamper switch that is activated upon removing keypad’s front part. Connect the Tamper switch to
Tamper, Day or 24H zone. For connection, refer to keypad’s wiring diagram, figure 2.

15
2. ALARM OUTPUTS
2.1 Sirens
The control panel contains two siren/bell outputs, individually protected by a fuse.
It’s recommended to use the same type of siren or bell for both internal and external sounders.
Siren mode is default-set at factory. In Siren mode, install speaker-type sirens, which DO NOT
contain sound driver or electronic modules. In Bell mode install a 12V DC sounder.
Note: “3 siren beeps on disarm” (073-6) is not working in “Bell” mode (072-1).
Consider using one internal and one external siren/bell. As Siren, use speaker siren type with a
minimum power of 15W, and 8 Ohms impedance.
Enclose the outdoor siren in a metal housing, with Tamper switch for protection.
The alarm from the Siren differs according to the type of zone: 24H, Fire, Burglary (not in Bell
Mode).
‘Bell Mode‘ converts Siren outputs into 13.6V DC outputs (no sound is issued). Bell mode is
applicable for driving self-powered sirens or bells, or combined sirens and strobes.
In Bell mode, connect only Bell or Siren with a 12V sound driver or electronic modules.
Piezo Sirens operating in the 12-20V DC range, are most recommended as Bell.
Self-contained Bell mode is programmable (address 073). Self-contained Bell mode provides
connection of Bells or Sirens that require 12V at ideal and 0V during alarm.
Starting version 2.17 siren voltage selector added, located in the upper-left side on the PCB. By
default set to drive 13.6V, fits siren and bell rated at 12V DC.
Warning!
Output power for each Bell should not exceed 0.65A (total Bell output is 1.3A).
Contact manufacturer's consultant before connecting higher power loads.
To connect self-contained sirens, Bells, and inner-oscillating sirens, refer to address 072, 073,
subject ‘Bell mode’.
2.2 Siren Connections
EasyLoader control panels enable driving of two separate speaker sirens or Bells
Speaker siren issues a multiple-tone alarm
The outdoor siren is enclosed in a metal box, with a Tamper Switch protection
Protect siren or bell box with a tamper-switch, connected to a 24H zone

16
2.3 Relay Module
The Relay Module enables connection of EasyLoader panels to most high current Bell types: Self-
contained internal battery Bells or Sirens (the term ‘Bell’ will apply to both Bells and Sirens).
The Relay Module is triggered via the siren output of the control panel. The power which drives the
Bell may be supplied either from the Aux. Power of the control panel or from an external power
supply in case the Bell requires higher current than the 0.6A already supplied by the control panel.
The Relay Module fits directly on the top the board, with the same screws that hold the main board.
Wiring information included with each Relay Module.
2.4 Remote Indication
Remote indications float while not alarmed and sink to –V during alarm, unless you program
differently.
Terminal Indication Application
ON (-V) on closing (Arming). Optional: Drives SVM-40 voice module
A1 Programmable. (-V) during alarm from the programmed zone
SLO Programmable. (-V) during alarm from the programmed zone
SLO is reset only upon disarming. The SLO is a non-timed output
Use the SLO output to drive a low current Strobe Light (Xenon) that
consumes up to 300 mA
Warning: The remote indications are capable of driving maximum 300 mA. Overloading or
applying +12V to the remote indications is dangerous and not assured. Take care!
Beginning with version 2.08, a new feature enables programming the listed outputs to supply float
output (0V) during alarm and -V at ideal. Refer to address 073-8.
In case other features are selected for the same output, this feature is not applicable.
When a relay is connected to the remote indication, a diode must be connected to the relay coil in
reserve polarity to the supplied voltage, or purchase AV-01/02 relay module. For LED driving,
connect a 2.2K resistor in series.
Hardware Tests for Outputs (from version 2.17)
This feature enables testing of devices connected to the remote indications.
In programming mode, using 200 + commands (30, 31,….):
ON output; 30 – ON, 31 - OFF
A1 output; 32 – ON, 33 - OFF
SLO output; 34 – ON, 35 - OFF

17
3. WIRING AND POWERING UP
3.1 Grounding – Lightning Protection
The control panel must be earth grounded for lighting protection to work effectively, and in order to
prevent RFI and EMI interfaces. Attach the ground connection to a verified cold-water pipe using a
minimum 16 AWG (or larger) wire, or according to the country grounding standard. Run the ground
wire via the shortest possible route.
System grounding is compulsory. For trouble free system, use a good ground.
Connect the Grounding wire to main board and to the metal box.
Note: Connect the Ground wire to the terminal marked . This is not a Minus (-V).
Beware of static discharge; before handling the main board touch a grounded metal.
Before grounding the system, verify that the ground is properly connected and does not transfer high
voltages. If ground is not available, run a ground wire and connect to a cold water pipe as close as
possible to earth.
3.2 Back Up Battery
Verify that Battery is in the correct polarity! Prevent long AC failures!
Red wire is the positive pole (+). Black wire is the negative pole (-).
Verify that your step-down transformer supplies 16V AC, higher voltage will cause over-heating.
The battery provides power back up in case of AC power failure.
Connect back-up battery to ensure proper operation of the system.
Recommended battery: 6.0 to 7.2 Amperes per Hour (AH), 12V SLA (Sealed Lead Acid) type.
A 7.2 AH battery provides back up power to control panel and a single keypad for approximately
10 hours.
Panel accommodates a battery of up to 12V - 7.2 AH (max.).
A 2.5A electronic fuse protects the battery.
Prevent full battery discharge; in case of long main AC fail disconnect the battery. Instruct
user not to disconnect AC when living premises for long journeys or other occasions.

18
3.3 Before Powering Up
Place the control panel in a dry and well-ventilated location, as far as possible from any heat
sources.
High power RF transmitters should be placed at least 2 meters away from the control panel.
Check for proper grounding. Uncharged your body by touching the Ground terminal.
Make sure polarity of detectors, keypads and other devices are correct.
Connect a momentary voltage to the siren; making sure a ‘beep’ is heard. If no beep, check for
short circuit or improperly connected wires.
Connect AC power to initial Power Up (transformer only). Connect battery only after keypad and
sensors seem to be operating properly. (Do not Power-up with battery alone.) Verify power
polarity of keypads.
Do not connect any devices to the battery terminals.
Series 860: Use only Fast Blow type fuse, size 20 x 5 mm, current 1.25A (supplied).
3.4 Connecting Smoke Detectors
The EasyLoader Series accommodate Ionization or Optical type 12V Smoke Detectors. Up to five
smoke detectors may be connected to each zone. Note: Most smokes output is Open Collector type;
program the Smoke zone as Fire and Normally Open zone type.
Panels are compatible with 12V smoke detectors with open collector or relay (-) output on alarm.
Smoke detector is reset by programming the SLO output to drive -V while holding-down key 9 (a
momentary switch or relay that disconnects power to smoke detector after a smoke alarm). Refer to
smoke wiring diagram.
When Fire Alarm occurs; hold-down key ‘9’ for reset, then enter valid code to disable alarm.
For connecting Smoke detector and EOL resistor, use a N.C. (normally close) smoke.
Reset Relay (or switch)
Relay or Switch mode, should be Normaly Close.
For reset cut power for Smoke during 3 Sec's
Connect EOL Resistor at last smoke
Av-Gad Systems
SLO
AV-2000 Panel
- +
+12V, Aux. Power
ZONE
-V
-V
AV-01 Relay Muodle
Aux. Power
1 2
4 3
+Vin +Vout
-V
-R
Type NE_2000 (D Ver.)
1 2
4 3
+Vin +Vout
-V
-R
Type NE_2000 (D Ver.)
-V switched by the Rest relay
Drive -V at Reset
To zone
N.C. Mode
Figure 4: Smoke Detectors (NE-2000) Wiring

19
3.5 Telephone System (dialer) Dialing and Wiring
It’s recommended to connect the control panel to an independent telephone line, if a device is in
parallel with the alarm panel, this may grab the call first (like a message answer/fax) during remote
up and download. Don’t connect fax or answering machine in parallel on the same telephone line.
In case of alarm, the dialer will dial to the programmed numbers, siren sound or voice message (if
SVM-40 connected) will be transmitted to the telephone. For further details, refer to dialer &
communicator chapter 2.9. Voice module types SVM-40/60 are compatible with AV-2005/8
EasyLoader panels. The voice module will apply spoken message over the telephone upon alarm.
Default dialing mode is DTMF. If Pulse dial is selected, the default is European Make/Break rate of
40/60 milliseconds (in Pulse dialing). The Make/Break rate is programmable.
Dialing mode is programmable (refer to programming sheet addresses 088 and 089).
Connect the telephone line to ‘TEL-LINE’ terminal, if handsets connected to same line connect them
to ‘PHONES’, when system attempt to dial the ‘PHONES’ is disconnected. Do not connect to ISDN
or other digital telephone system. Most ISDN converters have an Analog line; the Analog line of the
ISDN can be connected to the TEL-LINE terminal. Option: To protect the telephone line add the
Tele-Spy. The Tele-Spy it is a 24H telephone line monitor separate module. Starting version 2.17, a
software Dial Tone telephone monitor is included, refer to address 094, 051 options 5,6.
Note: To perform telephone line test enable Dial Tone detection at address 083.
For AUSTEL installations: At address 074 enter 8, at address 087 enter 2 (maximum), don’t connect
any phones in parallel with TEL-LINE terminal. Dialing problems may occur when system telephone
line is connected to Telstra Duet system or similar.
Software Telephone Line Test, address 094: Time interval between telephone line tests - in hours.
Range between 00-24. When ‘00’ programmed no test performed. Failure to get a dial tone when
dialing will cause a "Phone Line Fault" event.
3.6 SVM – Voice module
The SVM-40 and SVM-60 (replaces the SVM-24) speech modules allow the recording and playback
of two messages, with optional playback through an external speaker (not included). SVM-40
message duration is 40 seconds; SVM-60 message duration is 60 seconds. The SVM contains an on
board microphone.
The SVM is a high technology device, electronically stores messages with or without power.
The SVM is as a digital message source in Series 2000 Alarm Control Panels, telephone dialers or in
other applications. The SVM supplied audio is capable to drive audio amplifier, message center,
automatic dialer or other device.
When connected to Series 2000 Alarm Control Panels, program the SVM option (at programming
table 072-7, 074-1). Follow the wiring procedures (included in SVM manual) simulate alarm, the
panel will dial first the Communicator telephone number (telephone number 2 and 3), then to other
programmed numbers. After dialing, the panel will trig the SVM to send the recorded message. If
address 071 (1) is programmed (default) Tel. 1 is erased within arming and disarming.

20
3.7 Remote Key and Wireless Arming & Disarming
EasyLoader Series enables Arming/Disarming by remote momentary or latch key-switch (as
programmed in address 071), which is connected to terminals ‘KE’ and ‘- Aux. Power.’
When using remote key-switch, wire length should not exceed 10 meters.
Momentary or Latch pulse (programmable) between ‘KEY’ and ‘-V’ terminals will Arm and
Disarm the control panel. (Prior to arming, the ‘instant’ and ‘24H’ zones should be closed.)
System reverts to previous status with next momentary pulse (refer to Wiring Diagram.)
For Arming/Disarming via Wireless Radio Remote, connect receiver's relay to ‘KE’ and
‘- Aux. Power’ terminals. Verify the receiver relay mode, momentary, or latch, and set system
accordingly. Arming via key is indicated as event in history log.
For fully compatible trouble-free operation, AV-GAD's A11RX or A22RX wireless sets are
recommended. Programmable option: Arm with wireless with automatic Group bypass.
3.8 Auto Arming
Auto Arming provides automatic arming at pre-programmed time.
Setting the time for Automatic Arming:
- By Installer: Program (or display) hours and minutes at address 016.
- By User: Enter to user-programming mode. Hold down '8', 'A' is displayed; type hour and minutes
in 24 hours format. To display, hold down '8' and wait.
To disable Automatic Arming program 0000.
After Automatic Arming is programmed, the system time can be set only via User Programming
Mode: Enter User Programming Mode (hold-down 8 and 1234), hold down '1' ('t' is displayed) and
type hour and minutes. Hold down '1' and wait for the time to be displayed. Holding down keys '0'+'1'
to program the time is possible only if the Automatic Arming is disabled (otherwise an 'Error’
warning is displayed).
Automatic Arming will not operate if the time has not been set (blinking 'h'). Automatic Arming will
not operate if the control panel is already armed.
Automatic Arming will operate even if the control panel is currently in ALARM.
When the Automatic Arming programmed time arrives, the system starts at a 30-second countdown.
An 'A' is intermittently displayed and beeps are sounded at the keypad.
During the countdown period, the Automatic Arming can be aborted by entering a valid user code
(not code No. 7, if used to ‘open’ a door).
With PRO systems (in user programming mode):
To set systems clock when Auto Arming enabled: Press 20 and enter the time in 24H format, confirm
with #. Press 20 and # to display the system clock.
To set Auto Arming Time: Press 21 and enter the time in 24H format, confirm with #. Press 21 and #
to display the Auto Arming time.
This manual suits for next models
1
Table of contents
Other AV-GAD Cell Phone manuals