manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. B meters
  6. •
  7. Measuring Instrument
  8. •
  9. B meters HYDROCAL-M4 Assembly instructions

B meters HYDROCAL-M4 Assembly instructions

1
Subject to change without prior notice
EN
The HYDROCAL-M4 is a compact thermal energy meter that measures the energy consumption of heating and
cooling systems. The meter allows to measure the thermal energy passing into a hydraulic circuit used for
heating and\or for cooling, it also lets the acquisition through external module, of the volume measured by up
to 2 device (water, heat, gas, electricity, HCA) equipped with pulse emitter. The meter can also be connected to a
consumption reading network based on the wired M-BUS (IR-MB-PULSE), Wireless M-BUS and LoraWan protocols.
The product must be stored in a dry place at temperatures between -20 °C and +70 °C (even during transport).
The duration of the storage should not exceed 1 year.
Combined heating or cooling meters are precision devices and must be protected from shock and vibration.
STORAGE CONDITIONS
1. Introduction
WARNING
• Before proceeding with the installation and configuration of the product, carefully read the instructions in
this manual. For further technical clarification, please contact Customer Service.
• Installation should be carried out exclusively by qualified personnel.
• The reference standard for the instrument is EN 1434 and Directive 2014/32/EU (Annex MI-004).
• Any tampering of the meter or removal of the seals will void the warranty provided.
• For proper energy accounting, always respect the mounting type prescribed (inlet pipe installation/ return
pipe installation).
• The configuration of installation version and unit of measurement can be done with the buttons or an
Android device with NFC connectivity.
• Respect the installation point (input or output) of the instrument.
GENERAL INFORMATION
PACKAGING CONTENT: HYDROCAL-M4, installation manual, antifraud kit.
HYDROCAL-M4 •Operating and Installation Instruction v1.3
13.09.2023
The first configuration chosen during installation (supply or return pipe) can’t be modified!
The top calculation/electronic unit must not be separated from the bottom brass case.
This meter contains dangerous batteries, handle it with caution and do not disperse in the environment.
The installation must be carried out by qualified personnel only. The manufacturer doesn’t assume any
responsibility for improper installation or damages caused by third parties.
2. Safety information
Warning: highlights the instructions to be followed scrupulously for the correct functioning of the meter.
Danger: highlights important precautions to follow in order to avoid dangerous situations.
Notes: highlights important information for a proper experience while using the device.
Read all instructions carefully before proceeding with the installation! Failure to comply with one or more of the procedures
contained in the manual can be dangerous and cause damage to property and people. It is recommended to comply with
all applicable laws on safety and accident prevention.
2Subject to change without prior notice
EN
Observe national regulations relating to the measurement of cooling.
Observe the technical requirements relating to the installation of electrical equipment.
The instrument complies with the requirements of Directive 2014/30/EU of the European Council on electromagnetic
compatibility, Directive 2014/35/EU on electrical safety and Directive RED 2014/53/EU.
If more than one instrument is installed in a unit, the installation conditions must be the same for all instruments to
ensure that consumption is as equal as possible.
The warranty and validity of the verification become void if the identification plate or the seals applied to the instrument
are removed or damaged.
Remove the device from the package only at the time of installation to protect it from damage and dirt.
The air transport of active radio devices is prohibited.
Carefully observe the instructions in the data sheet, instruction manual, application notes and lid. Failure to comply with
the operating conditions may result in situations of danger and forfeiture of all claims of liability for defects as well as
liability based on any guarantees expressly granted. For more information visit the website www.bmeters.com.
Dispose of replaced devices and defective components in accordance with current environmental regulations.
Store out of the reach of children.
Wear protective gloves and pay attention to the sharp protrusions in the threads, flanges and measuring tube.
The device shall be used in such a way as to minimize the potential for human contact during normal operation. To avoid
the possibility of exceeding radio frequency exposure limits, human proximity to receivers with integrated antenna should
not be less than 20 cm (8 inches) during normal operation.
Do not expose the meter to the sun and heat sources. Do not attempt to burn the device.
In case of danger of frost, empty the system and, if necessary, remove the meter.
To clean the device externally use a soft cloth and moistened with water. Do not wash with high-pressure jets or soak the
device in water. Avoid contact with oils and solvent. Do not use alcohol or detergents.
Do not damage the casing of the device. In the event of collisions of blunt objects on the front of the display, it can be
irreparably damaged and lose the IP65 degree of protection. Install in areas protected against impacts. If the protective
casing breaks, contact customer service.
The display stays inactive. To activate it, press the button on the device. The display remains active for 60 seconds.
The meter is not suitable for drinking water but is suitable for circulating water in central heating systems.
Do not twist, wrap, extend or shorten the cables of the temperature probes and the cable that connects the electronic unit
to the part of the lower-case body.
The thermal energy meter can be installed only in areas protected from frost.
The thermal energy meter must be protected against pressure shocks in the pipeline.
Slowly fill the pipe with water at the end of the installation.
After installing the meter perform a leak test of the system.
Assemble or disassemble the meter only after depressurization of the system.
The meter does not have lightning protection.
Thermal energy meters do not require special protection against electrical interference; however, electromagnetic
interference must be avoided.
3
Subject to change without prior notice
EN
If transmission network interfaces are used, especially when cables are routed outside the building, use increased
protection against electrical interference.
Rinse the pipes thoroughly before installing the meter.
For a proper installation the direction of the arrow on the lower brass body must match the direction of the flow.
Avoid collecting air bubbles in the meter during the installation process.
The thermal energy meter must not be subjected to mechanical stress when installed in the pipeline.
The meter must be installed in such a way as to be protected from all impurities and external contamination.
Manually and simultaneously screw the device fittings on both sides, and then tighten in opposite directions using a
suitable device.
Remove old seals and clean the sealing surfaces.
Slightly grease the sealing surfaces (use grease approved by MID Standards).
Mount only the supplied gaskets (gaskets should not get in the pipeline). Seals provided on site must be fit for purpose and
comply with local guidelines and directives. B METERS is not liable for any damage resulting from the use of third-party
gaskets (corrosion of sealing surfaces and threads).
Problem Cause Solution
Display o, pressing buttons does
not respond The battery may be damaged or discharged
Inform Customer Service
Damaged container, or leakage Possible external impact or fall to the ground
Lower case brass separated
by electronic unit Tampering by third party or strong external impacts
Open and visible electronic unit
No consumption is accounted Tampering by third party, strong external shocks or damage
to the flow detection sensor
Error 12 always present Damaged temperature probes
Error 18 or 19 always present Damaged temperature probes or out of system temperatures
limits
Does not transmit via radio Failure to pass 5 absolute liters or the batteries may be
damaged or discharged
TROUBLESHOOTING
BEFORE INSTALLATION
3. Installation
Before the thermal energy meter installation make sure that the two ends of the inlet and outlet pipe are
perfectly aligned, clean them with the utmost care. Moreover, make sure there is a suitable filter placed at
the inlet and that clean and undamaged gaskets are inserted on both sides. The thermal energy meters must
be installed as specified by the CEN-TR 13582 regulation. Upstream and downstream the meter install an
appropriate water flow interception and regulation devices suitable to allow inspection and maintenance of the
meter, control of the water flow and eventual sealing of the system.
4Subject to change without prior notice
EN
All versions of the thermal energy meter can be
installed both horizontally and vertically. For a better
performance it is preferable, however, the horizontal
installation with the turbine axis perpendicular to the
ground and the reading mechanism facing upwards.
Ideal position Additional allowed positions
* This position is not suggested for cooling meters and for instances where moisture can enter the
electronic casing due to condensation (e.g. during an interruption of the plant in the summer)
Attention should be paid to the direction of flow. Install the thermal energy meter so that the passage of water takes place
in the direction indicated by the arrow in relief on the brass body and respecting the prescribed position.
To ensure proper measurement, make sure that there is no air inside the pipe and that the flow is clean and free of debris
(potentially harmful to the meter turbine).
It is mandatory to comply with the prescribed type of assembly (return pipe\supply pipe).
Always refer to what is on the meter menu 3 level 06. The figure below refers to a standard version of the device
installation (mounting on return pipe) and positioned horizontally.
For a correct installation, always proceed in compliance with the directives prescribed by current regulations.
TEMPERATURE SENSOR INSTALLATION
The meter is equipped with two digital probes compliant with: MID 2014/32/EU directive and EN1434 standard.
In the standard version (e.g mounting on return pipe), the return probe is already incorporated inside the brass
case. The supply probe must be installed in a ball valve or in a socket mounted on the flow pipe and complies
with the requirements of the sensor itself.
Vice versa, the version for installation on the inlet pipe the probe inserted inside the brass case will be the flow,
the return probe will need to be installed in a valve or a socket on the return pipe.
Before installing the ‘free’ probe (the one not inserted in the meter case), it is necessary to intercept the flow (close the
ball valve or the appropriate shutters).
5
Subject to change without prior notice
EN
For a correct temperature measurement, the tip of the probe must be in the center of the pipe. In addition, the axis of the
probe must be perpendicular to the pipe axis (see figure).
The temperature sensor must be sealed when the installation is complete.
INSTALLATION IN A SOCKET BALL VALVE INSTALLATION
The HYDROCAL-M4 is equipped with dedicated sections for the measurement of thermal energy of a heating/
cooling circuit and the volume measurement given by the domestic hot and cold-water meters. The meter is
suitable for domestic applications with two-pipe systems, in a thermal power plant or any other compatible
application.
1. Screw the socket in the pipe
2. Insert the temperature sensor
3. Tighten the screw
1. Insert the probe into the threaded nut
2. Insert the closing pin
3. Unscrew the valve closing screw, and place the seal
4. Insert the probe by screwing it on the thread
4. Functionality
In residential systems, usually with two pipes systems, the measurement of thermal energy takes place on
a single section both in heating and cooling cycle. The picture below reports a typical connection diagram
(installation on return pipe):
6Subject to change without prior notice
EN
5. Display and buttons
The device is equipped at the front with an LCD and two buttons (T1 and T2), useful for device initialization and
readings.
1) Eight-digit numeric field;
2) Single-digit numeric index (menu level);
3) Heating data index;
4) Cooling data index;
5) Circuit 1-2 pulse emitter (external module);
6) Return temperature index;
7) Indicator of sub level presence;
8) Supply temperature index;
9) Battery level indicator;
10) Faults or NFC/IR active communication indicator;
11) Flow presence indicator;
12) M-Bus wired communication data index;
12+13) Wireless M-Bus data index;
13) LoRaWAN communication data index;
14) Historical index;
15) Pulse value index (k);
16) Measurement unit index;
T1) Levels selection button;
T2) Scroll button within the selected level.
6. Commissioning
Premise: before a functional tests, the procedures indicated in this paragraph must be performed for completing
the physical installation phases including the connections.
The device is delivered in sleep mode and it must be configured if not requested during the ordering phase.
The first configuration chosen during installation (supply or return pipe) can’t be modified!
Long press
T2 button
or
Set mode
with both
buttons
Set unit
with both
buttons
or
or
or
or
Long press
T2 button
Long press
T2 button
Long press
T2 button
7
Subject to change without prior notice
EN
Press T2 button for three seconds to initialize the device, if the installation version and the unit of measurement have
already been configured as requested during the order.
1. Installation version (set Mode): select, through the left/right button (T1/T2), the type of installation
(supply or return). Holding down the right button for 3 seconds can temporarily confirm the choice made by
switching to level 2 (unit of measurement). If the T1 button is pressed for 3 seconds the device will return to
stock mode showing ‘SLEEP’ on display.
If the activation takes place with buttons, the items in the menu will be two:
2. Units of measurement (set Unit): select through the left/right button (T1/T2), one of the following items: 1
(Joule), 2 (MJ), 3 (GJ), 4 (kWh), 5 (MWh).
Holding down the right button for 3 seconds can temporarily confirm the choice made by switching to level
2 (unit of measurement). If the T1 button is pressed for 3 seconds the device will return to stock mode
showing ‘set Mode’ on display.
NOTE: after confirmation the thermal energy meter will perform the initialization for heating and cooling
accounting. The unit of measurement can be changed later via NFC through the BMetering NFC Config app
for Android operating systems.
INITIALIZATION (Installation version and measuring unit already configured)
x=1
x=2
1
2
1) Check that the mounting position of the thermal energy meter and all electrical wiring are carried out
correctly
2) Check if the device is configured, otherwise set the installation version and the unit of measurement
3) Check at level 3 that all configured parameters are correct (heating and cooling data)
4) Check that the thermal energy meter, pulse devices, probes etc. are installed correctly (refer to the specific
installation manuals for each product)
5) Start the heating/cooling system:
→ Check the consistency of the reported values (energy and volume)
→ Check in level 2 the instant data
6) Check for errors
7) Apply installation seals. It’s recommended to lock the device with a password set through the BMETERING
NFC Config android app (downloadable from the Google Play Store).
PROCEDURE FOR COMMISSIONING
8Subject to change without prior notice
EN
7. Consultation menu
The consultation menu is divided into 9 levels by a numerical index always visible at the top left of the display.
By pressing the T1 button you can choose the desired level, while pressing the T2 button you can view the
sublevels of the preset level. After 60 seconds without iteration the display turns o. If no button is pressed
within 20 seconds (with the display o) the display cycle will start again from level 1. If a button is pressed
within 20 seconds (with the display o) the last level consulted will be displayed. In any level or sublevel,
holding down the T1 button for 3 seconds will direct the index to level 1. To access to a sublevels, where present
(indicate by the symbol ‘–‘), it is necessary to hold down the T2 button for 3 seconds. To return to a main level
from a sublevel it’s necessary to hold down the T2 button again for 3 seconds. Each level consists of a brief
indication in letters of the data that will be shown after a few seconds in a second screen.
1
1.1 HEAT J, MJ, GJ, kWh, MWh
1.2 COOL J, MJ, GJ, kWh, MWh
1.3 HEAT m�
1.4 COOL m�
1.5 ABSOLUTE m�
1.6 FORWARD m�
1.7 REVERSE m�
1.8 IN 1 J, MJ, GJ, kWh, MWh, Unit
1.9 IN 2 J, MJ, GJ, kWh, MWh, Unit
1.10 LOST m�
2
2.1 POWER H kW
2.2 POWER S W
2.3 HEAT J, Wh
2.4 FLOW m�/h
2.5 TEMP. SUPPLY °C
2.6 TEMP. RETURN °C
2.7 TEMP.DIFFERENCE °C
2.8 TEMP. AMBIENT. °C
3
3.1 SERIAL NUMBER
3.2 CRC FW
3.3 MAIN FW
3.4 RADIO FW
3.5 DISPLAY FW
3.6 INSTALL TYPE Supply, Return
3.7 DATE
3.8 TIME
3.9 UNIT 1,2,3,4,5
3.10 MODULE On, O
3.10.1 SERIAL Module’s serial number
3.10.2 FIRMWARE Module’s firmware
3.10.3 DATE
3.10.4 TIME
3.10.5 POLLING Synchronization interval
3.10.6 NEXT Next synchronization
3.10.7 LOST Missed communications
3.11 IN 1-2
3.11.1 IN 1 On, O
3.11.2 PULSE RATE Type of pulse
3.11.3 START VALUE Type of pulse
3.11.4 MEDIUM Type of pulse
3.11.5 IN 2 On, O
3.12 MBUS On, O
3.13 MONTHLY SAVE DAY
3.14 BIWEEKLY SAVE DAY
3.15 DATE SAVE MEM1
3.16 DATE SAVE MEM2
3.17 DATE SAVE ANNUAL
3.18 WMBUS TYPE WB, AMR, AMR CUSTOM, O
3.19 LORAWAN On, O
3.20 DISPLAY TEST
3.12.1 PRIMARY ADDRESS
3.12.2 SECONDARY ADDRESS
3.12.3 BAUD RATE BPS
3.11.6 PULSE RATE Type of pulse
3.11.7 START VALUE Type of pulse
3.11.8 MEDIUM Type of pulse
9
Subject to change without prior notice
EN
4
4.1 MEMORY DAY 1
4.2 MEMORY DAY 2
4.1.1 HEAT J, MJ, GJ, kWh, MWh
4.1.2 COOL J, MJ, GJ, kWh, MWh
4.1.3 IN 1 Type of pulse
4.1.4 IN 2 Type of pulse
4.2.1 HEAT J, MJ, GJ, kWh, MWh
4.2.2 COOL J, MJ, GJ, kWh, MWh
4.2.3 IN 1 Type of pulse
4.2.4 IN 2 Type of pulse
5
5.1 METER LIFE h
5.2 START COUNTING h
5.3 HEATING HOURS h
5.4 COOLING HOURS h
5.5 NO DELTA HOURS h
5.6 NO ERRORS HOURS h
6
6.xx* MONTHLY MEMORY 1
6.xx.1 HEAT J, MJ, GJ, kWh, MWh
6.xx.2 COOL J, MJ, GJ, kWh, MWh
6.xx.3 IN 1 Type of pulse
6.xx.4 IN 2 Type of pulse
6.xx.5 AVG. FLOW TEMP °C
6.xx.6 AVG. RET. TEMP °C
6.xx.7 AVG. CPU TEMP °C
6.xx.8 AVG. HEAT W
6.xx.9 AVG. FLOW m�/h
7
7.xx* ANNUAL MEMORY 1
7.xx.1 HEAT J, MJ, GJ, kWh, MWh
7.xx.2 COOL J, MJ, GJ, kWh, MWh
7.xx.3 IN 1 Type of pulse
7.xx.4 IN 2 Type of pulse
7.xx.5 AVG. FLOW TEMP °C
7.xx.6 AVG. RET. TEMP °C
7.xx.7 AVG. CPU TEMP °C
7.xx.8 AVG. HEAT W
7.xx.9 AVG. FLOW m�/h
8
8.1 ACTIVE ERRORS
8.xx* ERRORS CODE
9
9.xx* LOG MEM ERRORS
9.xx.1 ERROR DATA
9.xx.2 ERROR TIME
9.xx.3 ERROR COUNT
* xx equals an incremental index
NOTE: in absence of historical data, levels 6-7-9 will show - - (text).
9. Operating mode - M-Bus and pulse inputs activation
8. Operating mode – Radio activation
For wired M-Bus transmission or pulse inputs activation see the separated wired M-Bus or IR-MB-PULSE
documentation. Note: module compatible from Hydrocal-M4 serial number 05053000.
This section describes the radio communication management implemented. The WMBUS or LoRaWAN radio will
activate after the passage of ±5 litres. Pre-configured radio parameters (wM-Bus): AMR, 200s , everyday from 0 to
24h, encryption disabled, no historical data, standard package (standard data (heating energy, heating volume,
errors, battery value as a percentage). For more details see the specific wM-Bus or LoRaWAN documentation
obtainable by contacting the customer support.
RADIO INDICATOR ON DISPLAY
During the JOIN to the network procedure, if the LoRaWAN transmission has been activated, the radio symbol
will flash quickly on the display (at a period of 1 second) until the device reaches the JOINED state and then
remains always active. In the case of a failed JOIN the radio symbol turns o. In the case of WMBUS mode only
after switching +/- 5 liters the icon will remain permanently active. In the case of wired M-BUS mode
only after switching +/- 5 liters the icon will remain permanently active. The radio icon will flash
quickly during a transmission (LoRaWAN or wM-Bus) in cases where the device has reached the JOINED state or
when only wM-Bus mode is active.
During the wM-Bus and/or LoRaWAN test procedures, after starting the procedure via NFC app, the following
10 Subject to change without prior notice
EN
Error Name Description
03 Qmax Overflow The device operates at a flow rate greater than Q4 for 10 consecutive minutes.
06 Reverse installation Occurs during first installation only, when the absolute count (forward counter -
reverse counter) is equal to 0 and a reverse flow (>10 Liters) is detected.
08-09-10 Reserved Inform Customer Service
11 End of battery life The remaining battery life is less than 1 year. Permanent error, the icon is
shown on display.
12 Probe failure Failure, short circuit or tampering on supply or return probe(s).
13-14-15-16 Reserved Inform Customer Service
17 Wrong Real Time Clock Is recorded when a sudden reset of date and time is detected.
18 Supply Measurement out of range Measurement of the supply probe over the measuring range.
19 Return measurement out of range Measurement of the return probe over the measuring range.
21 Delta T non-compliant 24 continuous hours without flow and Delta T (temperature dierence) > 10°C.
25 Display Overflow The energy digits, based on the selected unit, exceed the display’s capacity
26-27 Reserved Inform Customer Service
35 MBUS disconnected The M-Bus communication is not detected for 2 consecutive hours.
36 Wrong module The external module has been removed and a second module is mounted.
10. Errors and anomalies
When one or more anomalies occur, the thermal energy meter will report the recorded error and show the
following icon on the display . If the NFC or IR interface is used, the icon will blink for the duration of the
communication. The register of all the anomalies present is shown at level 8 of the consultation menu, where
the abbreviation Ern followed by two digits identifies the anomaly.*
cases will be handled:
WMBUS_TEST_MSG: the icon will remain active for 1 minutes and will flash quickly on the display (at a
period of 1 second) with each wM-Bus package sent. After that time the icon will turn o.
LORA_TEST_JOIN: the radio icon will start flashing quickly on the display (at a period of 1 second).
If the join operation was successful, the icon will remain stable for 1 minute and then turn o otherwise it
will continue to flash until all join attempts are concluded. In the case of a forced join procedure, after the
passage of ±5 liters, the icon will flash throughout the 6 minutes cycle to various SFx and then remain on or o
depending on the outcome of the join request.
In the case of wired M-Bus mode only (after installing the module) the icon will remain permanently
active (if the M-Bus module is connected). If the module is installed and impulsive inputs are active, the icon
will activate permanently. If the module is momentarily disconnected, the icons and will start
flashing on the display (1 second intervals) up to a maximum of 4 attempts (based on the default) or on the
first successful reconnection. If the module is disconnected both icons described above will be deactivated. The
message ‘Mod ON’ will be shown on the display (for 10 seconds) when the communication procedure
between the meter and the module is concluded correctly.
11
Subject to change without prior notice
EN
* Per l’attivazione di allarmi opzionali che possono essere attivati tramite NFC o ulteriori dettagli fare riferimento al Manuale Utente reperibile sul sito www.bmeters.com
11. Battery and replacement procedures
The thermal energy meter constantly monitors the status of the battery (maximum life: 10 years*) and signals
the imminent discharge by showing the icon on display . Reporting takes place one year before full discharge.
For more details see the separated WMBUS specification document. For replacement, contact the manufacturer.
Do not recharge or replace the battery.
Do not open, puncture or damage the batteries.
Do not short-circuit the battery.
Do not expose the battery to temperatures above 85° C.
Do not expose the battery to an extremely low pressure
environment which could cause an explosion or a leak of
gases or flammable liquids.
Do not use naked flames near the device.
Do not put in contact with water.
Always use original spare parts authorized by the
manufacturer.
Do not insert into ovens, crush or cut: these actions
could cause an explosion or leakage of flammable
gases or liquids.
The thermal energy meter uses non-rechargeable batteries that, if misused, can be potentially dangerous. To reduce the
risks, you should take the following precautions.
37 Module removal The module is not detected for 5 consecutive failed communications.
38 End of battery life module The remaining battery life of the external module is less than 1 year.
39 Reserved Inform Customer Service
40 NFC Fraud An NFC field is detected for more than some minutes.
*The battery life strongly depends on the working time window, set during the
configuration process, and on the environmental conditions. Estimation of the
battery life is given by the configuration software.
12. Technical data
Model Hydrocal-M4
Power supply Batteries
Battery type LiMnO2, 2 x 3.0V
Battery life Maximum 10 years
Use temperature range +5 to +55°C
Storage temperature range -20 to +70°C
Dimensions 110 x 78 x 73 mm (DN15);
130 x 78 x 76 mm (DN20)
Degree of protection IP65
Weight 575g (DN15); 700g (DN20)
Liquid supported Water
Accuracy class 2
Environmental class A (E1, M1)
Display LCD, 8 digits + icons
Units of measurement J, MJ, GJ, KWh, MWh
Measurement temperature range
(heating) Θ: +1 °C - +90°C
Temperature range dierence
(heating) ΔΘ: 3 K - 90 K
Measuring temperature range
(cooling)* Θ: +0.2 °C - +90°C
Temperature range dierence
(cooling)* ΔΘ: 0.2 K - 90K
Counting operating conditions
(start)
Heating: ΔΘ≥1K (counting
enabling conditions)
Cooling: ΔΘ≥0.2K
Max. measurable power 650 kW
Pulse input (external module) 2 for impulsive device
Max. pulse input frequency 25 Hz
* The thermal energy calculation for heating application is MID certified.
The cooling energy calculation is not compliant with the MID regulation.
12 Subject to change without prior notice
EN
qp\qi ratio
Size qp (m�/h) Ratio qi (l/h)
DN15 0.6 50:1 12
DN15 1.5 50:1** 30
DN20 2.5 50:1** 50
**On request 100:1
13. Information for the correct disposal of the product
B METERS srl
Via Friuli, 3 • Gonars 33050 (UD) • ITALY E-mail (sales/info): [email protected]
E-mail (support): [email protected]
Web: www.bmeters.com
Tel: +39 0432 931415
Tel: +39 0432 1690412
Fax: +39 0432 992661
For the complete manual,
please refer to the product
page on our website →
This product falls within the scope of Directive 2012/19/EU on the management of waste electrical and electronic equipment (WEEE). The appliance should not
be disposed of with household waste as it is composed of dierent materials that can be recycled at the appropriate facilities. Inquire through the municipal
authority regarding the location of the ecological platforms suitable for receiving the product for disposal and its subsequent correct recycling. The product is
not potentially dangerous to human health and the environment, but if abandoned in the environment it negatively impacts the ecosystem. The symbol of the crossed-
out bin, present on the label placed on the appliance, indicates the compliance of this product with the legislation on waste electrical and electronic equipment. The
abandonment of the equipment in the environment or the abusive disposal of the same are punishable by law.
Installation
Selectable by the
customer, flow or return
on request
Temperature probes Digital
Homologation 2014/32/EU MID (Module
B) - EN1434
Probe cable length 1.5 m free probe
1 m internal probe

Other B meters Measuring Instrument manuals

B meters GSD534AF Operating manual

B meters

B meters GSD534AF Operating manual

B meters HYDROSPLIT R 21 User manual

B meters

B meters HYDROSPLIT R 21 User manual

B meters HYDRODIGIT-S1 User manual

B meters

B meters HYDRODIGIT-S1 User manual

B meters MAG User manual

B meters

B meters MAG User manual

B meters GMDM-I User manual

B meters

B meters GMDM-I User manual

B meters H7-BM1 User manual

B meters

B meters H7-BM1 User manual

B meters HYDROCAL-M4 User manual

B meters

B meters HYDROCAL-M4 User manual

B meters HYDROCAL-M4 Assembly instructions

B meters

B meters HYDROCAL-M4 Assembly instructions

B meters HYDRODIGIT-S1 User manual

B meters

B meters HYDRODIGIT-S1 User manual

B meters HYDROCLIMA 2 User manual

B meters

B meters HYDROCLIMA 2 User manual

B meters HYDROCLIMA 2 User manual

B meters

B meters HYDROCLIMA 2 User manual

B meters Hydrocal-M3 User manual

B meters

B meters Hydrocal-M3 User manual

B meters IWM-LR3 User manual

B meters

B meters IWM-LR3 User manual

B meters Hydrosplit-M3 User manual

B meters

B meters Hydrosplit-M3 User manual

B meters HYDRODIGIT User manual

B meters

B meters HYDRODIGIT User manual

B meters IWM-TX5 User manual

B meters

B meters IWM-TX5 User manual

B meters HYDROSONIS-UP User manual

B meters

B meters HYDROSONIS-UP User manual

B meters LORA-PULSE LORAWAN pulse User manual

B meters

B meters LORA-PULSE LORAWAN pulse User manual

B meters HYDROSONIC-M1 User manual

B meters

B meters HYDROSONIC-M1 User manual

B meters HYDROCAL-M4 User manual

B meters

B meters HYDROCAL-M4 User manual

Popular Measuring Instrument manuals by other brands

Turf-Tec Light-DLI-W quick start guide

Turf-Tec

Turf-Tec Light-DLI-W quick start guide

FormFactor ACP40-GSG Series Quick reference guide

FormFactor

FormFactor ACP40-GSG Series Quick reference guide

Keysight N5264A Service guide

Keysight

Keysight N5264A Service guide

Motorola R-2002A manual

Motorola

Motorola R-2002A manual

Magnetrol Thermatel series Measurement Handbook

Magnetrol

Magnetrol Thermatel series Measurement Handbook

Endress+Hauser analytikjena Biometra TMS operating manual

Endress+Hauser

Endress+Hauser analytikjena Biometra TMS operating manual

Fluke CableAnalyzer DSX-602 user manual

Fluke

Fluke CableAnalyzer DSX-602 user manual

Spectris Malvern Panalytical ZETASIZER NANO Basic guide

Spectris

Spectris Malvern Panalytical ZETASIZER NANO Basic guide

Oxford PRECISION OXD-315-2740F Operator's manual

Oxford PRECISION

Oxford PRECISION OXD-315-2740F Operator's manual

Hiwin MAGIC Assembly instructions

Hiwin

Hiwin MAGIC Assembly instructions

TELNET GPONDoctor 9500 user manual

TELNET

TELNET GPONDoctor 9500 user manual

RoboCam F12 Quick installation guide

RoboCam

RoboCam F12 Quick installation guide

PCB Piezotronics 351B31 Installation and operating manual

PCB Piezotronics

PCB Piezotronics 351B31 Installation and operating manual

Southwire 21005N operating instructions

Southwire

Southwire 21005N operating instructions

Kapro Prolaser 862 user manual

Kapro

Kapro Prolaser 862 user manual

Bosch vivatmo pro Instructions for use

Bosch

Bosch vivatmo pro Instructions for use

Young 81005A instructions

Young

Young 81005A instructions

Oakton PH200 instruction manual

Oakton

Oakton PH200 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.