Azbil Inflex GD WY5110 User manual

AB-6529
Azbil Corporation’s controller Infilex series: Infilex is named for “Infinity” and “Flexible”.
1
Specifications/Instructions
InfilexGD
Multipurpose Data Gathering Panel
Model WY5110
General
Infilex GD (Infilex: named for “Infinity” and “Flexible”) Model
WY5110 is a multipurpose terminal data transfer device
designed to collect the data about various types of equipment
inside the building, to monitor the equipment status, and to
control the equipment operation.
Infilex GD consists of a basic unit and I/O modules, UT
module, integral type Operator Panel, and SAnet interface
module. The number and types of the modules can be
flexibly changed corresponding to the total number of the
management points.
Infilex GD can communicate with BMS (building
management system) center unit (Azbil Corporation’s
savic-net
FX) through the transmission trunk line called
NC-bus. By sending the operation status to the center unit or
by controlling the operation based on the commands sent
from the center unit, the integrated control of the entire
building can be performed. Azbil Corporation’s field devices,
Intelligent Component Series devices, are also connectable
to Infilex GD via SAnet, allowing high-performance control.
Features
Compact design:
Small size body allows free installation in a desired place.
I/O module configurations:
Input and output types can be selected, and the number
of points to be mounted can be increased or decreased
corresponding to the application.
User interface module (Operator Panel):
Operator Panel (panel mount type/integral type)
connected to Infilex GD allows you, without changing the
settings from the BMS center unit, to change the Infilex
GD settings.
Autonomous distributed control:
Even if a trouble occurs in the BMS, the backup operation
is performed individually to distribute potential risks
caused by malfunction of the system.
Installation:
A quick-fit screwless (clamp) terminal block for the
communication line reduces wiring work load.
Additionally, either DIN rail mounting or screw mounting
can be selected.
Connection to Intelligent Component Series devices:
Intelligent Component Series devices offering advanced
control are connectable via SAnet.
CE Marking certified product:
Infilex GD Model WY5110W (NC-bus model (Line A))
conforms to all the applicable standards of CE Marking
(Class A).

AB-6529
2
Safety Instructions
Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual near by for
ready reference.
Usage Restrictions
This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If
this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact Azbil
Corporation’s sales representative. Azbil Corporation will not bear any responsibility for the results produced by the operators.
WARNING
DANGER: To prevent the risk of severe or fatal electrical shock, always disconnect power source and product
power supply before performing any wiring or maintenance (except lithium battery replacement).
Be sure to ground with 100 or lower ground resistance. Improper grounding may cause electrical shock or
equipment damages.
Do not detach the terminal cover at any time except when wiring. After wiring, be sure to attach the terminal cover.
Before attaching/detaching the terminal cover, make sure that the wires are not current-carrying to prevent
electrical shock.
Disconnect power before the product replacement to prevent electrical shock.
Wire strip length to be connected to the quick-fit screwless terminal block must be 8 mm. If the strip length is longer
than 8 mm, the conductor will be exposed, causing electrical shock or short circuit between adjacent terminals. If it
is shorter, the conductor will not contact the connector.
Do not disassemble the product. Disassembly may result in electrical shock or equipment damage.
CAUTION
Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.
Installation must be carried out according to the operating conditions (power, temperature, humidity, vibration,
shock, installation position, atmospheric condition, etc) specified in this manual to prevent equipment damages.
All wiring must comply with local codes of indoor wiring and electric installation rules.
Use crimp terminal lugs with insulation for electric wires connected to the screw terminals.
Connect cables to the power source with terminals or the like for permanent connection.
Make sure all the wires are tightly connected to prevent heat generation or equipment damages.
If more than the rated power supply voltage is applied, product replacement is required for safety.
Install this product in a location out of reach of unauthorized people. (e.g. Inside of the control panel cabinet)
Lightening protection based on the regional characteristics and the building structure is needed to minimize
equipment damages.
Noise protection is necessary when the product is installed in a location close to many noise sources.
Do not block the vent holes of the product to prevent equipment damages. Remove protective sheet after
installation and wiring.
After mounting the product on DIN rail, make sure that the holding parts of all the modules are properly fixed with
their whole parts lifted. The product may drop from the DIN rail and be damaged due to improper mounting.
Dispose of the lithium battery in accordance with your local regulations.
Dispose of this product in accordance with your local regulations. Do not reuse all or a part of this product.
Trademark information:
ACTIVAL, Infilex, PARAMATRIX and savic-net are trademarks of Azbil Corporation in Japan or in other countries.
BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
KPEV is a registered trademark of Furukawa Electric Co., Ltd.

AB-6529
3
System Configurations
Infilex GD integrated into BMS: savic-net
FX
Figure 1. System configuration example: Infilex GD integrated into savic-net FX BMS
Notes:
MIS may be used instead of SMS and DSS for your system. Note that MIS cannot be mixed with SMS or DSS in the same system.
For details of I/O modules, UT module, integral type Operator Panel and SAnet interface module to be assembled with Infilex GD basic
unit, refer to the Specifications/Instructions of Model RY50XX (AB-6527).
SAnet is connectable to Infilex GC/Infilex GD for NC-bus and IP, not connectable to those for LC-bus.
Up to two SAnet I/F module can be connected to one Infilex GC/Infilex GD.
For detailed specifications of SAnet, refer to Installation Manual of Intelligent Component Series for SAnet Communication (AB-6713).
1 ACTIVAL PLUS requires 2 SAnet addresses.
For constraint and requirement of SC-bus, refer to the Specifications/Instructions of Infilex ZM/Infilex SC/Infilex FC/Infilex VC.
Model Numbers
Model number Description
WY5110 Basic model number
W
100 V AC to 240 V AC power
0000
NC-bus model (Line A)
* CE Marking (Class A) certified
0010
Redundant NC-bus model (Lines A and B)
Notes:
For I/O modules, UT module, integral type Operator Panel,
and SAnet interface module to be combined with Infilex GD
Model WY5110, separate order is required.
Regarding I/O modules, UT module, integral type Operator
Panel, and SAnet interface module to be combined with Model
WY5111, refer to AB-6527 Specifications/Instructions of
Model RY50XX.
Parts for Installation
Part number Description
83165861-001 Screw tab
83104567-001 DIN rail mounting bracket
Note:
For mounting Infilex GD, either the screw tab (for screw
mounting) or the DIN rail mounting bracket (for DIN rail
mounting) is required. Be sure to separately order depending
on your mounting type.
Infilex AC / Infilex GC / Infilex GD basic unit is combined with I/O
modules, UT module, and integral type Operator Panel.
Infilex GC / Infilex GD basic unit is also combined with SAnet I/F
(interface) module, as shown in Fig. 1.
InfilexGD
InfilexAC
InfilexGC
PMX-III*3
InfilexZM
Infilex
FC Infilex
VC
DSS: Data Storage
MIS: Management Integration Server
PMX-III: PARAMATRIX-III
SAnet I/F: SAnet interface module
SCS: System Core Server
SMS: System Management Server
BACnet/IP
(with Web browser)
NC-bus (Max. 25 units and 500 m, but extendable up to 1000 m with the repeater module.)
SC-bus
Neopanel
(Digital user terminal)
Temperature
sensor
InfilexSC
Neopanel
(Digital user terminal)
Client PCSMS DSS
MIS
SCS
Intelligent Component
Series
ACTIVALPLUS
Intelligent Component
Series
ACTIVAL
Intelligent Component
Series
Damper actuator
SAnet
I/F
SAnet (for Intelligent Component Series devices)

AB-6529
4
Specifications
Basic specifications
Item Specification
Rated voltage 100 V AC to 240 V AC, 50 Hz/60 Hz
Allowable voltage
range 85 V AC to 264 V AC, 50 Hz/60 Hz
Power shutdown
detection 80 V AC or less
Power consumption 40 VA
Power supply
Leakage current 1 mA or less
Ambient temperature 0 C to 50 C
Ambient humidity 10 %RH to 90 %RH (Non-condensing)
Altitude 2000 m or lower
Rated operating
conditions
Vibration Max. 3.2 m/s² (at 10 Hz to 150 Hz)
Ambient temperature -20 C to 60 C
Ambient humidity 5 %RH to 95 %RH (Non-condensing)
Vibration for storage Max. 3.2 m/s² (at 10 Hz to 150 Hz)
Environmental
conditions
Transport/storage
conditions
Vibration for transport Max. 9.8 m/s² (at 10 Hz to 150 Hz)
Green LED ON: Power ON
Power supply
(POWER) Green LED OFF: Poser OFF
Red LED ON: Major failure or system restart
Major failure (ERR1) Red LED OFF: Normal operation
Red LED ON: Minor failure or system restart
Operation
Minor failure (ERR2) Red LED OFF: Normal operation
LED indication
Communication NC-bus Transmit (TX), Receive (RX)
RAM, RTC Lithium battery backup
Power failure backup Data file Non-volatile memory backup
Transmission system Current transmission
Transmission speed 4800 bps
Transmission distance 500 m
Communications NC-bus
Remote units Max. 25 remote units connectable
Weight 400 g
Material (housing), color Modified PPE, light gray
Power supply, ground M3 screw terminals (7.62 mm pitch between terminals)
Terminals connection NC-bus communication Quick-fit screwless (clamp) terminal block
Wiring specifications
Basic unit
Item Wiring Wiring length Condition
Power supply JIS IV 2.0 mm² or JIS CVV 2.0 mm² or greater
Grounding JIS IV2.0 mm² or JIS CVV2.0 mm² or greater Ground resistance: 100 or lower
NC-bus JCS IPEV-S 0.9 mm² 500 m
Notes:
Pin terminals cannot be used.
JIS: Japanese Industrial Standards
JCS: Japanese Electric Wire and Cable Makers’ Association

AB-6529
5
I/O module
Item Wiring Wiring length
Temperature input JIS IV, JIS CVV, KPEV
1.25 mm2
100 m
Voltage/Current input JIS IV, JIS CVV, KPEV
1.25 mm2
100 m
Voltage/Current output JIS IV, JIS CVV, KPEV
0.9 mm2, 1.25mm2
100 m
Modutrol motor output JIS IV, JIS CVV, KPEV
1.25 mm2
100 m
Digital input JIS IV, JIS CVV, KPEV
0.5 mm2, 0.75 mm2, 0.9 mm2, 1.25 mm2
100 m
Relay output JIS IV, JIS CVV, KPEV
1.25 mm2
100 m
Remote control relay
output
JIS IV, JIS CVV, KPEV
1.25 mm2
100 m
Notes:
Since a quick-fit screwless terminal block is provided on I/O modules, the wires can be connected only by stripping the sheath.
Sheath stripped length: 8 mm (Pin terminal cannot be used.)
KPEV is a wiring standard provided by Furukawa Electric Co., Ltd.
Specifications of I/O modules, integral type Operator Panel, UT module, and SAnet I/F module
For the specifications of I/O modules, UT module, and SAnet interface module, refer to Specifications/Instructions of Model
RY50XX (AB-6527). For the specifications of integral type of Operator Panel, refer to Specifications/Instructions of Model
RY5001Q/QY5100W (AB-6546).
CE Marking Conformity
This product must be installed in a panel cabinet. Besides, the product in the panel cabinet must be out of reach of unauthorized
people who are not well-trained for electric facilities.
This product complies with the following Electromagnetic Compatibility (EMC) and the Low Voltage Directive (LVD).
EMC: EN61326-1 Class A, Table 2 (For use in an industrial electromagnetic environment)
LVD : EN61010-1 Overvoltage category II
Pollution degree 2
Input/Output and Terminal Arrangement
Figure 2. Input/output and terminal arrangement
100 V AC to 240 V AC
NC-bus Line A
1
2
3
4
TX IN
TX OUT
TX IN
TX Out
(+)
(-)
Shield
Shield
(+)
(-)
(+)
(-)
5
6
7
8
9
10
11
12
NC-bus Line

AB-6529
6
Dimensions
Figure 3. Dimensions (mm)
60 90
140

AB-6529
7
Parts Identification
Figure 4. Parts identification
Table 1. Indication and operation of operating status LED
LED indication LED operation
Data transmitting NC-bus TX LED: flashing
Data receiving NC-bus RX LED: flashing
Major failure / initializing ERR1: ON
Minor failure / initializing ERR2: ON
Connection of Data Setter (H-MMI) / PC-MMI
1) Connection of Data Setter Model QY5111B
No conversion cable is required. Directly insert the male connector of the Data Setter into the female connector provided on
the Infilex GD basic unit.
At this time, hold the male connector with the ◄mark facing left and insert it as the mark points to the ►mark on the Infilex
GD basic unit.
2) Connection of Data Setter Model QY7211B / PC-MMI
Convert the D-SUB connector to the mini DIN connector with the conversion cable (Part No. 83104995-001).
At this time, hold the male connector with the ◄mark facing left and insert it as the mark points to the ►mark on the
Infilex GD basic unit.
Figure 5. Connecting Data Setter/PC-MMI
DIN rail
mounting
hook
Do not press the S1 switch.
S1 switch*
Connector (female)
for Data Setter
Power switch
LED fo
r
Power ON/OFF
Battery holde
r
LED for
operating status
Insert the male connector as
the two arrows point to each
other.

AB-6529
8
Mounting Dimensions
DIN rail mounting
Fig. 6 shows the mounting dimensions of Infilex GD on the DIN rail.
Mount and fix Infilex GD on DIN rail so that it does not fall from the DIN rail. Check that the DIN rail holders of each module are
pushed up and fixed on the DIN rail.
Fasten the bilateral sides of Infilex GD with two DIN rail mounting brackets (Part No. 83104567-001, separate order is required).
Notes:
1 Pitch between upper/lower duct and DIN rail.
2 Hatched area shows the maintenance space.
3 ‘n’ indicates the number of I/O module, UT module, integral type Operator Panel, and/or SAnet I/F module assembled with Infilex GD basic
unit.
4 DIN rail position is shifted 5 mm downward from the center of Infilex GD.
The width of Infilex GD may vary depending on the number of an I/O module, UT module,
integral type Operator Panel, and/or SAnet I/F module to be assembled. Their dimensions
are the same.
Width of Infilex GD = One module (30 mm) n (quantity) + Infilex GD basic unit (60 mm)
Notes:
Panel mount type Operator Panel is not directly assembled with Infilex GD. To connect it to Infilex
GD, a UT module is required.
For details of panel mount type Operator Panel, please refer to Specifications/Instructions of
Operator Panel (AB-6546).
For details of I/O modules and user interface modules that can be assembled with Infilex GD, refer
to Specifications/Instructions of I/O modules and user interface modules (AB-6527).
I/O module (mm)
Figure 6. Mounting dimensions: DIN rail mounting (mm)
30
DIN rail mounting brackets for bilateral sides
Part No. 83104567-001
Duct
Duct
Infilex GD
(
45
)
35
140 (45)
(122.5)*1(132.5)*1
Duct
20
50 92
(60)
(60)
Duct
65 75
35
2
DIN rail holder
Infilex GD
basic unit
DIN rail
Infilex GD
60 + 30 n*3
Hook
I/O modules, UT
module, integral type
Operator Panel,
SAnet I/F module
5*4
106

AB-6529
9
Direct screw mounting
Fig. 7 shows the mounting dimensions of Infilex GD directly on a mounting surface, with screws.
To mount Infilex GD with screws, the screw tabs (Part No. 83165861-001, with separate order required) are required. Mount
and fix Infilex GD on the mounting surface with M4 8 screws. (1 screw tab and 2 screws for 1 basic unit/module are required.)
Lengthwise mounting
Incorrect mounting: Crosswise, face-up/face-down*2
Notes:
1 Hatched area shows the maintenance space.
2 ‘n’ indicates the number of I/O module, UT module, integral type Operator Panel, and/or SAnet I/F module assembled with Infilex GD basic
unit.
3 Do not mount Infilex GD in the crosswise direction (basic unit positioned above or below the assembled modules). Do not mount it with the
front surface facing upward or downward, either.
The width of Infilex GD may vary depending on the number of an I/O module, UT module,
integral type Operator Panel, and/or SAnet I/F module to be assembled. Their outside
dimensions are the same.
Width of Infilex GD = One module (30 mm) n (quantity) + Infilex GD basic unit (60 mm)
Notes:
Panel mount type Operator Panel is not directly assembled with Infilex GD. To connect it to
Infilex GD, a UT module is required.
For the dimensions of panel mount type Operator Panel, please refer to
Specifications/Instructions of Operator Panel (AB-6546).
For details of I/O modules and user interface modules that can be assembled with Infilex GD,
refer to Specifications/Instructions of I/O modules and user interface modules (AB-6527).
I/O module (mm)
Figure 7. Mounting dimensions: Direct screw mounting (mm)
30
DIN rail holder
Pull down the DIN rail holders.
Screw tab Part No. 83165861-001
Rear
side
Screw tab
50 20
30 45 30 30
35 140 35
154
7
To attach the screw tab,
insert the screw tab into
the slit provided on the
rear side of Infilex GD.
1
Infilex GD
basic unit
60 + 30 n*2
I/O modules, UT module,
integral type Operator Panel,
SAnet I/F module
Insert.
Vertical direction
Infilex GD
basic unit

AB-6529
10
Wires Connection
Connection to the power supply terminal block
Crimp the terminal lugs for the M3 screw terminal block to the
wire ends, and connect them to the terminal block.
Connection to I/O modules and NC-bus terminal block
Since quick-fit screwless terminal block is used for the I/O
modules and the NC-bus terminal block, the procedure for
wiring is specified as follows.
1) Strip the wire sheath 8 mm. (The gauge for the strip
length is located at the front lower part of Infilex GD basic
unit. If the stripped part is longer than 8 mm, the
conductor will be exposed, causing electrical shock or
short circuit between adjacent terminals. If it is shorter,
the conductor may not contact the connector.)
2) Make sure that no wire fiber is protruded from the
conductor (stripped wire).
3) Press the button on the terminal block deeply enough to
insert the wire using a slotted screwdriver.
(Maximum button-pressing force is 14 N.)
4) Release the button, and gently pull out the wire
horizontally to make sure that it is tightly fastened. (If you
pull out the wire diagonally, it may be disconnected.)
Make sure that no wire fiber is protruded from the
conductor (stripped conductor).
Positions for connected cables
Neatly place the wires, using cable ties or the like, connected
to Infilex GD so as not to hide LED, Data Setter connector, ►
mark, S1 switch, battery holder, or indication tag, as shown in
Fig. 8.
Make sure there is no slack in the wires from the cable ducts
to Infilex GD.
Figure 8. Connected cables in position
Tube marker
Since Infilex GD adopts a quick-fit screwless terminal block,
wires are connected without crimp terminals. Therefore, if
normal tube markers are used, they may come off when the
wires are disconnected. To prevent this, use the following
Flat Tube Marker. It is held on a wire by friction and thus
does not come off easily.
Manufacturer Phoenix Contact
Part name Flat Tube Marker
Part number 5880029
Model TMC-3
Applicable wire size 0.4 mm2to 2 mm2
Package unit: 200 m/roll
System indication label for the controller number
The indication tag has the system indication label on its back.
Turn it over and fill in the controller number on the label.
Figure 9. System indication label
Protective sheet
After connecting the wires, be sure to peel off the protective
sheet before turning on the power.
1) Adhesive is applied to the sheet approximately 20 mm
from the front edge. Peel off this area.
2) Tear off the sheet along the perforations.
Figure 10. Protective sheet
Turn over.
Indication tag
2) Tear off.
1) Peel off the adhesive area.
LED
S1 switch
Connector for
Data Setter
Battery holder
Indication tag
Power switch
LED

AB-6529
11
Maintenance (Lithium Battery Replacement)
Replace the lithium battery for backup (Part No. 83104934-001) every 5 years.
IMPORTANT:
Since the remaining battery capacity cannot be checked by measuring the terminal voltage, be sure to replace
the battery every 5 years.
Only authorized service personnel is allowed to replace the battery.
Do not touch the power supply unit when replaceing the battery.
Replace the lithium battery every 5 years if the product is always in use (in ON state).
Replace the lithium battery with the power ON.
If the product has never or hardly been operated (in OFF state) for a year, replace the lithium battery before the
product operation.
Battery replacement
Replace the lithium battery while Infilex GD is ON.
Figure 11. Battery replacement
1) Pull out the battery holder using a slotted screwdriver.
2) Disconnect the connector and detach the lithium battery from the battery holder.
3) Place a new lithium battery in the battery holder and connect the connector to it.
4) Insert the battery holder into the basic unit.
5) Fill in the date for next replacement (5 years after the replacement) on the indication tag using an oil-based pen.
1)
4)
5)
3)
2)
Infilex GD
basic unit
Lithium battery
for backup
Battery holder Battery Connector

AB-6529
Specifications are subject to change without notice.
Building Systems Company
http://www.azbil.com/
Rev. 8.0 Sep. 2015 AB-6529
(J: AI-6529 Rev. 4.1) Printed in Japan.
12
Precautions for Use
Do not mount the product under the conditions of high temperature and humidity.
Do not drop the product.
For the wire replacement, be sure to shut down the power. (Disconnect the wiring between the power supply and the
product power terminals.)
Before turning on the power, make sure that the wires are correctly connected.
Several tens of seconds are required for the product normal operation after the power is turned on. During this time, the red
LED “ERR1” (major failure) on the front lights up indicating major failure temporarily, but this does not indicate an error.
Do not connect wires to vacant terminals.
Leave at least 35 mm clearance between the top/bottom surfaces of the product and other devices.
Peel off the protective sheet on the top surface of the product before turning ON the power.
(See Figs. 10 and 12.)
Figure 12. Batter label and protective sheet
Protective sheet
Battery label
Table of contents
Other Azbil Control Panel manuals
Popular Control Panel manuals by other brands

DeDietrich
DeDietrich S2NA manual

GC5
GC5 iSMA-B-SP user manual

Blue Sea Systems
Blue Sea Systems 8081 installation manual

Crow
Crow Runner Series user guide

Alderon Industries
Alderon Industries Check It Panel Operation, maintenance & installation manual

Arrowhead Alarm Products
Arrowhead Alarm Products ESL-2 Installation & programming guide